background image

AAF-HermanNelson

®

Installation Instructions For
Floor Mounted Model ARQ, ERQ

©1999 AAF-HermanNelson

IM UV-3-202D (Rev. 6/99)

HermanNelson

®

Installation and Maintenance Data

IM UV-3-202D

Group:  Unit Ventilator

Part Number: 106100901

Date: June 1999

IMPORTANT: Operating the water source
heat pump system before cleaning the
pipe loop can cause series damage to the
equipment. Confirm that the system has
been cleaned in accordance with the
procedure on page 3 before completing
the installation of this equipment.

NOTE: These are general instructions.
Refer to the AAF-HermanNelson Environ-
mental submittal drawings for specific
dimensions, unit arrangement, stub-up
locations, etc.

Uncrating and Inspection

Upon receipt of the equipment, check
carton for visible damage. Make a nota-
tion on the shipper's delivery ticket
before signing. If there is any evidence of
rough handling, the cartons should be
opened at once to check for concealed
damage. If any is found, notify the carrier within 48 hours to
establish a claim and request their inspection and a report.
The Warranty Claim Department should be contacted.

Inspect the carton for any specific tagging numbers
indicated by the factory per a request from the installing
contractor.

Check the number against the plans to be sure that the unit
will be installed in the correct location.

Note:

 

Installation and maintenance must be performed by

qualified personnel who are familiar with local codes
and regulations, and are experienced with this type
of equipment.

Caution:

 Sharp edges are a potential injury hazard. Avoid

contact with them.

Uncrating

1. Check tagging on unit carton to confirm that unit is

correct for the location.

2. Position the carton so the end marked "TRUCK FROM

THIS END" is on the right-hand side as you face the unit.

3. Carefully remove the carton from the unit. The carton may

be retained to provide protection for the unit after
installation. Do not remove the protective plastic
covering until the unit is to be started. When removing
the protective plastic covering, be certain that it is
removed from the interior of the front panel.

4. Check for shipping damage.

Figure 1.

WALL SURFACE

1. The wall behind the unit should be smooth and plumb.

2. The seals on the rear of the unit will take up the small irregu-

larities of normal masonry construction.

3. Furring strips must be installed on irregular walls or walls

with mullions in order to provide a flush surface for the unit to
seal against.

4. Any moldings at the floor/wall line should be omitted

behind the unit.

5. A sealing surface must be provided at the floor line

(see Figure 2).

The above steps are important to prevent leakage of outdoor air
which wastes energy, causes erratic control, AND MAY CAUSE
FREEZE-UP OF WATER SYSTEM.

LEFT END VIEW

DRAIN CONNECTION
FIELD REVERSIBLE

KNOCK-OUT
FOR MAIN
ELECTRICAL
CONECTION

TOP VIEW

HINGED ACCESS
DOOR

FRONT VIEW

WATER RETURN

WATER SUPPLY

FAN MOTOR

Figure 2.

INTAKE
LOUVER

SEALING SURFACE

SEALING
SURFACE
PITCH AWAY
FROM UNIT

1"

Reviews: