INSTALLATION,  COMMISSIONING AND OPERATION

Whisper Air

EN

ver. 1 29.05.20

Summary of Contents for Whisper Air HRWA1-040 Series

Page 1: ...INSTALLATION COMMISSIONING AND OPERATION Whisper Air EN ver 1 29 05 20 ...

Page 2: ...necting the unit please read carefully and follow all instructions below The manufacturer reserves the right to make changes including technical documen tation without previ ous notification Please keep this manual for further references Consider this manual an integral part of the product EC DECLARATION OF COMPLIANCE The product was designed and manufactured to comply with all relevant provisions...

Page 3: ...tact the supplier immediately After unpacking check that the unit and accessories are in good order Contact the supplier in case of any doubt Do not attempt to commission a damaged ventilation unit If unit is not intended for immediate installation it must be stored in a dry room with a temperature range of 5 C to 40 C This product must not be used by persons incl minors with mental or physical di...

Page 4: ... r h e a t e r N a c h h e i z e i n r i c h t u n g D X C O B y p a s s fl a p B y p a s s K l a p p e P r e h e a t e r V o r w ä r m e r O p e r a t i o n a l d i a g r a m F u n k t i o n s s c h e m a Fan Ventilator Heat exchanger Wärmetauscher Filter Filter Regulation die Regulation Condesate exhaust Kondensatausscheidung Afterheater Nachheizeinrichtung DX CO By pass flap By pass Klappe Preh...

Page 5: ...our business since 1995 4 SPARE PARTS Number Description Controls Water coil Electric heater CO2 sensor Heat exchanger Fan motor exhaust air Actuator for the bypass Fan motor fresh air Pressure sensor Preheater 1 2 3 4 5 6 7 8 9 1 2 5 3 6 4 8 9 7 8 8 ...

Page 6: ... DX CO By pass flap By pass Klappe Preheater Vorwärmer Operational diagram Funktionsschema Fan Ventilator Heat exchanger Wärmetauscher Filter Filter Regulation die Regulation Condesate exhaust Kondensatausscheidung Afterheater Nachheizeinrichtung DX CO By pass flap By pass Klappe Preheater Vorwärmer Operational diagram Funktionsschema Fan Ventilator Heat exchanger Wärmetauscher Filter Filter Regul...

Page 7: ...5 962 31 1203 150 367 802 Fan Ventilator Heat exchanger Wärmetauscher Filter Filter Regulation die Regulation Condesate exhaust Kondensatausscheidung Afterheater Nachheizeinrichtung DX CO By pass flap By pass Klappe Preheater Vorwärmer Operational diagram Funktionsschema Fan Ventilator Heat exchanger Wärmetauscher Filter Filter Regulation die Regulation Condesate exhaust Kondensatausscheidung Afte...

Page 8: ... R S T U V W X HRWA2 040 1901 397 963 195 165 1408 228 198 250 1835 689 32 922 45 265 446 88 600 212 70 74 120 179 46 HRWA2 070 2171 455 1116 172 102 1649 261 228 315 2105 763 37 1054 38 295 465 96 650 302 123 89 134 224 46 HRWA2 100 2501 575 1280 167 97 1920 291 288 315 2435 962 31 1251 64 420 550 104 625 303 244 184 230 224 46 ...

Page 9: ...49 186 315 962 962 31 1251 169 367 802 Fan Ventilator Heat exchanger Wärmetauscher Filter Filter Regulation die Regulation Condesate exhaust Kondensatausscheidung Afterheater Nachheizeinrichtung DX CO By pass flap By pass Klappe Preheater Vorwärmer Operational diagram Funktionsschema Fan Ventilator Heat exchanger Wärmetauscher Filter Filter Regulation die Regulation Condesate exhaust Kondensatauss...

Page 10: ...7 HRWA1 100 E 1000 EPM 1 55 F7 Coarse 60 G4 50 3 400 7 5 3770 3 400 11 8 6770 3 400 7 5 3770 151 HRWA1 100 X 1000 EPM 1 55 F7 Coarse 60 G4 50 1 230 5 770 3 400 9 3 3770 1 230 5 770 150 The listed weight is valid for the heaviest unit in a given class The rest of technical data can be found in the technical catalogue 6 INSTALLATION Select unit location It is recommended that a ventilation system sh...

