Section 2
DNP3 data mappings
2.1
Overview
This document describes the DNP3 data points and structures available in
REF630 / REM630 / RET630 Ver. 1.0. The data points are unmapped as a default.
The point lists describe a superset of all data available including the optional
functionalities.
The point tables show all the available DNP3 data points in these IEDs. The DNP3
points can be freely added, removed, reorganized and reconfigured using PCM600.
As a default, the class assignments are Class 0 and Class 3 for binary inputs and
outputs and for double bit indications. The class assignment for analog inputs and
for counters are Class 0 and Class 2. Analog values are provided with default
scalings. The scalings can be freely modified by the user.
This list represents the superset of DNP3 points. The actual set of available points
depends on the product, optional functionalities and configuration.
See the engineering manual and DNP3 communication protocol
manual for more information.
2.2
Point list for 630 series IEDs
Table 2:
Signal point list
Function name
Signal type
Signal name
Description
Active Group (ACTVGRP)
Binary inputs
ACTVGRP.1.GRP1
Setting group 1 is active
ACTVGRP.1.GRP2
Setting group 2 is active
ACTVGRP.1.GRP3
Setting group 3 is active
ACTVGRP.1.GRP4
Setting group 4 is active
Automation bits (AUTOBITS)
Binary outputs
AUTOBITS.1.CMDBIT1
Command out bit 1
AUTOBITS.1.CMDBIT2
Command out bit 2
AUTOBITS.1.CMDBIT3
Command out bit 3
AUTOBITS.1.CMDBIT4
Command out bit 4
AUTOBITS.1.CMDBIT5
Command out bit 5
AUTOBITS.1.CMDBIT6
Command out bit 6
AUTOBITS.1.CMDBIT7
Command out bit 7
Table continues on next page
1MRS756791 A
Section 2
DNP3 data mappings
630 series
11
Point List Manual