61
time to clear any liquid accumulation out of
the compressor before it is started.
Always control the unit from the control
panel, never at the main power supply, except
for emergency or complete shutdown of the
unit.
During the cooling season, if the airflow is
reduced due to dirty air filters or any other
reason, the cooling coils can get too cold
which will cause excessive liquid to return to
the compressor. As the liquid concentration
builds up, oil is washed out of the
compressor, leaving it starved for lubrication.
Compressor life will be shorted by reduced
lubrication and the pumping of excessive
amounts of liquid oil and refrigerant.
Note: Low Ambient Operation
Air-cooled DX units without a low ambient
option, such as condenser fan cycling or the
0°F low ambient option, will not operate in
the cooling mode of operation properly when
the outdoor temperature is below 55°F. Low
ambient and/or economizer options are
required if cooling operation below 55°F is
expected.
Note: Multiple Units with Multiple Unit
Controllers
When several heating and cooling units are
used to condition a space, all unit controllers
must be set in either heating mode, cooling
mode or off. Do not leave part of the units
switched to the opposite mode. Cooling only
units must be switched off during the heating
season.
Evaporator Coil
Removal
Isolate the evaporator section and recover the
refrigerant in that section. Make sure to
weigh the amount of refrigerant recovered.
Remove the expansion valve bulbs and/or the
valve controller from the suction lines.
Disconnect the suction and liquid line copper
connections to the evaporator coil.
Depending on the configuration, remove
additional components such as filters, reheat
coils or UV lights to allow the coil to be
removed.
Remove screws attaching access side, back,
and top blank-off panels to the evaporator
coil and the unit.
Remove the evaporator coil through the door
opening.
Reinstallation
Place the evaporator coil back in the unit
drain pan. There should be about a 1/4” gap
between the upstream side of the coil and the
back of the drain pan.
Secure the coil to the back wall of the unit
with the blank-off panel. Attach the top and
access side blank-off panels to the coil.
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
WARNING
Polyolester (POE) and Polyvinylether
(PVE) oils are two types of lubricants
used in hydrofluorocarbon
(HFC)
refrigeration systems. Refer to the
compressor label for the proper
compressor lubricant type.
CAUTION