1MAC050144-MB C
Section 3
Basic functions
615 series ANSI
101
Technical Manual
Figure 41:
A = Trip pulse is shorter than Cold load time setting, B = Trip pulse is
longer than Cold load time setting
3.13.3
Local/remote control function block CONTROL
3.13.3.1
Function block
Figure 42:
Function block
3.13.3.2
Functionality
Local/Remote control is by default realized through the R/L button on the front panel. The
control via binary input can enabled by setting the value of the
LR control
setting to
"Binary input".
The actual Local/Remote control state is evaluated by the priority scheme on the function
block inputs. If more than one input is active, the input with the highest priority is selected.
The actual state is reflected on the CONTROL function outputs. Only one output is active
at a time.
CONTROL
CTRL_LOC
CTRL_OFF
OFF
LOCAL
CTRL_REM
CTRL_STA
STATION
REMOTE