background image

35

trouBleshootInG GuIdelInes

trouBle shootInG

Please check guidelines below.  For your safety, water heater service should be performed only by a qualified service technician.  

Read the GENERAL SAFETY INFORMATION section first.

INTELLI-VENT TROUBLESHOOTING CHART - USER CONTROL

 

 

 

proBleM

 

 

 

solutIon

 

 

Inadequate or no earth ground  

1. Ensure the wall outlet is properly grounded.

 

sensed by the Intelli-Vent™

 

 

control. 

2. Ensure all ground connections/wires on the 

 

 

 

  water heater are secure.

 

 

 

 

 

 

Power supply to Intelli-Vent™ 

1. Ensure the wall outlet is properly wired.

 

control has reversed polarity or a

 

 

high resistance to earth ground. 

2. Ensure all internal 120 VAC wiring connections and 

 

 

 

  wiring harness have no reversed wires. 120 VAC

 

 

 

  “hot” wire must connect to the on/off switch.

 

 

 

3. Ensure the wall outlet is properly grounded.

 

4. Ensure all ground connections/wires on the water

 

 

  heater are secure.

 

 

Pressure switch circuit remaining 

1. Ensure air pressure switch circuit wiring is correct

 

closed for more than 5 seconds 

  and the air pressure switch is not jumpered.

 

 

after heating cycle begins.

 

 

Blower does not start. 

2. Secure power to water heater, check continuity of air

 

 

 

  pressure switch contacts with wires disconnected.

 

 

service note:

 

 

 

Disconnect power - disconnect one 

  A  If pressure switch contacts show continuity (closed

 

 

wire from the air pressure switch 

    circuit) replace the pressure switch.

 

 

or the vent temperature limit

 

 

switch. Turn power back on - 

  B  If pressure switch contacts are open and all wiring

 

 

blower should start. 

    is correct - turn the power off for 10-20 seconds

 

 

 

    then on again to clear the error code - if the error

 

 

 

    code persists replace the Intelli-Vent™ control.

 

 

 

 

 

Pressure switch circuit remains open 

1. Ensure the blower is running - check for 120 VAC to

 

longer than 5 seconds after the blower 

  the blower when the heating cycle begins, check the

 

 

is energized. 

  wiring. If the control does not energize the blower -

 

 

 

  replace the Intelli-Vent™ control. If the blower fails to

 

 

Blower may run continuously in 

 

  start when energized - replace the blower assembly.

 

 

this condition.

 

 

 

 

2. Ensure the air pressure switch sensing tube is properly 

 

 

 

  connected - not kinked or damaged.

 

 

 

3. Check continuity of vent temperature limit switch - replace

 

 

 

  switch if contacts remain open under 160ºF (71°C).

 

 

 

 

 

 

4. Ensure the correct size of vent pipe (2”, 3”, 4”) was used

 

 

service note:

 

  per installation manual for vent length. Ensure maximum

 

 

To learn more about performing Air 

  number of elbows or equivalent feet of vent pipe has not

 

 

Pressure Switch tests visit our web 

  exceeded maximum limits.

 

 

site www.hotwater.com to download

 

 

technical bulletin A-023-06 Air Pressure 

5. Ensure there are no obstructions in the vent pipe.

 

 

Switches. 

 

 

 

6. Check air pressure switch performance - check pressure

 

 

 

  with a digital manometer - check continuity of contacts.

 

 

 

  (see service note in left column) If the switch proves  

 

 

 

  defective - replace the air pressure switch and or the

 

 

 

  blower assembly as required.

 

 

 

7. If air pressure switch performance test results prove

 

 

 

  the air pressure switch is working properly and error

 

 

 

  code 4 persists - replace the Intelli-Vent™ control.

 

 

The Intelli-Vent™ control has detected 

1. Check wiring to the hot surface ignitor - replace ignitor

 

an open ignitor circuit. 

  assembly if wiring is damaged or worn.

 

 

 

 

 

service note:

 

2. Check ignitor assembly plug and the socket on the

 

 

The resistance (ohms) of a hot surface 

  Intelli-Vent™ body for good connection. Replace

 

 

ignitor will increase over time. If the 

  ignitor assembly and/or control if necessary.

