80
Piping systems must not exceed 10 ft/sec
fluid velocity to ensure tube wall integrity
and reduce noise.
Energy Recovery Units
Some RN units have been equipped with an
energy recovery wheel. AAON provides
options for either an aluminum energy
recovery wheel or a polymer energy recovery
wheel. Follow the instructions for the
specific type of energy recovery wheel in
your installed equipment.
Initial Mechanical Check and Setup
Outdoor units equipped with outside air
intake will have an outside air hood. The
outside air hood must be opened prior to unit
operation.
Outdoor air intake adjustments must be made
according to building ventilation, or local
code requirements.
After the unit installation is complete, open
the cassette access door and determine that
the energy wheel rotates freely when turned
by hand. Apply power and observe that the
wheel rotates. If the wheel does not rotate
when power is applied, it may be necessary
to readjust the “diameter air seals”.
Airflow Balancing and Checking
High performance systems commonly have
complex air distribution and fan systems.
Unqualified personnel must not attempt to
adjust fan operation, or air circulation, as all
systems
have
unique
operations
characteristics. Professional air balance
specialists must be employed to establish
actual operating conditions, and to configure
the air delivery
system for optimal
performance.
Controls
A variety
of controls
and electrical
accessories may be provided with the
equipment. Identify the controls on each unit
by consulting appropriate submittal, or order
documents, and operate according to the
control manufacturer’s instructions. If you
cannot locate installation, operation, or
maintenance information for the specific
controls,
then
contact
your
sales
representative, or the control manufacturer
for assistance.
Installing contractor is responsible for
properly sizing and installing water
system components. Improper fluid
flow due to valves, piping, or improper
pump
operation
may
result
in
unacceptable unit operation and void
warranty.
CAUTION
Improper
installation,
adjustment,
alteration, service or maintenance can
cause property damage, personal
injury or loss of life. Startup and
service must be performed by a
Factory Trained Service Technician.
WARNING
Do not alter factory wiring. Deviation
from the supplied wiring diagram will
void all warranties, and may result in
equipment damage or personal injury.
Contact the factory with wiring
discrepancies.
WARNING
Summary of Contents for RN Series
Page 2: ......
Page 32: ...32 Figure 5 RN Series 6 8 and 10 ton Unit Isolator Locations ...
Page 33: ...33 Figure 6 RN Series 9 and 11 15 ton Unit Isolator Locations ...
Page 34: ...34 Figure 7 RN Series 16 25 and 30 ton Unit Isolator Locations ...
Page 35: ...35 Figure 8 RN Series 26 31 50 60 and 70 ton Unit Isolator Locations ...
Page 36: ...36 Figure 9 Steel Mounting ...
Page 102: ...102 Figure 56 Example 6 50 60 70 ton through the Base Gas Piping ...
Page 105: ...105 Gas Heater Operating Instructions Figure 58 Gas Heater Instructions ...
Page 129: ...Maintenance Log E Coated Coil ...