Size supply conductors based on the unit
MCA rating. Supply conductors must be
rated a minimum of 75°C (167
°
F).
Protect the branch circuit in accordance with
code requirements. The unit must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the current National Electric Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Note:
All units are factory wired for 208V,
230V, 380V, 460V, or 575V. The
transformer configuration must be checked
by a qualified technician prior to service,
especially if unit is to be connected to a 208V
or 230V supply. For 208V service
interchange the yellow and red conductor on
the low voltage control transformer.
Red-Black for 208V
Yellow-Black for 230V
Wire power leads to the unit’s terminal block
or main disconnect. All wiring beyond this
point has been completed by the
manufacturer and cannot be modified without
affecting the unit’s agency/safety
certification.
Available short circuit current must not
exceed the short circuit current rating
(SCCR) shown on the unit nameplate.
Three phase voltage imbalance will
cause motor overheating and
premature failure.
CAUTION
Utility Entry
Field
Connection
Location
Summary of Contents for RQ NextGen Series
Page 2: ......
Page 26: ...26 Figure 3 RQ Cabinet Standard and Power Exhaust Gasket Locations...
Page 40: ...40 Figure 23 Post Corner Hole Piping Figure 24 Post Back Hole Piping...
Page 88: ...88 Gas Heater Operating Instructions Figure 36 Gas Heater Instructions...
Page 95: ...95...
Page 96: ...96...
Page 105: ...105 Maintenance Log E Coated Coil...
Page 107: ...107...