Page 11: ... designed for installation in the vertical position Other installation position is not possible Installation of the unit shall allow a sufficient access for performing maintenance servicing and dismounting operations AUFSTELLUNG UND AUFBAU Das Gerät ist zum Einbau in vertikaler Position be Andere Einbauposition ist nicht möglich Das Gerät muss so installiert sein dass ein ausrei Zugang zwecksWartu...

Page 12: ...ceiling 1 Measure carefully the position of the holes for the threaded rods not included 2 Drill the holes 3 Install threaded rods of the appropriate length C D E C HRWA1 040 110 mm HRWA1 070 168 mm HRWA1 100 150 mm D HRWA1 040 689 mm HRWA1 070 763 mm HRWA1 100 962 mm E HRWA1 040 1835 mm HRWA1 070 2105 mm HRWA1 100 2435 mm ...

Page 13: ... no 3 Allen wrench Movethecoverupwardstoremoveit Itissecuredbyauxiliarybrackets see following picture Removed cover with brackets 6 INSTALLATION Hang the unit from the rods and secure the holes in the wall appropriately Inspect all mounting brakets and screws Installprotectiongrillesontheoutsideofthewalltopre vent the ingress of water and larger objects not included ...

Page 14: ...UM AKOVAT PRÁŠKOVOU BARVOU AKOVAT ZE VŠECH STRAN ELIKOST LAKOVANÉ PLOCHY 0 17 m2 284 6 340 R2 6 2 44 6 26 306 8 380 8 OZ NÁZEV ČÍSLO MN MJ MJ IFS HRWA1 KONZOLE P 3 026 D14358 1 289 ks kg 2 3 1 4 A4 D C A E F B 1 289 Úprava laku HRWA1 KONZOLE P 4 001 0013 PL ZN 2 0 DX51D ISO 2768 mK 22 08 2019 Josef Řezníček A 17 7 2019 Michal Král NÁZEV MATERIÁLU VOD ZMĚNY TUM ESNOST LEROVÁNÍ HMOTNOST ČISTÁ 1 5 MĚ...

Page 15: ...s threaded rods and anchors are not included 2 Measure carefully the position of the anchoring holes on the wall threaded rods and anchors are not included A B A HRWA2 040 802 mm HRWA2 070 934 mm HRWA2 100 1112 mm B HRWA2 040 1835 mm HRWA2 070 2105 mm HRWA2 100 2435 mm 3 Drill the holes 4 Install the anchor and threaded rods of the required length 200 mm 200 mm 6 INSTALLATION ...

Page 16: ... to the above steps see C 4 Deployunitonthepreparedanchoringandinsertthethreadedrods into the hinges on the unit Connect the hinges with anchors with M8 screws Náhled na ukotvení jednotky Inspect all mounting brakets and screws Installprotectiongrillesontheoutsideofthewalltopre vent the ingress of water and larger objects not included ...

Page 17: ...s 1 Carefully measure the position of the holes on the ceiling where the unit s ductwork will be connected A HRWA2 040 1408 mm HRWA2 070 1648 mm HRWA2 100 1920 mm B HRWA2 040 250 mm HRWA2 070 315 mm HRWA2 100 315 mm 2 Create openings for the air ducts C D E Preparation of fixing to the ceiling 1 Carefully measure the position of the holes in the ceiling for the threaded rods threaded rods not incl...

Page 18: ...ed rods and holes in the wall and properly secure Check securing For ductwork connected to the unit from the top the use of a condensate header is recommended due to the potential for condensed water to run into the unit ATTENTION Connect and secure the modules for connection from the top 3 2 1 4 6 INSTALLATION ...

Page 19: ...nics remove the following screws Electronic parts 1 Remove 12 screws on the lower side CAUTION Door is held closed by 2 safety latches to prevent door from swinging down quickly Once the 12 screws are removed from the unit press latches to open access door A Electronic board Module A G Electronic board Module G 1 Terminals for the power supply L and the output of the auxiliary power supply 12V 24V...