 

 

resistance at room temperature is near 

 

 

 

18.8 ohms - consider replacing the ignitor  3. Check resistance of ignitor at room temperature 77ºF 

 

 

as a preventative measure. 

  (25°C) at the plug end. Replace ignitor if resistance

 

 

 

  is not within 11.5 and 18.8 ohms at room temperature.

 

 

 

 

 

 

4. If results from the above tests were good and error

 

 

 

  code 5 persists - replace the Intelli-Vent™ control.

B  c  d  e  f

#       led status

w

ater

 hea

ter

 control

B  c  d  e  f

B  c  d  e  f

B  c  d  e  f

B  c  d  e  f

Summary of Contents for BTX-80 SERIES 100

Page 1: ...MODEL BTX 80 SERIES 100 ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED...

Page 2: ...alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type...

Page 3: ...3 GENERAL SAFETY INFORMATION...

Page 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk...

Page 5: ...d Cleveland OH44131 NFPAdocumentsarealsoavailablefromNational Fire Protection Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the...

Page 6: ...feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch...

Page 7: ...Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shut Off Valve H Ground Joint Union J Dirt Leg K O...

Page 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1 continued...

Page 9: ...ship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water tempe...

Page 10: ...cs All models Maximum Supply Pressure 14 inches W C 3 48kPa Minimum Supply Pressure Natural Gas 5 0 inches W C 1 24kPa Minimum Pressure must be maintained under both load and no load static and dynami...

Page 11: ...talled in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water s...

Page 12: ...rine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heate...

Page 13: ...e the size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air shall be provided to replace the exhausted air When an exhaust fan is insta...

Page 14: ...a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 19 26 fo...

Page 15: ...e requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the water...

Page 16: ...the T P valve Secure all insulation using tape Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized T...

Page 17: ...P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Syste...

Page 18: ...system by closing itsindividualmanualShut offvalveduringanypressuretestingofthegas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping...

Page 19: ...uctions Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assembly is shown in Figure 16 However this assembly may...

Page 20: ...0 cm 12 inches 30 cm K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 10 feet 3 m horizontally E Clearance to unventilated soffit 12 inches 30 cm 12 inches 30 cm...

Page 21: ...rectmaterialasdetailedabovehasbeenused andthatminimum ormaximumventlengthsandterminallocationasdetailedinthismanual have been met Carefully inspect entire venting system for any signs of cracks or fra...

Page 22: ...hat the plastic tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower h...

Page 23: ...ine This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLA...

Page 24: ...ighest anticipated snow level install a snorkel as shown in bottom portion of Figure 20 NOTE With the installation of a snorkel it is necessary to use two 90 elbows that shall be considered along with...

Page 25: ...cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA 4...

Page 26: ...and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical...

Page 27: ...and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleanin...

Page 28: ...make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and pr...

Page 29: ...R buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off all ele...

Page 30: ...c does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressing t...

Page 31: ...cal water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment If the smelly water persists after the anode replacement and chl...

Page 32: ...uld be made of the main burner and the hot surface igniter assembly for proper flame characteristics and ignition sequences This can be done by removing the Outer Door and viewing the main burner oper...

Page 33: ...have a thermal expansion tank installed is not covered under the limited warranty Thermal expansion tanks must be installed on all closed water systems DO NOT PLUG THE TEMPERATURE PRESSURE RELIEF VALV...

Page 34: ...ose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances wat...

Page 35: ...control does not energize the blower replace the Intelli Vent control If the blower fails to Blower may run continuously in start when energized replace the blower assembly this condition 2 Ensure the...

Page 36: ...ff for 10 20 seconds then on again to clear this error code 4 Ensure the flame sensor is clean use ultra fine steel wool or Scotch Brite pad to clean flame sensor 5 Ensure the hot surface ignitor is p...

Page 37: ...in tolerance 1 Ensure air pressure switch hose is not kinked or clogged ensure the blower housing is clear of any condensation 2 Check vent temperature limit switch if it is determined that the vent t...

Page 38: ...38 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES...

Page 39: ...unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVI...

Page 40: ...40 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com Copyright 2010 A O Smith Corporation All rights reserved...

Reviews: