Hi-K Silicone Rubber Termination Kit, 15 kV

Instruction Sheet

 Technical Information:

For use on 15 kV Tape or Wire Shielded Cable

 Conductor Size Range:

#2 AWG-1000 kcmil

 Primary Insulation O.D. Range:

.637”-1.810” (16.2-46.0 mm)

Hi-K Silicone Rubber Termination Kits

for

Tape or Wire Shielded Cable

15 kV Class

5671      5672

 Number of Pages:   4

 Issue Date:  9/9/97

 Scale:   Not to Scale

 Issue:

78-8111-0842-8

DIMENSION TABLE

Kit No. A B 15 kV Cond.

Size Range

(AWG - kcmil)

Primary Insul.

O.D. Range

(inch-mm)

5 6 71

10"

(254

mm)

Depth of

Lug or

#2 -2 50

.637-1.120"

(16.2-28.4 mm)

5 6 72

10"

(254

mm)

Stem

Connector

Barrel 250-I000

.940”-1.810”

(23.9-46.0 mm)

IEEE Std. No. 48, 1975

Class 3 Termination
15 kV Class

Kit Contents:

1 Hi-K Silicone Rubber Termination
1 Packet of Silicone Grease
1 Instruction Sheet

Summary of Contents for Quick Term II

Page 1: ...e Shielded Cable 15 kV Class 5671 5672 Number of Pages 4 Issue Date 9 9 97 Scale Not to Scale Issue 78 8111 0842 8 DIMENSION TABLE Kit No A B 15 kV Cond Size Range AWG kcmil Primary Insul O D Range inch mm 5 6 71 10 254 mm Depth of Lug or 2 2 50 637 1 120 16 2 28 4 mm 5 6 72 10 254 mm Stem Connector Barrel 250 I000 940 1 810 23 9 46 0 mm IEEE Std No 48 1975 Class 3 Termination 15 kV Class Kit Cont...

Page 2: ...onnection Figure 2 2 WIRE SHIELD a Remove jacket as shown in Figure 3 and dimension table below Be sure to allow for depth of lug B b Wrap 2 full wraps of Scotch 24 Shielding Tape over shielding wires at jacket edge Cut off excess 24 Tape Figure 3 c Bend shielding wires back over 24 tape and cut off excess at cable jacket edge Figure 3 d Remove cable semi con as shown in Figure 3 3 Remove cable in...

Page 3: ...Figure 4 Note Cinch tighten the applied coil after final wrap C Install Termination 1 Cover the edge of the 13 tape or semi con material with a liberal coating of silicon grease Figure 4 NOTE ON THIS PRODUCT THE SILICONE GREASE DOES NOT SERVE AS A LUBRICANT IT MUST BE USED TO FILL THE STEP AT THE LEADING EDGE OF 13 TAPE OR THE STEP AT THE SEMI CON CUTOFF Spread silicone grease over the entire expo...

Page 4: ... Seller s products are based on information believed to be reliable but the accuracy or completeness thereof is not guaranteed Before utilizing the product the user should determine the suitability of the product for its intended use The user assumes all risks and liability whatsoever in connection with such use Any statements or recommendations of the Seller which are not contained in the Seller ...

Reviews: