Three phase voltage imbalance will cause
motor overheating and premature failure.
The maximum allowable imbalance is 2%.
Voltage imbalance is defined as 100 times the
maximum deviation from the average voltage
divided by the average voltage.
Example:
(221V+230V+227V)/3
=
226V,
then
100*(226V-221V)/226V
= 2.2%, which
exceeds the allowable imbalance.
Check voltage imbalance at the unit
disconnect switch and at the compressor
terminal. Contact your local power company
for line voltage corrections.
Installing contractor must check for proper
motor rotation and check blower motor
amperage listed on the motor nameplate is
not exceeded. Motor overload protection may
be a function of the variable frequency drive
and must not be bypassed.
Wire control signals to the unit’s low voltage
terminal block located in the controls
compartment.
Variable Speed Compressors
Variable speed compressors with VFD speed
control are available on 7-13, 15, 16, 20, 25,
30, 55, 65 and 75-140 ton units. Variable
speed compressors must not be operated
outside the factory determined turndown
ratio or frequency range. The factory
determined compressor VFD ranges are
given in the following tables.
Table 7 - RN-A through C Cabinet Variable
Speed Compressor Turndown Ratio
Model (RN-)
Compressor
Turndown Ratio
007
17%
008
15%
009
10%
010
20%
011
10%
013
10%
015
12%
016
20%
020
12%
025
15%
030
15%
Three phase voltage imbalance will
cause
motor
overheating
and
premature failure.
CAUTION
Rotation must be checked on all
MOTORS AND COMPRESSORS of
three phase units. Supply fan, exhaust
fan, return fan, and condenser fan
motors must all be checked by a
qualified service technician at startup
and any wiring alteration must only be
made at the unit power connection.
CAUTION
Scroll compressors are directional
and will be damaged by operation in
the wrong direction. Low pressure
switches on compressors have been
disconnected after factory testing.
Rotation must be checked by a
qualified service technician at startup
using suction and discharge pressure
gauges and any wiring alteration must
only be made at the unit power
connection.
CAUTION
Summary of Contents for RN Series
Page 2: ......
Page 32: ...32 Figure 5 RN Series 6 8 and 10 ton Unit Isolator Locations ...
Page 33: ...33 Figure 6 RN Series 9 and 11 15 ton Unit Isolator Locations ...
Page 34: ...34 Figure 7 RN Series 16 25 and 30 ton Unit Isolator Locations ...
Page 35: ...35 Figure 8 RN Series 26 31 50 60 and 70 ton Unit Isolator Locations ...
Page 36: ...36 Figure 9 Steel Mounting ...
Page 102: ...102 Figure 56 Example 6 50 60 70 ton through the Base Gas Piping ...
Page 105: ...105 Gas Heater Operating Instructions Figure 58 Gas Heater Instructions ...
Page 129: ...Maintenance Log E Coated Coil ...