background image

-20°C to +55°C (-4°F to +131°F)

UL Type 4/4X/13/3R

Disconnect from power source to prevent electrical shock before installing 

or servicing. Check power supply voltage and frequency. 

 

Déconnecter l’alimentation avant toute opération d’installation ou de maintenance, 

afin d’éviter les décharges électriques. Controler la tension et la fréquence d’alimentation. 

Scollegare dall’alimentazione prima dell’installazione e della messa in servizio. 

Controllare la tensione di alimentazione e la frequenza. 

Desligar a alimentação antes de realizar qualquer intervenção. Verificar a tensão e 

frequência da alimentação. 

Durante el proceso de instalación o mantenimiento desconectar la tensión de 

alimentación para evitar descargas eléctricas. Comprobar tensión y frecuencia de alimentación. 

Schalten Sie den Strom während der Installation oder bei Wartungsarbeiten ab um  

einen elektrischen Schlag zu vermeiden. Prüfen Sie die Spannung und Frequenz der Stromquelle. 

WARNING

AVERTISSEMENT

WARNUNG

AVVERTENZA

ATENÇÃO

ADVERTENCIA

  
 

 

 

 

Bulletin 855H Recordable Horn  

   

    (Frame C)

855H-R30C, 855H-R45C, 855H-RC30Cx, 855H-RC45Cx

IP66

Wiring practices must meet applicable electrical codes.

Les procédures de câblage doivent répondre aux codes électriques en vigueur.

Bei der Verdrahtung sind die geltenden elektrotechnischen Sicherheitsvorschriften zu befolgen.

Le procedure adottate per i cavi devono rispettare le codifiche elettriche applicabill.

A instalação da fiação deve atender aos códigos elétricos aplicáveis.

Las prácticas de instalación eléctrica deben seguir los códigos eléctricos. 

FEATURES:






4 stages - Each stage can record up to 30 seconds of CD quality audio
Record via on-board microphone or from external source using audio input jack
Message can be played back preceded by one of forty five alarm tones, or without any alarm tone if desired
Master / Slave functionality allows multiple horns to be set up exactly the same way
Optional high-output LED beacon available
Horn / LED combination units allow user to select steady or flashing LED function (2 Hz flash rate)

OPERATING AND MARKING:

All units have the following operating requirements and limitations.

855H Horn only units:

Catalog No. 

Voltage Range

Current

855H-R30C          10-30V DC                190mA@12V

                                                               256mA@24V

                                                               256mA max@30V

855H-R45C           90-260V AC             112mA@120V

                               (50/60Hz)                124mA@230V

                                                               127mA max@260V

855H Combined horn/LED units:

Catalog No. 

Voltage Range

Current

855H-RC30Cx     12-30V DC                347mA@12V

                                                              413mA@24V

                                                              416mA max@30V

855H-RC45Cx      90-260V AC             172mA@120V

                              (50/60Hz)                159mA@230V

                                                              252mA max@260V

Prior to use, the unit will need to be configured to suit the end user.

If recording either via the onboard microphone or the line-in jack, the unit will need to be supplied with power.

Important Note:

 For all versions, a source of DC power is required.


HORN SET-UP AND RECORDING

DC units (855H-R30C and 855H-RC30Cx) can be powered normally to complete recording and set-up.
AC units (855H-R45C and 855H-RC45Cx) must be temporarily powered from either a 12V battery or a

separate 10-30VDC isolated power supply, connected directly to the + and - DC terminals on the main PCB.

(Layout of main PCB is illustrated on page 5).

Risk of Electrical Shock. Disconnect from power source to prevent electrical 

shock before servicing. 

WARNING

  

1

Sound Output @ 1 meter: 

101 dB (A) Voice     102 dB (A) Music    110 dB (A) Tone

Hearing protection required.

 


Summary of Contents for 855H Series

Page 1: ...os FEATURES 4 stages Each stage can record up to 30 seconds of CD quality audio Record via on board microphone or from external source using audio input jack Message can be played back preceded by one of forty five alarm tones or without any alarm tone if desired Master Slave functionality allows multiple horns to be set up exactly the same way Optional high output LED beacon available Horn LED co...

Page 2: ...ONS DC UNITS AC UNITS TONE SELECTION The 855H Recordable Horn has 45 different tones See page 12 that can be selected for the first stage alarm The unit can then be switched to sound second third and fourth stage alarm tones The tones are selected by operation of DIP switch S4 on the main PCB The tone selection table page 12 shows the switch positions for the 45 tones and which tones are available...