Page 20: ...max 3 5 m min 100 mm 18 mm Siphon SK HL138 Wall mounted or embedded in wall type not included RECOMMENDED SIPHON TYPES Siphon SK AKS3 not included min 100 mm Condensate pump CERP MAXI ORANGE Please read condensate pump manual for more information not included reservoir must be placed below the unit level to allow the water flow out of the unit pressure balancing tube to connect the reservoir and t...

Page 21: ...21 2VV Creating innovative solutions for you and your business since 1995 6 INSTALLATION CONNECTION OF THE WATER COIL C O SMU2 024 3 2 ZV3 24 1 ZV2 024 HRWA2 xxx V1 2x G HRWA2 xxx C3 2x G ...

Page 22: ...he installation check that the indication of the terminals corresponds to the wiring connection diagram In case of doubt contact the supplier and do not connect the unit under any circumstances The unit must be connected to the main power source via isolated cable with a heat resistance in compliance with the diameter and the applicable laws and regulations of the country where the unit is install...

Page 23: ...be connected through an earth leakage breaker according to the current model The unit must be connected in a way that it can be discon nected from the power supply with one breaker Table of minimum breaker sizes according to heat recovery unit model Recommended minimum circuit breaker values XS0 ES0 EE1 EV1 XE1 XV1 HRWA1 040 4A 1F 10A 1F 16A 1F 10A 1F 10A 1F 4A 1F HRWA1 070 4A 1F 13A 1F 10A 3F 13A...

Page 24: ...etta Aria fresca Klapka pro čerstvý vzduch 5 Flap outlet Клапан отработанного воздуха Klapa wydechu Aletta Scarico Klapka pro odvodní vzduch 6 Water pump Водяной насос конденсат Pompa wodna Pompa dell acqua Vodní čerpadlo N Neutral Entrée 24VAC 24V GND GND GND CAPTEUR PRÉSENCE DX GENERAL ERROR settable DX DEFROST settable 230VAC GND 2 1 V 0 10 VDC CO2 RH VOC EXT CO2 RH VOC EXTERNAL CAPTEUR 0 10V 1...

Page 25: ...ain is properly connected That the installation corresponds to the instructions in the manual That no tools or objects have been left inside unit That the filters are clean CAUTION Alterations and changes to the internal connections of the unit are forbidden and may result in the loss of warranty We recommend the use of accessories and components provided by our company Contact your supplier in ca...

Page 26: ...r intervals or ac cording to the demands of the operating environment Iftheunitisoutofserviceforalongperiod itisadvisableto turn it on for one hour at least every six months CAUTION The service of internal components and cleaning of the unit must be done only by a professional It is forbidden to operate the unit without filters It may damage the unit Clean the heat recovery unit with a vacuum clea...

Page 27: ...Filtr ePM 10 60 M5 2 ps FILTR HRWA1 xxx M5 1 1 2 Standard Optional xxx 040 070 100 2 Replacing filters After replacing filters check that the filters are properly secured and close the door The following picture shows the location of the filters in the unit and the table lists the appropriate types of spare filters Please note that there are 2 type 1 filters required for this unit 1 1 2 1 2 ...

Page 28: ...he temperature sensor behind the exchanger T EXT2 unit is ventilating Defective contact or sensor Control the connection of the sensor and replace if needed professional service 18 Inlet Temperature sensor failure in the supply canal T EXT3 unit is ventilating Defective contact or sensor Control the connection of the sensor and replace if needed professional service 21 Exhaust Tempera ture sensor ...

Page 29: ...PAIRING OVERHEATED ELECTRIC PREHEATER AND AFTER HEATER CAUTION The service of internal components must be done only by a professional Always disconnect the unit before servicing Firstly remove the cause of the overheated electric preheater and after heater The reset of the electric after heater is located here The reset of the electric preheating is located here The thermostat can be returned to t...

Page 30: ...rame pliers for precision mechanics Releasing the printed circuit Philips screw no 0 Plastic parts Ceiling insulation of front panels box cutter 10 CONCLUSION Once the it has been installed read carefully the safe operation manual of the unit That manual includes examples of possible problems and recommended solutions In case of any requests or inquiries contact our sales or technical department w...