51
service manifold must be attached prior to
filter maintenance.
Figure 26 - Replaceable Core Liquid
Filter/Driers Suction Filter
In an effort to help protect the compressors
from contaminants during testing and startup,
AAON factory installs pleated replaceable
core suction line filters on the RZ Series.
Figure 27 - RPE-48-BD filter element
One month after startup, remove the RPE-48-
BD filter element for the lowest possible
pressure drop. Removing the suction line
filter will improve the efficiency and capacity
of the unit. AAON installs isolation ball
valves on both sides of the suction line filter
so the complete system will not have to be
reclaimed/evacuated.
Suction Filter Removal Instructions
1.
Shut down operation of the unit
2.
Close both shut-off valves to isolate
the suction filter
3.
Reclaim the refrigerant from the
suction filter section
4.
Remove the bolts from the suction
filter end plate
5.
Remove the pleated filter assembly
6.
Replace the suction filter end plate
and bolts