1MAC050144-MB C
Section 8
Measurement functions
615 series ANSI
593
Technical Manual
8.13.2
Function block
Figure 319:
Function block symbol
8.13.3
Signals
Table 500: F Input signals
8.13.4
Settings
Table 501: F Non group settngs
8.13.5
Monitored data
Table 502: FMMXU Monitored datas
F
Name
Type
Default
Description
F
SIGNAL
-
Measured system frequency
Parameter
Values (Range) Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
F high high limit
35.00...75.00
Hz
60.00
High alarm frequency limit
F high limit
35.00...75.00
Hz
55.00
High warning frequency limit
F low limit
35.00...75.00
Hz
45.00
Low warning frequency limit
F low low limit
35.00...75.00
Hz
40.00
Low alarm frequency limit
F deadband
100...100000
1000
Deadband configuration value for integral
calculation (percentage of difference
between min and max as 0,001 % s
name
Type
Values (Range)
Unit
Description
f Hz
FLOAT32
35.00...75.00
Hz
Measured frequency
F_INST
FLOAT32
35.00...75.00
Hz
Frequency instantaneous value
F_DB
FLOAT32
35.00...75.00
Hz
Frequency reported value
F_RANGE
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Measured frequency range
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......