Installation-, User- and Service Manual
63
2 Working principal
2.1 Introduction
2.2 General working
principle of the
Theta dual service
module
2.3 Heating cycle
This chapter covers the following topics:
General working principle of the dual service modules;
Heating cycle;
Safety of the dual service modules.
Dual service is a module that connects a Domestic Water system (DHW system) and a
heating system. By using a Theta dual service module, heat from a BFC, SGE or SGS
can be transferred, through a plate heat exchanger, to the heating system.
Through the use of an intelligent control there is an optimal use of the available hot water
supply. Without compromising on comfort the system can provide hot water demand
from both domestic hot water system and heating system.
The intelligent control controls the domestic hot water and heating system through a
number of sensors and directs the DHW-pump and 3-way mixing valve in order to
achieve the desired flow temperature on the heating side of the system.
Note
The maximum working pressure, on the DHW-side of the system, is 8 bar. The minimum
working pressure, on the heating-side of the system, is 1 bar and the maximum working
pressure is 3 bar.
At heat demand on the heating side of the system, from the room thermostat, the DHW-
pump(modulating) an heating pump will be activated by the controller. To reach the
desired supply temperature the 3-way mixing valve will also be activated.
In the 3-way mixing valve, the water that runs through the plate heat exchanger is mixed
with hot water from the water heater, in order transfer enough heat in the plate heat
exchanger, which will result in the desired supply temperature of the heating water. The
desired heating supply temperature (heating setpoint) can be set on the controller of the
water heater.
The desired temperature depends on the type of heating system. The heating supply
temperature is measured by temperature sensor S
5
which is mounted on heating supply
pipe.
Note
Temperature sensor S
5
has a control function and is not to be used as a safety for the
heating system. This kind of safety should be regulated separately and is the full
responsibility of the installer.
Note
The pressure protection must also ne provided separately and is the full responsibility of
the installer.
Summary of Contents for Theta T Series
Page 4: ...Theta Dual Service Module 2 0 4...
Page 6: ...Installatie Gebruikers en Service handleiding 6...
Page 16: ...Installatie Gebruikers en Service handleiding 16...
Page 28: ...Installatie Gebruikers en Service handleiding 28...
Page 30: ...Installatie Gebruikers en Service handleiding 30...
Page 32: ...Installatie Gebruikers en Service handleiding 32...
Page 38: ...Installatie Gebruikers en Service handleiding 38...
Page 44: ...Installatie Gebruikers en Service handleiding 44...
Page 46: ...Installatie Gebruikers en Service handleiding 46...
Page 58: ...Installation User and Service Manual 58...
Page 68: ...Installation User and Service Manual 68...
Page 80: ...Installation User and Service Manual 80...
Page 82: ...Installation User and Service Manual 82...
Page 84: ...Installation User and Service Manual 84...
Page 90: ...Installation User and Service Manual 90...
Page 96: ...Installation User and Service Manual 96...
Page 98: ...Installation User and Service Manual 98...
Page 108: ...Installation User and Service Manual 108 11 5 Configuration 3 way mixing valve IMD 1124 R0 0...
Page 109: ...Installation User and Service Manual 109 0311 686 R0 0 NL EN...