Installing Block I/O
Chapter 2
2-7
Figure 2.7
Wiring Connections for the 120V ac Analog Block with Current Input and
CustomerSupplied Loop Power
RIO
1
30
L2/N
L1
L1
GND
N
NOT
USED
NOT
USED
BLU
SHD
in V0
CLR
in I0
in V1
+24
Vdc
RET
in0
GND
in0
RET
in1
GND
in1
RET
in2
GND
in2
RET
in3
GND
in3
RET
out0
RET
out1
in I1
in V2
in I2
in V3
in I3
out0
out1
NOT
USED
User Analog
Input Device
+
-
User Analog
Output Device
+
-
User +24V User GND
Analog signals must be within the
10V common mode voltage range
which is referenced to the analog
input common (GND). Typically, this
is accomplished by connecting to
user ground. If an input channel
floats outside of this range, invalid
input readings will result.
Current Input
Output
ATTENTION:
The 249 ohm
input current shunt is rated
at 0.25 Watts. Do not
exceed this rating.
Figure 2.8
Wiring Connections for the 24V dc Analog Block with Current Input and
CustomerSupplied Loop Power
RIO
1
30
+24
GND
RET
+24
NOT
USED
NOT
USED
BLU
SHD
in V0
CLR
in I0
in V1
+24
Vdc
RET
in0
GND
in0
RET
in1
GND
in1
RET
in2
GND
in2
RET
in3
GND
in3
RET
out0
RET
out1
in I1
in V2
in I2
in V3
in I3
out0
out1
NOT
USED
User Analog
Input Device
+
-
User Analog
Output Device
+
-
User +24V User GND
Current Input
Output
ATTENTION:
The 249 ohm
input current shunt is rated
at 0.25 Watts. Do not
exceed this rating.
+24V dc
Supply
+
-
Analog signals must be within the
10V common mode voltage range
which is referenced to the analog
input common (GND). Typically,
this is accomplished by connecting
to user ground. If an input channel
floats outside of this range, invalid
input readings will result.