92
Removal
Disconnect all wiring on the heat exchanger.
Disconnect flex gas lines and pull out of the
way.
Remove screws around the perimeter of the
heat exchanger face plate that connect it to
the unit. Only the outermost screws should be
removed.
Pull the heat exchanger straight back and out
of the unit. It may be necessary to remove
some of the control door jambs.
Reinstallation
Ensure that the neoprene isolator is installed
around the perimeter of the heat exchanger.
Insert heat exchanger into opening so that the
back of the main plate is against the unit
bulkhead.
Figure 41 - Gas Heat Exchanger
Attach the heat exchanger to the bulkhead
using the holes around the perimeter.
Connect flex gas lines to the piping on the
heat exchanger. If flexible gas piping in the
unit must be replaced connectors cannot be
reused, only new connectors may be used.
Connect wiring per the wiring diagram on the
controls compartment door.
Purge gas lines to the gas valves at the unit.
Phase and Brownout Protection Module
The DPM is a Digital Phase Monitor that
monitors line voltages from 200VAC to
240VAC 1
ɸ
and 200VAC to 600VAC 3
ɸ
.
The DPM is 50/60 Hz self-sensing. DPM
must be wired according to unit specific
wiring diagram include in the control
compartment
When the DPM is connected to the line
voltage, it will monitor the line and if
everything is within the setup parameters, the
output contacts will be activated. If the line
voltages fall outside the setup parameters, the
output relay will be de-energized after the trip
delay.
LEAK CHECK GAS PIPE
The gas pipe in the unit must be
checked for leaks before startup. Leak
checking is the responsibility of the
installing contractor. All connections
must be checked for leaks annually
after installation. Failure to leak check
could result in fire, explosion, or other
hazardous situations.
DANGER