Page 3: ...damaged WARNING DC CIRCUIT WIRING DIAGRAM CUSTOMER SUPPLIED SWITCHES See PCB layout on page 5 for actual terminal block positions BEACON PRE WIRED INTERNALLY TERMINALS ON MAIN PCB Beacon Sounder S4S3S2 S4 S3 S2 3 AC Units Second Third and Fourth Stage Selection Connect correct AC input voltage to L and N as appropriate AC Units Stage 1 operation The 855H Recordable Horn uses Line switching to chan...

Page 4: ... The 855H Combo units will have the beacon already pre wired to the unit so no extra wiring is required Beacon will activate when any stage is energized BEACON SET UP The LED beacon is factory set to the 2Hz flash mode but it can easily be set to steady mode if desired To alter the settings change the position of the header pin as shown Remove header for steady mode Keep header in standard positio...

Page 5: ...s Peak level LED On board microphone Audio Line in Jack J3 Jumpers Alarm Tone Voice Recorded Content Volume Controls MAIN PCB LAYOUT 5 Master Slave Connector Beacon pre wired to and DC combo units only 7 2 3 4 5 6 ON 1 6 ON 1 2 3 4 5 ACTION RESET ON RA R E TA ME SYNC S M OFF ON PEAK MIC LINE IN MAX MIN S2 S3 S4 ...

Page 6: ...corded stages and also reset the unit Once the user has configured the unit it must be put into its Playback Mode and S2 switches set to stage 1 as shown in Quick Ref Playback Mode Stage 1 illustrated guide below OFF Position Function Record Mode Stage selection switch Stage selection switch Line In selected Program Record Erase Mode ON Message Tone Playback Single Message or Mass Erase Mode OFF S...

Page 7: ...o the microphone The peak detector LED should flash regularly to maintain a good recording level However if it stays on for most of the time the recording may be distorted Press action button Stop recording TO RECORD FROM LINE IN JACK J3 INSTEAD OF THE ON BOARD MICROPHONE Ensure that the audio cable is connected from the message source to jack J3 before recording Follow above step 1 but set Switch...

Page 8: ... Stage 2 Set Switch S2 positions 1 3 5 to ON For Stage 3 Set Switch S2 positions 1 2 5 to ON For Stage 4 Set Switch S2 positions 1 5 to ON 2 Switch on power or Press reset button 3a 8 Unit will sound alarm tone if selected and then recorded content repeatedly If no alarm tone selected then recorded content only TA R E RA ON TA R E RA ON TA R E RA ON ...

Page 9: ...positions 2 3 7 to ON Alternatively For Stage 2 Set Switch S2 positions 3 7 to ON For Stage 3 Set Switch S2 positions 2 7 to ON For Stage 4 Set Switch S2 position 7 to ON 2 Switch on power or Press reset button 3a Press action button Erase will begin 3b erase complete 9 TA R E RA ON TA R E RA ON TA R E RA ON TA R E RA ON ...

Page 10: ...t jumper J4 ME to ON position centre and right pin connected 3 Switch on power or Press reset button 4a Press action button Erase will begin 4b erase complete 5 Reset Jumper J4 ME to OFF position NOTE The Mass Erase mode will also reset the unit to factory settings 10 TA R E RA ON TA R E RA ON TA R E RA ON TA R E RA ON ...

Page 11: ...witches and jumper J4 ME does not affect synch operation 3 Apply power to the Master unit first Then apply power to the Slave unit Master Unit Slave Unit 4a Press action button on the Master Unit Synchronisation will begin Master Unit Slave Unit 4b Synchronisation complete Switch off Power to units Master Unit Slave Unit 5 On both units Reset on jumper J6 SYNC to OFF Set jumper J5 S M on both unit...

Page 12: ... 13 2400 Hz 1 Hz Intermittent Tone 14 800 Hz 0 25 sec on 1 sec off Intermittent Tone 15 800 Hz Continuous Tone 16 660 Hz 150mS on 150 mS off Intermittent Tone 17 544 Hz 100mS 440 Hz 400mS NF S 32 001 Tone 18 660 Hz 1 8sec on 1 8sec off Intermittent Tone 19 1 4KHz 1 6KHz 1s 1 6KHz 1 4KHz 0 5s NFC48 265 Tone 20 660 Hz Continuous Tone 21 554 Hz 440 Hz 1 Hz Alternating Tone 22 544 Hz 0 875 sec Intermi...

Reviews: