Section 8
1MAC050144-MB C
Measurement functions
554
615 series ANSI
Technical Manual
8.5.4
Settings
Table 464: VA, VB, VC Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
1=Enable
Operation Off / On
Measurement mode
1=RMS
2=DFT
2=DFT
Selects used
measurement mode
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases
required by limit
supervision
V high high limit
0.00...4.00
xVn
1.40
High alarm voltage
limit
V high limit
0.00...4.00
xVn
1.20
High warning voltage
limit
V low limit
0.00...4.00
xVn
0.00
Low warning voltage
limit
V low low limit
0.00...4.00
xVn
0.00
Low alarm voltage
limit
V deadband
100...100000
10000
Deadband
configuration value
for integral
calculation.
(percentage of
difference between
min and max as
0,001 % s)