50
C
HAPTER
2: I
NSTALLATION
Connecting the Visual Alarm
Table 20 lists the pinouts for the visual alarm
connector. Connect your alarm equipment to the appropriate pins, as determined
by the type of alarm equipment you are using. For example, if the alarm
equipment you are using requires an Open state when there is no alarm, connect
to pins 1 and 2 for the minor alarm, 7 and 8 for the major alarm, and 4 and 5 for
the critical alarm. When the MCPU detects a minor, major, or critical alarm, the
appropriate LED illuminates. To turn off the LED, you must clear the alarm.
Connecting the Audible Alarm
Table 21 lists the pinouts for the audible alarm
connector. Connect your alarm equipment to the appropriate pins, as determined
by the type of alarm equipment you are using. For example, if the alarm
equipment you are using requires an Open state when there is no alarm, connect
to pins 1 and 2 for the minor alarm, 7 and 8 for the major alarm, and 4 and 5 for
the critical alarm. When the MCPU detects a minor, major, or critical alarm, the
alarm rings. To turn off the alarm, press the ACO button on the front of the MCPU
module.
Table 20
Visual Alarm Connector Pinouts
PIN 1
Minor Alarm Return (Common)
PIN 6
Minor Alarm Normally Closed (NC)
PIN 2
Minor Alarm Normally Open (NO)
PIN 7
Major Alarm Return (Common)
PIN 3
Major Alarm Normally Closed (NC)
PIN 8
Major Alarm Normally Open (NO)
PIN 4
Critical Alarm Return (Common)
PIN 9
Critical Alarm Normally Closed (NC)
PIN 5
Critical Alarm Normally Open (NO)
Table 21
Audible Alarm Connector Pinouts
PIN 1
Minor Alarm Return (Common)
PIN 6
Minor Alarm Normally Closed (NC)
PIN 2
Minor Alarm Normally Open (NO)
PIN 7
Major Alarm Return (Common)
PIN 3
Major Alarm Normally Closed (NC)
PIN 8
Major Alarm Normally Open (NO)
PIN 4
Critical Alarm Return (Common)
PIN 9
Critical Alarm Normally Closed (NC)
PIN 5
Critical Alarm Normally Open (NO)
Summary of Contents for 3C63400-3AC-C - PathBuilder S700 Switch
Page 14: ...xiv CHAPTER SUPPLEMENTARY REGULATORY INFORMATION ...
Page 18: ...4 ABOUT THIS GUIDE ...
Page 28: ...14 CHAPTER 1 SYSTEM DESCRIPTION ...
Page 88: ...74 CHAPTER 3 GETTING STARTED ...
Page 260: ...246 CHAPTER 6 PATHBUILDER S700 DIAGNOSTICS AND PERFORMANCE MONITORING ...
Page 270: ...256 INDEX ...