10.4.2.1 Examples of Readouts of Demand Data
Introduction
In the following is a number of commented practical examples of demand data.
All data is in hexadecimal format. Comments are preceded by a semicolon.
Minimum values have the function field in the DIF set to 10 hex and maximum
values 01 hex.
Readout of demand data
System sends read request command for demand with date 14-08-17:
68 0A 0A 68 73 FE 51 02 EC FF F9 18 D1 18 A9 16
Meter sends out acknowledge:
E5
System sends out request UD2:
10 7B FE 79 16
Meter sends out data telegram 1:
68 CE CE 68 08 00 72 34 12 00 00 42 04 20 02 B2 00 00 00
;Data header
01 FD A5 00 0F
;Interval length 15 minutes
01 FF AB 00 01
;Subinterval length 1 minute
14 A9 FF F9 D1 00 66 33 00 00
;Current demand (storage number 0) for 1:st
max-imum total active power import, VIF A9 -> data in W with 2 decimals.
Data = 00003366 hex = 131.58 W
0E ED EB 00 00 15 00 16 08 14
;Date/time stamp for maximum given above:
16:th
of august 2014, 00:15:00 (hour:minute:second)
14 A9 FF F9 D2 00 6A 02 00 00
;Current demand (storage number 0) for 2:nd
maximum total active power import, VIF A9 -> data in W with 2 decimals.
Data = 0000026A hex = 6.18 W
0E ED EB 00 00 30 00 16 08 14
;Date/time stamp for maximum given above:
16:th
of august 2014, 00:30:00 (hour:minute:second)
14 A9 FF F9 D3 15 00 00 00 00
;Current demand (storage number 0) for 3:rd
maximum total active power import, status 15 hex -> no data available (data
set to 0 when not available)
0E ED EB 00 00 00 00 01 01 00
;Date/time stamp for maximum given above: Set
to 1:st of january 2000, 00:00:00 when data not available
24 A9 FF F9 D9 00 8C 01 00 00
;Current demand (storage number 0) for 1:st
minimum total active power import, VIF A9 -> data in W with 2 decimals.
Data = 0000018C hex = 3.96 W
Summary of Contents for A43
Page 1: ...A43 A44 User Manual ...
Page 40: ...Meter Settings A43 A44 40 2CMC48001M0201 User Manual Revision C ...
Page 55: ...Technical Description 2CMC48001M0201 55 A43 A44 Revision C User Manual ...
Page 58: ...Technical Description A43 A44 58 2CMC48001M0201 User Manual Revision C ...
Page 61: ...Technical Description 2CMC48001M0201 61 A43 A44 Revision C User Manual ...
Page 75: ...Technical Description 2CMC48001M0201 75 A43 A44 Revision C User Manual ...
Page 84: ...Measurement Methods A43 A44 84 2CMC48001M0201 User Manual Revision C ...
Page 91: ...Measurement Methods 2CMC48001M0201 91 A43 A44 Revision C User Manual ...
Page 95: ...Measurement Methods 2CMC48001M0201 95 A43 A44 Revision C User Manual ...
Page 102: ...Communication with Modbus A43 A44 102 2CMC48001M0201 User Manual Revision C ...
Page 107: ...Communication with Modbus 2CMC48001M0201 107 A43 A44 Revision C User Manual ...
Page 131: ...Communication with Modbus 2CMC48001M0201 131 A43 A44 Revision C User Manual ...
Page 147: ...Communication with Modbus 2CMC48001M0201 147 A43 A44 Revision C User Manual ...
Page 154: ...Communication with Modbus A43 A44 154 2CMC48001M0201 User Manual Revision C ...
Page 157: ...Communication with Modbus 2CMC48001M0201 157 A43 A44 Revision C User Manual ...
Page 161: ...Communication with Modbus 2CMC48001M0201 161 A43 A44 Revision C User Manual ...
Page 166: ...Communication with Modbus A43 A44 166 2CMC48001M0201 User Manual Revision C ...
Page 180: ...Communication with M Bus A43 A44 180 2CMC48001M0201 User Manual Revision C ...
Page 182: ...Communication with M Bus A43 A44 182 2CMC48001M0201 User Manual Revision C ...
Page 188: ...Communication with M Bus A43 A44 188 2CMC48001M0201 User Manual Revision C ...
Page 195: ...Communication with M Bus 2CMC48001M0201 195 A43 A44 Revision C User Manual ...
Page 254: ...Communication with M Bus A43 A44 254 2CMC48001M0201 User Manual Revision C ...
Page 257: ...Communication with M Bus 2CMC48001M0201 257 A43 A44 Revision C User Manual ...