![AB Quality 1756-ENBT ControlLogix Installation Instructions Manual Download Page 144](http://html.mh-extra.com/html/ab-quality/1756-enbt-controllogix/1756-enbt-controllogix_installation-instructions-manual_450632144.webp)
12
ControlLogix Voltage/Current Output Module
Publication 1756-5.42 - September 1999
Install the Removable Terminal Block onto the Module
Before installing the RTB, make certain:
•
field-side wiring of the RTB has been completed.
•
the RTB housing is snapped into place on the RTB.
•
the RTB housing door is closed.
•
the locking tab at the top of the module is unlocked.
ATTENTION
!
6KRFNKD]DUGH[LVWV
If the RTB is installed onto the module
while the field-side power is applied, the RTB will be
electrically live. Do not touch the RTB’s terminals. Failure to
observe this caution may cause personal injury.
The RTB is designed to support Removal and Insertion
Under Power (RIUP). However, when you remove or insert
an RTB with field-side power applied,
XQLQWHQGHGPDFKLQH
PRWLRQRUORVVRISURFHVVFRQWUROFDQRFFXU
. Exercise extreme
caution when using this feature. It is recommended that
field-side power be removed before installing the RTB onto
the module.
20853–M
20854–M
Top
guide
Left-side guides
Bottom guide
Locking
tab
Align the top, bottom and left
side guides of the RTB with
the guides on the module.
Press quickly and evenly to seat
the RTB on the module until the
latches snap into place. Slide
the locking tab down to lock the
RTB onto the module.
Summary of Contents for 1756-ENBT ControlLogix
Page 38: ...18 ControlLogix DC 10 31 2V Input Module Publication 1756 IN031D EN P February 2003 Notes ...
Page 39: ...ControlLogix DC 10 31 2V Input Module 19 Publication 1756 IN031D EN P February 2003 Notes ...
Page 63: ...ControlLogix Voltage Current Input Module 23 Publication 1756 IN039D EN P February 2003 Notes ...
Page 151: ...ControlLogix Voltage Current Output Module 19 Publication 1756 5 42 September 1999 ...