22
Altitude
(0000)Ft
Op Range Outside
Allowable Value.
Reset to Max F.S.
(Press Enter)
Op Range value within
New Min/Max values
Op Range value exceeds
New Min/Max values
Entering a new Altitude
and pressing the Enter
button will calculate
new Min & Max Op
Range values.
Warning Message
Operating Range
(ACFM)
(6,000 - 12,000)
(12,000)
Pressing the Enter button
will reset the current Op
Range value to the new
calculated Max. F.S value
which will represent 100%
of the process output value.
The Op Range value can be
changed and will represent
100% of the process output
signal (5vdc, 10vdc or 20mA).
-Altitude Example-
Altitude
Accepted
(0100)Ft
6.1.3. Modbus ID (Modbus Communication Option)
When the Modbus Communication option is ordered, the Modbus ID Menu allows the user to set a
unique device address when connecting to a Modbus network. The default is 002. For communication
with WattMaster Controls the Modbus ID has been set by the factory to 009 for outside airflow
applications. For additional information refer to the AAON Outdoor Airflow Measurement System
O&M.
Tech. Config.
Password: 1000
4PT Flow Corr
Modbus ID
MAC Address
(Range = 01 to 254)
Instance Number
Modbus ID
(002)