ControlLogix EtherNet/IP Bridge Module
17
Publication
1756-IN019C-EN-P - November 2004
Link Status Indicator
The Link Status LED provides the following information:
OK Status Indicator
The OK Status LED provides the following module information:
Where to Find Information on Configuring the Module
To configure your module, refer to the configuration chapter of your
EtherNet/IP Modules User Manual, publication number ENET-UM001,
available online at www.rockwellautomation.com/literature.
State
Status
Description
Off
No data transmission
Module is not ready to communicate.
Green
Ready
Module is ready to communicate.
Flashing Green
Data transmission in
progress
Module is communicating over the
network.
State
Status
Description
Off
No Power
Module does not have 24V DC power.
Verify there is chassis power and the
module is completely inserted into
chassis and backplane.
Flashing Green
Standby
Module is not configured.
Green
Operational
Module is operating correctly.
Flashing Red
Minor Fault
A recoverable fault has been detected.
This could be caused by an error in the
configuration.
Red
Major Fault
An unrecoverable fault has been
detected. Recycle power to the module.
If this does not clear the fault, replace
the module.
Flashing Red and Green Self Test
Module performing power-up self-test.
Summary of Contents for 1756-ENBT ControlLogix
Page 38: ...18 ControlLogix DC 10 31 2V Input Module Publication 1756 IN031D EN P February 2003 Notes ...
Page 39: ...ControlLogix DC 10 31 2V Input Module 19 Publication 1756 IN031D EN P February 2003 Notes ...
Page 63: ...ControlLogix Voltage Current Input Module 23 Publication 1756 IN039D EN P February 2003 Notes ...
Page 151: ...ControlLogix Voltage Current Output Module 19 Publication 1756 5 42 September 1999 ...