1MAC050144-MB C
Section 4
Protection functions
615 series ANSI
161
Technical Manual
Table 148: 50N/G-3 Group settings
Table 149: 50N/G-3 Non group settings
4.1.4.10
Monitored data
Table 150: 51N/G and 50SEF Monitored data
Table 151: 50N/G-1/2 Monitored data
Table 152: 50N/G-3 Monitored data
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
1.00...40.00
xIn
0.01
1.00
Pickup value
Pickup value mult
0.8...10.0
0.1
1.0
Multiplier for scaling the pickup value
Trip delay time
20...200000
ms
10
20
Trip delay time
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Reset delay time
0...60000
ms
1
20
Reset delay time
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
51N/G and 50SEF
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
50N/G-1/2
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
50N/G-3
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......