38
Electrical
Verify the unit nameplate agrees with power supply. Connect power and control field wiring as
shown on the unit specific wiring diagram provided laminated and attached to the door in the
controls compartment.
Table 4 - Nameplate Voltage Markings & Tolerances
Hz
Nameplate
Voltage
Nominal
System
Voltage
Operating Voltage Range
1
Acceptable Performance
Range
2
Min
Max
Min
Max
60
115
120
104
127
108
126
208/230
208/240
187
254
187
252
208
208
187
228
187
228
230
240
208
254
216
252
265
277
240
293
249
291
460
480
416
508
432
504
575
600
520
635
540
630
50
230
230
198
254
208
254
400
400
344
440
360
440
Notes:
1.
Operating voltage is the min and max voltage for which the unit can function. Never
operate outside of this min and max voltage.
2.
The Acceptable Performance Range is the min and max voltage for which the unit
performance is designed and rated to give acceptable performance.
Route power and control wiring, separately,
through the utility entry in the base of the
unit. Do not run power and signal wires in the
same conduit.
Size supply conductors based on the unit
MCA rating. Supply conductors must be
rated a minimum of 167°F (75°C).
Protect the branch circuit in accordance with
code requirements. The unit must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the
current
National
Electric
Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Electric
shock
hazard.
Before
attempting to perform any installation,
service, or maintenance, shut off all
electrical power to the unit at the
disconnect switches. Unit may have
multiple power supplies. Failure to
disconnect power could result in
dangerous operation, serious injury,
death or property damage.
WARNING
Installing Contractor is responsible for
proper sealing of the electrical and
gas entries into the unit Failure to seal
the entries may result in damage to
the unit and property.
CAUTION
Summary of Contents for RZ Series
Page 2: ......
Page 31: ...31 Figure 4 4 Point Lift RZ Series Air Cooled Condenser Unit ...
Page 90: ...90 Gas Heater Operating Instructions ...
Page 108: ...108 Maintenance Log E Coated Coil ...
Page 110: ...110 ...
Page 111: ......