Name
Type
Description
PF
REAL
Power factor magnitude of deadband value
PF_RANGE
INTEGER
Power factor range
ILAG
BOOLEAN
Current is lagging voltage
ILEAD
BOOLEAN
Current is leading voltage
U
REAL
Calculated voltage magnitude of deadband value
U_RANGE
INTEGER
Calcuated voltage range
I
REAL
Calculated current magnitude of deadband value
I_RANGE
INTEGER
Calculated current range
F
REAL
System frequency magnitude of deadband value
F_RANGE
INTEGER
System frequency range
14.1.2.4
Settings
Table 347:
CVMMXN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
-
-
A, B, C
Selection of measured current and voltage
PowAmpFact
0.000 - 6.000
-
0.001
1.000
Magnitude factor to scale power calculations
PowAngComp
-180.0 - 180.0
Deg
0.1
0.0
Angle compensation for phase shift between
measured I & V
k
0.00 - 1.00
-
0.01
0.00
Low pass filter coefficient for power
measurement
SLowLim
0.0 - 2000.0
%SB
0.1
80.0
Low limit in % of SBase
SLowLowLim
0.0 - 2000.0
%SB
0.1
60.0
Low Low limit in % of SBase
SMin
0.0 - 2000.0
%SB
0.1
50.0
Minimum value in % of SBase
SMax
0.0 - 2000.0
%SB
0.1
200.0
Maximum value in % of SBase
SRepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
PMin
-2000.0 - 2000.0
%SB
0.1
-200.0
Minimum value in % of SBase
Table continues on next page
Section 14
1MRK 502 048-UUS A
Monitoring
510
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...