4EVAC 4E-FMTC Installation And User Manual Download Page 1

Hacousto Holland bv 

Industrieweg 87 

2651BC  Berkel & Rodenrijs 

 

4E-FMTC installation and user guide 

Author: 

DD 

 

 

 

Page 1 of 17 

  

 

 

 

 

 
 
 
SUMMARY 
This document includes both installation and user guides  of  the  4E-FMTC, the dual-mode 

(commercial/fireman) microphone station with touchscreen for the Compact 500 Voice Evacuation System. 

It explains how the 4E-FMTC should be installed and configured. The installation instructions are addressed 

to trained technical personnel, such as installers, service technicians and commissioning engineers. The user 

instructions explain how to operate the 4E-FMTC and how to interpret indications by end users as well as 

technical personnel, such as service technicians. 
 
REVISION AND APPROVAL 

Rev. 

Date 

Nature of Changes 

Approved By 

01 

24-06-2018 

Original draft 

DD 

02 

05-06-2020 

Corrections 

TvdH 

 

 

 

 

 

 

Summary of Contents for 4E-FMTC

Page 1: ...ion System It explains how the 4E FMTC should be installed and configured The installation instructions are addressed to trained technical personnel such as installers service technicians and commissi...

Page 2: ...t 3 3 Configuration settings 4 4 Hardware installation and settings 5 L Net 5 4 1 1 Network ports 5 4 1 2 Redundant link 6 4 1 3 Network cabling 7 Device ID 8 5 Front Panel 9 LED indicators 10 5 1 1 P...

Page 3: ...e paging and emergency evacuation management is necessary 4E FMTC includes fault monitoring and EVAC functionality thus is suitable as an emergency microphone 2 Where do I start First make sure that y...

Page 4: ...ilable for audio routing BGM inputs general purpose messages microphone volume level individual for both gooseneck and fireman s mic TALK button mode PTT toggle etc The configuration file should be pr...

Page 5: ...m 8 of stations per L Net port A maximum 16 of stations per single C500 main unit total sum of all 3 L net ports The microphone station may be also daisy chained together with other L Net devices Comp...

Page 6: ...ith other L Net devices NOTE The device is equipped with a power link jumper which by default is in the ON position pass through power over L Net In order to create a redundant link the jumper must be...

Page 7: ...least FTP NOTE If you use a straight cable the device will power up but the Tx Rx data terminals will not be properly connected This will result in a communication fault between the L Net device and...

Page 8: ...set the Device ID you must access the rotary switches on the back side of the unit 1 Remove the steel plate covering back of the station 2 Identify the high significant and low significant rotary swi...

Page 9: ...eck microphone Emergency section with fireman microphone The emergency section is closed behind a transparent door for access level protection While the door remains closed the 4E FMTC remains in gene...

Page 10: ...east one device in the system is reporting a fault Continuous when a local station fault is detected o Microphone short or open circuit o PTT button short or open circuit o Network link fault Blinking...

Page 11: ...reen If there are more than 6 zones accessible use the scroll arrow button to scroll through pages with zone selection 5 2 1 2 Source selection Next on the right section of the screen select the sourc...

Page 12: ...nel ALL CALL NOTE In paging mode you can use only gooseneck microphone 5 2 1 4 Stop message BGM Select zones where the message BGM audio signal is being transmitted and press STOP This will reset thes...

Page 13: ...group of zones For more information about programming events please look in the user manual of the 4EVAC Manager where all configuration settings are explained 5 2 3 LOG tab Under the LOG tab you will...

Page 14: ...nes accessible than the screen can display at one time use the scroll arrow button to scroll through pages with zone selection 5 3 1 2 Emergency Message selection Next on the left bottom section of th...

Page 15: ...L NOTE In emergency mode you can only use the fireman s microphone 5 3 1 4 Stop emergency message Select the zones where the message audio signal is being transmitted and press STOP This will reset th...

Page 16: ...ncy response 100 Hz 12 kHz Digital audio format 24 kHz sampling ADPCM compressed Audio processing Fixed BP filter fixed dynamics compression Local network interface Architecture Master slave up to 16...

Page 17: ...651BC Berkel Rodenrijs 4E FMTC installation and user guide Author DD Page 17 of 17 M A D E I N T H E N E T H E R L A N D S 4EVAC is a trade name of Hacousto Holland bv Industrieweg 87 2651BC Berkel Ro...

Reviews: