ABB 616016-T2 Replacement Procedure Download Page 1

ABB 

ABB Inc. 

 

 

 

 

 

Address 
655 Century Point 

Telephone 
+1-407-732-2000 

Fax 
407-732-2029 

www.abb.com/mediumvoltage

 

 

March 24, 2005 
1VAL264211-HT 

Lake Mary, FL 32746 

1-800-929-7947 

 

 

 

 

 

 

 

 

 

 
 

 

PCD CPU Module Replacement Procedure  

 

Follow these instructions to replace the PCD CPU Type 2 modules.  

CPU Type 2 Part Number: 616016-T2  
Precautions 

 

The following precautions should be taken when replacing or servicing any of the PCD modules:  
1. Use antistatic precautions when handling modules. Always use antistatic bags for transporting modules  
2. Remove AC power 

and 

DC power from the PCD before removing, installing or wiring any of the PCD  

    modules.  
3. Incorrect wiring may result in damage. Before energizing the PCD verify that the connectors are  
    plugged into the correct locations and the wiring agrees with the connection diagram.  
4. Apply only the rated AC control voltage. 
 

Instructions 

 

The following instructions contain information required to correctly replace the PCD CPU Type 2 module, 
located in Slot D. 

 

1. Remove AC and DC system power from the PCD, following your company safety guidelines 

 

2. Locate the module labeled “CPU Type 2”, which is mounted Fourth from the left side when  

 

    facing the rear of the PCD in Slot D , see figures 1 & 2. 

 

3. Locate the mounting screw in the top center of the CPU Type 2 module. Remove the screw 

 

    and set aside.  

 

4. Locate the mounting screw in the bottom center of the CPU Type 2 module. Remove the screw and set  

 

     aside.  
5. Carefully remove the CPU Type 2 module from the relay housing and set aside. 

 

6. Carefully remove the replacement CPU Type 2 module from the packaging and insert into  

 

    the PCD chassis. Be certain to align the printed circuit board with the card guides in the  

 

     housing.  

 

7. Insert the mounting screws that were previously set aside and tighten.  

 

8. Reconnect DC then AC power and the PCD should power up normally.  
9. Once the new module is installed, you may get the following prompt on the LCD: “Modules  
     have changed, Press key to update”. If so, do the following: 

a)

 

Press the ENTER key. Prompt will appear: “Update Catalog number?”  

b)

 

Press the right arrow key to select “Yes” then press ENTER 

c)

 

The old style number will appear. Press the down arrow key once. 

d)

 

The new style number will appear. Press the down arrow key once. 

e)

 

Prompt will appear: “Confirm Update?” Press the right arrow key to select “Yes”. 

f)

 

A password prompt will appear. Press ENTER to proceed, as the default password is 4 spaces. 

g)

 

After the modules have been updated, reset the PCD by pressing the reset button on the rear of the 
CPU module. The Self Check LED at the right hand side center of the faceplate should now be 
GREEN. If it is RED call ABB for assistance. 

h)

 

All settings on the PCD are stored in the CPU card. Therefore, after installing the new CPU card, 
the desired protection setting will need to be reprogrammed into the unit. 

 

 
 
 
 
 