background image

Solution: Connect the connectors properly, the swapping does not damage the equipment. 
- When the adapter has been connected, yellow and, in some cases, green LEDs are lighted on EnergyBank, the 
back-up equipment is supplied. 
Cause: An unsuitable type of adapter, insufficiently low output voltage or current. This situation may happen 
whenever EnergyBank is used with a unit other than a GSM gateway and available adapter. 
Solution: Use a suitable adapter, the adapter output voltage must be in the whole range of load within the limits 
included in the 

"Technical Parameters“ 

section, the adapter current must be 200mA higher at least than the 

maximum power consumption. 
- EnergyBank has a substantially lower capacity during back-up despite of having been fully charged. 
Cause 1: The usable capacity of accumulators decreases at higher discharge currents. 
Cause 2: A deteriorated capacity of accumulators due to ageing. 
Solution: Replace the accumulators. 
- EnergyBank turns off when the backed-up equipment is turned on in the back-up mode. 
Cause: The inrush current following the equipment turn-on made the accumulator voltage drop and EnergyBank 
turns off. 
Solution: Keep the equipment connected to EnergyBank continuously, never switch the backed-up equipment in 
the back-up mode. 
 

7. Technical Parameters 

Input voltage: 

 

 

11.5 to 14.5V 

Pass-through loss at mains supply: 

max. 0.5V 

Maximum output current: 

 

adapter output current minus 200mA, max. 1A 

Accumulators used:   

 

NiMh, size AA, 1800mAh, 10 pcs. 

Self-consumption - off status: 

 

30uA 

Self-consumption - back-up status: 

15mA 

Self-consumption - charging: 

 

max. 200mA 

Charging current: 

 

 

60 to 200mA (according to the battery charging level) 

Accumulator voltage for low power: 

11.3V 

Accumulator voltage for turn-off: 

10V 

Dimensions: 

  170x130x45mm 

Operational temperature: 

 

0 to 45

°

 
EasyGate operation time in EnergyBank back-up mode (applies to new accumulators): 
- Standby mode (70mA) 

 

approx. 20 hours 

- GSM in connection (200-300mA) 

approx. 6 hours 

Warranty for this device is 24 month, not valid for accumulators 
___________________________________________________________________________________________ 

EC Declaration of Conformity 

 

Directive: 

Electromagnetic compatibility 
(EMC): 89/336/EEC 

Manufacturer: 
 

2N TELEKOMUNIKACE a.s. 

 Mod

ř

anská 621 

 

143 00 Prague 4 

 Czech 

Republic 

 

Declares that the product: 

 

ATEUS

® 

-

 

 EnergyBank 

 

Type numbers: 

ATEUS

® 

 – EnergyBank, 

501399E  

 

Description: Backup power supply  

 

Designed for: Backup power supply for 12V 

powered devices 

 
Conforms to the following Standards: 
EMC: EN 55 024:1998, A1:2001, A2:2003 

EN 55 022:1998, A1:2000, A2:2003, 
A1/Cor.:2003, Cor.:2003

 

 

Date and place of issue:  
Prague, Czech Republic, 17.3.2005 
 

 

 

 

 

Manufacturer’s stamp 
 

 

 

 

……………………………………………

………………………. 
 

 

 

 

 

Ing. Old

ř

ich Stejskal, executive director 

 

© 2005, 2N TELEKOMUNIKACE a.s. – Praha,  PS 1174 v.1.0 

 

 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 

 

EnergyBank - Instructions for Use 

 
1. Purpose 

EnergyBank is designed to back up accidental supply voltage outages for equipment supplied with 12 V dc 
voltage with the peak current drain of 1A. The backed-up power supply works as a pass-through system, i.e. the 
backed-up equipment is connected continuously to the output connector and the power supply (typically a mains 
adapter) to be backed up is connected to the input connector. During a voltage failure on the input connector, 
EnergyBank transits automatically into the back-up mode. 
Primarily, EnergyBank is designed to back up EasyGate and SmartGate GSM gateways made by 2N 
TELEKOMUNIKACE (hereinafter referred to as GSM gateways). The backed-up power supply is connected 
between the mains adapter and the GSM gateway, the adapter being included in the GSM gateway delivery.  
- When a device other than a 2N gateway is used for back-up, it is necessary to observe the parameters included 
in the 

"Technical Parameters“ 

section

.

  Especially, be sure to use an appropriate mains adapter. The adapter 

voltage must be within the input voltage limits mentioned in the Technical Parameters; common transformer 
adapters usually do not meet these requirements. The use of an unsuitable adapter may lead to a substantial 
reduction of the battery life or equipment damage. You can purchase a suitable adapter with stabilised output 
voltage from the 2N company. 
- When your EnergyBank outlives its usefulness, dispose of it in accordance with applicable legal regulations. 
 

2. Delivery Contents 

- a backed-up power supply base board, including accumulators; 
- screws and dowels for wall mounting; 
- an EnergyBank - backed-up equipment interconnecting cable; 
- a mounting pattern template and Instructions for Use. 
 

 