BFC 80 to 120
The gas control valve has a test nipple that can be used for measuring the supply
pressure.
This test nipple has a sealing screw. Loosen the sealing screw by a few turns. Do not
completely loosen it as it can be difficult to retighten.
IMD-1097a R0
Open the gas supply and vent the gas supply line via the test nipple.
Connect a pressure gauge to the test nipple as soon as gas starts to flow from it.
Switch on the power to the appliance using the isolator on the appliance.
Switch the controller
ON
by setting the
0/I switch
to position
I
.
The display will now show INTERNAL CHECK for about 10 seconds, and will then go
to the main menu.
Select SERVICE OPERATION, FULL LOAD from the service menu.
Confirm with
[ENTER]
.
The display shown here will appear
The appliance is now in
Full load
mode and will ignite.
You must wait about 1 minute after the display shows the text RUNNING before
reading the dynamic pressures (the fan needs this time to get up to full speed, so
that you can get a reliable reading).
Use the pressure gauge to read the supply pressure and compare it against the value
from the gas table (see section 12.3).
Note
Consult the mains gas supply company if the supply pressure is not correct.You cannot
yet start using the appliance. You must now take the appliance out of service (see section
4.2.2).
5.
6.
7.
8.
9.
10.
11.
12.
13.
n
0311704_BFC_28-120_III_
ENEN_V2.4, 2022-10-17
69
Summary of Contents for BFC Cyclone
Page 6: ...6...
Page 13: ...User part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 13...
Page 14: ...14...
Page 16: ...16 User part...
Page 18: ...18 User part...
Page 24: ...24 User part...
Page 41: ...Installation Maintenance and Service part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 41...
Page 42: ...42 User part...
Page 46: ...46 Installation Maintenance and Service part...
Page 52: ...52 Installation Maintenance and Service part...
Page 59: ...Fig Venting systems 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 59...
Page 76: ...76 Installation Maintenance and Service part...
Page 78: ...78 Installation Maintenance and Service part...
Page 84: ...84 Installation Maintenance and Service part...
Page 102: ...Fig Dimensions BFC 28 30 50 60 102 Installation Maintenance and Service part...
Page 104: ...Fig Dimensions BFC 80 100 120 104 Installation Maintenance and Service part...
Page 112: ...12 7 Declaration of conformity 112 Installation Maintenance and Service part...
Page 113: ......
Page 114: ......
Page 118: ...116 Installation Maintenance and Service part...