background image

27

Cleaning the Combustion Chamber and 
Flame-arrestor                                                      

1.  Follow procedure outlined in “Removing the Manifold/

Burner Assembly”.

2.  Use a vacuum cleaner/shop vac to remove all loose 

debris in the combustion chamber (Figure 32). Use 
compressed air to clear any dust or debris that may 
have accumulated in the flame-arrestor.

DOOR GASKET

FLAME ARRESTOR COMBUSTION CHAMBER

BASE-RING
FILTER

FIGURE 32.

3.  Reassemble following the procedure under “Replacing 

the Manifold/Burner Assembly”.

Replacing  the  Manifold/Burner  Assembly                             

WARNING

Explosion Hazard

•   Tighten both manifold door screws securely.

•   Remove any fiberglass between gasket and 

combustion chamber.

•   Replace viewport if glass is missing or damaged.

•   Replace two piece wire connector if missing or 

removed.

•   Replace door gasket if damaged.

•   Failure to follow these instructions can result in 

death, explosion, or fire.

1.  Check the door gasket for damage or imbedded debris 

prior to installation.

2.  Inspect the view port for damage and replace as 

required.

3.  Insert the manifold/burner assembly into the burner 

compartment, making sure that the tip of the manifold 
tube engages in the slot of the bracket inside the com-

bustion chamber (Figures 33 & 34). 

4.  Inspect the door gasket and make sure there is no 

fiberglass insulation between the gasket and the 

combustion chamber.

5.  Replace the two screws, which secure the manifold/

burner assembly door to the combustion chamber and 

tighten securely. Once the manifold/burner assembly 

door is tightened, visually inspect the door gasket 

between the manifold/burner assembly door and the 

combustion chamber for spaces or gaps that would 

prevent a seal. IMPORTANT: Do not operate the water 

heater if the door gasket does not create a seal be-

tween the manifold door and the combustion chamber.

6.  During the following procedure, do not cross-thread 

or apply any thread sealant to any of the fittings listed 

below. First, reconnect the manifold tubing to the gas 

control valve/thermostat. NOTE: L.P. gas systems use 

reverse (left-hand) threads on the manifold tube.   

 

NOTE: If a ferrule nut needs to be installed for the pilot 

tube, locate the one provided with your parts kit.  Install 

it in the gas control valve/thermostat at the pilot loca-

tion, hand tight only.  

 

Next, insert the pilot tube into the ferrule nut until it bot-

toms out. NOTE: Hold the tube in this position. Tighten 

the ferrule nut with a wrench until the crimp connection 

seals to the pilot tube. Continue to tighten until the nut 

is tight in the gas control valve/thermostat. When you 

are finished, connect the two wire leads that go to the 

thermal switch.

7.  Reconnect the igniter wire.
8.  Turn gas supply on and refer to the Lighting Instruc-

tions.

9.  With the burner lit, check the gas control valve/thermo-

stat supply line, manifold component block, manifold 

tube, and pilot tube connections for leaks. Check for 

leaks by brushing on an approved noncorrosive leak 

detection solution. Bubbles forming indicate a leak. 

Correct any leak found. IMPORTANT: All leaks must be 

fixed immediately.

10.  Replace the outer door.

DOOR GASKET

FLAME ARRESTOR COMBUSTION CHAMBE

BASE-RING
FILTER

FIGURE 33.

Summary of Contents for High Efficiency 100 series

Page 1: ...ctrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fi...

Page 2: ...Installation 17 Important Information About this Water Heater 18 Operating Your Water Heater 19 21 Lighting Instructions 19 Checking the Draft 20 Burner Flames 20 Emergency Shutdown 20 Water Temperat...

Page 3: ...t water heaters and have a thorough understanding of this instruction manual Service Agency A service agency also must have ability equivalent to a licensed tradesman in the fields of plumbing air sup...

Page 4: ...oid all ignition sources if you smell Natural or LP gas Do not expose water heater control to excessive gas pressure Use only gas shown on rating plate Maintain required clearances to combustibles Kee...

Page 5: ...n Valve U Pilot and Main Burner V Flue W Metal Drain Pan X Igniter Wire Y Base Ring Filter Z FV Sensor AA Transformer BB Flue Damper ALL PIPING MATERIALS TO BE SUPPLIED BY CUSTOMERS TO VENT TERMINATIO...

Page 6: ...instructions you should not proceed but have a qualified technician perform the installation of this water heater Massachusetts code requires this water heater to be installed in accordance with Mass...

Page 7: ...to clean the spill until all ignition sources have been extinguished Fire or Explosion Hazard WARNING Read instruction manual before installing using or servicing water heater Improper use may result...

Page 8: ...ctor or water shut off device used in conjunction with a piped metal drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to leakage in variou...

Page 9: ...ural gas water heater to an L P gas supply Do not connect an L P gas water heater to a natural gas supply Failure to follow these instructions can result in death explosion or carbon monoxide poisonin...

Page 10: ...in the occurrence of a leak in the system the gas will settle at floor level Basements crawl spaces closets and areas below ground level will serve as pockets for the accumulation of gas Before lighti...

Page 11: ...y a qualified technician using the installation instructions Examples of a qualified technican include gas technicians authorized gas company personel and authorized service persons Failure to so do c...

Page 12: ...typical examples of each method Louvers and Grilles In calculating free area for ventilation and combustion air supply openings consideration must be given to the blocking effect of protection louver...

Page 13: ...re certified by CSA International this certification applies to the vent damper device only and does not mean they are certified for use on this water heater U L recognized fuel gas and carbon monoxid...

Page 14: ...Before connecting a vent to a chimney make sure the chimney passageway is clear and free of obstructions The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces...

Page 15: ...off valve in the cold water inlet line It should be located close to the water heater and be easily accessible Know the location of this valve and how to shut off the water to the heater 6 A temperatu...

Page 16: ...se excessive restriction to water flow is not recommended Use only 95 5 tin antimony or other equivalent solder Any lead based solder must not be used Piping that has been treated with chromates boile...

Page 17: ...h duct tape 7 Repeat steps 5 and 6 for the hot water outlet pipe 8 Add additional sections of pipe insulation as needed T P RELIEF VALVE T P RELIEF VALVE MANUAL RELIEF LEVER T P RELIEF VALVE INSULATIO...

Page 18: ...es Questions Contact Residential Technical Assistance by referencing the phone number on the front of the Installation Instructions and Use Care Guide Installation Checklist Water Heater Location Wate...

Page 19: ...ier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Use only your hand to turn the gas control knob Never use tools If the...

Page 20: ...emperature range of 120 F 140 F 49 C 60 C is recommended by most dishwasher manufacturers The thermostat of this water heater has been factory set at the VAC Vacation position It is adjustable and mus...

Page 21: ...erature set by the user Vacation Setting The Vacation Setting VAC sets the controller at approximately 70 F This setting is recommended when the water heater is not in use for a long period of time Th...

Page 22: ...YL YL BN 24VAC V 24VAC BK 120VAC WH 120VAC GR BK 24VAC HOT WH 24VAC NEUTRAL BL RD BL RD YL YL BK 24VAC HOT WH 24VAC NEUTRAL YL 24VAC YL 24VAC TRANSFORMER YL 24 VAC GAS CONTROL VALVE THERMOSTAT FV SENS...

Page 23: ...ce information at 1 800 527 1953 A temperature limit switch or ECO Energy Cut Off sensor located in the gas control valve thermostat is used to shut off the water heater if the water temperature excee...

Page 24: ...ting Your Water Heater See the Repair Parts Illustration section for anode rod location TEFLON is a registered trademark of E I Du Pont De Nemours and Company Draining and Flushing It is recommended t...

Page 25: ...ush down slightly to free the manifold and pilot tube 7 Carefully remove the manifold assembly from the burner compartment NOTE Be sure not to damage internal parts Replacement Parts IMPORTANT The fol...

Page 26: ...lot before going to the next step FIRST BEND S OTHER FITTINGS NOT SHOWN FOR CLARITY PILOT TUBE SCREWS OLD PILOT IGNITER FLAME SENSOR ASSEMBLY FIGURE 30 7 Push the new pilot tube and igniter wire throu...

Page 27: ...ssembly door is tightened visually inspect the door gasket between the manifold burner assembly door and the combustion chamber for spaces or gaps that would prevent a seal IMPORTANT Do not operate th...

Page 28: ...26 NOTE L P Gas systems use reverse left hand threads on the manifold tube 6 Refer to Gas Piping section Figure 5 and disconnect the ground joint union in the gas piping Disconnect the remaining pipe...

Page 29: ...roubleshooting Table section 2 See Pilot Light Troubleshooting Flowchart section 3 Seat connector firmly in socket 4 Bleed the air from the gas line 5 Check with gas utility company 6 Check with gas u...

Page 30: ...at COMBUSTION ODORS 1 Insufficient secondary air 2 Flue clogged 3 Heater installed in a confined area 1 Provide ventilation to water heater Check flue way flue baffle and burner 2 Clean locate source...

Page 31: ...wer switch on the gas control valve to the OFF position and unplug the power cord from the power outlet 1 Attempt to depress the TCO door switch button see figure 27 If the TCO door switch button depr...

Page 32: ...e electrode flame sense rod replace the igniter pilot assembly Follow the directions on page 27 to re install the burner assembly into the combustion chamber Follow the instructions for lighting on pa...

Page 33: ...alve Open Is Main Flame Sensed Is Demand for Heat Satisfied Pilot Main Valve De Energize Is Flame Sensed Damper Energizes and Closes Will not light 8 4 flash error code See Corrective Action Table on...

Page 34: ...List Item No Parts Description 1 DRAFT HOOD 2 FLUE DAMPER 3 FLUE BAFFLE 4 HEAT TRAP COLD SOME MODELS 5 HEAT TRAP HOT SOME MODELS 6 COLD WATER DIP TUBE 7 ANODE ROD 8 TEMPERATURE PRESSURE RELIEF VALVE L...

Page 35: ...assembly which contains the manifold tube gasket door pilot igniter flame sensor assembly manifold component block with retainer clip thermal switch and pilot tube Natural Gas Low Nox Item 14B Manifol...

Page 36: ...36 NOTES...

Page 37: ...37 NOTES...

Page 38: ...38 NOTES...

Page 39: ...in accordance with proper sizing techniques for residential water heaters bearing a rating plate which has not been altered defaced or removed except as required by the warrantor used in an open syst...

Page 40: ...OF PURCHASE OR PROOF OF INSTALLATION DISCLAIMERS NO EXPRESSED WARRANTY HAS BEEN OR WILL BE MADE ON BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY OF THE HEATER OR THE INSTALLATION OPERATI...

Reviews: