6 78-8127-8864-0-C
3.3
If using a crimp type connector,
remove cable insulation for 1/2 connector length plus an allowance* for
increases in connector length due to crimping. Insulation removal length shall not exceed 3 3/4" (95 mm) from
conductor end.
Do not install connector now
(Figure 8).
*Note: This assumes that the installer has determined the increased length of an aluminum connector crimped
with a specific tool and die.
Aluminum (Al/Cu) Crimp Connector Growth Chart
Conductor Size
Typical growth allowance (per end)
350–500 kcmil
1/4" (6 mm)
750 kcmil
3/8" (10 mm)
Note: 1) Copper connectors do not require a length change allowance.
2) Maximum aluminum connector crimped length allowed is 7.50" (191 mm).
One-half connector length
+ growth allowance*
Figure 8
3.4
For 350 and 500 kcmil copper connectors, or connectors with an O.D. between 0.80–1.04"
(20,3–26,4 mm):
Park cold shrink adapter tube on cable insulation
(Figure 9).
Cold shrink adapter tube
Figure 9