background image

STANDARD FOR ALARM LOCATION

Smoke detectors used with this system should be installed in accordance 
with Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72 (National Fire 
Protection Association , Batterymarch Park, Quincy, MA 02269) which reads as 
follows:

2-1.1.1

  Smoke alarms shall be installed outside of each separate sleeping area 

in the immediate vicinity of the bedrooms and on each additional story of the 
family living unit including basements and excluding crawl spaces and unfi nished 
attics. In new construction, a smoke alarm shall be installed in each sleeping 
room.

2-1.1.2

  For family living units with one or more split levels (i.e., adjacent levels 

with less than one full story separation between levels), a smoke alarm required by 
2-1.1.1 shall suffi ce for an adjacent lower level, including basements. (Exception: 
Where there is an intervening door between one level and the adjacent lower 
level, a smoke alarm shall be installed on the lower level.)

✔ 

Ceiling mounted smoke alarms should be located in the center of the room 
or hall, or not less than 4 inches from any wall. When the alarm is mounted 
on a wall, the top of the alarm should be 4 to 12 inches from the ceiling.

✔ 

Do not install smoke alarms where normal ambient temperatures are above 
100°F (37.8°C), or below 40°F (4°C). Also, do not locate alarm in front 
of air conditioners, heating registers, or other locations where normal air 
circulation will keep smoke from entering the detector.

A-2.5.2.1

  Smoke Detection - Are More Smoke Alarms Desirable? The required 

number of smoke alarms might not provide reliable early warning protection for 
those areas separated by a door from the areas protected by the required smoke 
alarms. For this reason, it is recommended that the householder consider the use 
of additional smoke alarms for those areas for increased protection. The additional 
areas include the basement, bedrooms, dining room, furnace room, utility room, 
and hallways not protected by the required smoke alarms. The installation of 
smoke alarms in kitchens, attics (fi nished or unfi nished), or garages is not 
normally recommended, as these locations occasionally experience conditions 
that can result in improper operation.

Smoke alarms are not to be used with detector guards unless the combination 
has been evaluated and found suitable for the purpose.

 National Fire Protection Association Standard #72

Recommendations for Smoke Detectors

THIS SECURITY SYSTEM COMPLIES WITH 

NFPA REQUIREMENTS FOR TEMPORAL 

PULSE SOUNDING OF FIRE NOTIFICATION 

APPLIANCES.

Figure 1. Smoke Alarm Locations

Summary of Contents for GO!control 2GIG-CNTRL2

Page 1: ...Wireless Security System Installation Programming Instructions 2GIG CNTRL2 2GIG CP2...

Page 2: ...e ceiling Do not install smoke alarms where normal ambient temperatures are above 100 F 37 8 C or below 40 F 4 C Also do not locate alarm in front of air conditioners heating registers or other locati...

Page 3: ...ounder Disable Icon 14 Backup Battery Status Icon 14 Test Mode Icon 14 Touch Screen Keypad Traffic Icon 14 GSM Radio Icon 14 Interior Sensor Open Icon 14 Programming Navigation 15 Navigation Arrows Go...

Page 4: ...requirements to qualify for a discount For an ETL smoke alarm system use only approved model smoke detectors with this Control Panel NOTE Some cities and municipalities may require an alarm system per...

Page 5: ...subscribers can query and control their system using a computer browser from anywhere in the world The Alarm com server can also send messages time corrections and software updates to the Control Pan...

Page 6: ...lashes ORANGE when ANY sensor is open not ready to arm Flashes RED while system is armed HOME BUTTON INDICATOR THIRD HAND HANGER STRAP Hooks onto mounting plate during installation to hold the Control...

Page 7: ...ery connector into the connector on the Control Panel s circuit board 14 Swing the Control Panel up placing the bottom over the lip of the mounting bracket Push the top of the Control Panel into the m...

Page 8: ...second button lockout Lithium battery 345 MHz ETL Listed 2GIG GB1 Glass Break Detector Monitors for the sound of breaking glass Two test LEDs Dual shatter recognition technology thud then crash Lithiu...

Page 9: ...module Locking connector 2GIG ANT4X External In wall GSM Antenna Antenna installs in the wall behind Control Panel 2 foot cable Plugs into GSM module Locking connector 2GIG BATT1 Standard Battery Pac...

Page 10: ...rmally open N O or normally closed N C End of line resistors EOLR can also be used to supervise the loops Only contacts should be used with the hardwired loops The Control Panel does not support power...

Page 11: ...LCO INPUT DROP SIDE OFTHE BOX OR ANY EARTH GROUNDS 3 At the demarcation box connect the RED cable wire to the box RING and the GREEN cable wire to the box TIP 4 At the demarcation box connect the BLAC...

Page 12: ...as simply plug the antenna connector into the GSM module The antenna will drop into the wall or mount in the attic with the cable passing through the slot in the Control Panel s mounting plate See Fig...

Page 13: ...ug the backup battery pack s connector into the connector on the Control Panel s circuit board The Control Panel will not recognize that the battery is connected until AC power is connected to the pow...

Page 14: ...e displayed To arm the system without an entry delay un check the ENTRY DELAY check box To arm silently without sounding the Exit Delay beeps check the SILENT EXIT check box Stay Mode arming always ha...

Page 15: ...shortcut to help the installer access the Installer Toolbox quickly Pressing the lower right corner of the Home Screen while the system is disarmed will immediately display a code entry screen When t...

Page 16: ...he system is being tested in Walk Test Mode the test mode icon will be displayed on the status bar Touch Screen KeypadTraffic Icon When the Control Panel is communicating to a touch screen keypad the...

Page 17: ...utton advances to the next programming question section The arrows select the next or previous programming sub question The arrows choose values for the question or move the cursor left and right alon...

Page 18: ...allation The volume setting DOES NOT affect the volume of alarm sounds 9 Press to view the second toolbox screen 10 Press BACKLIGHTTIMEOUT and set the display lighting timeout 11 Press SET DATE and SE...

Page 19: ...delay restart 0 1 1 enabled Q QUESTION DEFAULT Q 28 Select quick exit 0 1 1 enabled Q 29 Enter periodic test in days 0 255 30 days Q 31 Enter cancel time in minutes 5 255 5 minutes Q 32 Select cancel...

Page 20: ...ion trouble report but not an alarm when the system is disarmed 06 24 hour Silent Alarm This sensor type is active independent of the system arming status The code for silent panic is sent to the Cent...

Page 21: ...LAUNDRY 127 LEFT 128 LEVEL 129 LIBRARY 130 LIGHT 131 LIGHTS 132 LIQUOR 133 LIVING 134 LOADING 135 LOCK 136 LOFT 137 LOW WORD 138 MAIN 139 MAINTENANCE 140 MASTER 141 MEDICAL 142 MEDICINE 143 MENU 144 M...

Page 22: ...umber 01 48 Sensor Type Exit entry perimeter interior etc Sensor Equipment Type Certain sensor types will ask for equipment type Sensor Equipment Code Sensor model door window PIR smoke detector etc S...

Page 23: ...ON KEYPAD OR PRESS TO SELECT FROM LIST OR ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR insert PRESS...

Page 24: ...arrows or enter the equipment type number directly on the keypad Select RF sensor equipment code DEFAULT 0000 other The equipment code is a 4 digit code that is assigned to the model of sensor being u...

Page 25: ...button can be used to recall the last programmed sensor s serial number The sensor number will be filled in automatically if LEARN is used Select RF sensor dialer delay 0 1 DEFAULT Enabled 1 Required...

Page 26: ...announcement and chime options for the sensor Wired Sensor Summary Screen After setting all the options for a sensor the wired sensor summary screen is displayed The screen can also be displayed for p...

Page 27: ...ol Panel can be used with new or existing wired sensors If this wired sensor is new for the installation leave the default of new 0 If this wired sensor is already installed select existing 1 Select w...

Page 28: ...button RF Key Fob Summary Screen After setting all the options for a sensor the key fob summary screen is displayed The screen can also be displayed for programmed key fobs during key fob program edit...

Page 29: ...quipment age 0 1 DEFAULT New 0 The Control Panel can be used with new or existing key fobs If this fob is new for the installation leave the default of new 0 If this fob is already installed select ex...

Page 30: ...een After setting all the options for a sensor the RF keypad summary screen is displayed The screen can also be displayed for programmed RF keypads during RF keypad program editing by pressing the SUM...

Page 31: ...the Control Panel will learn the RF keypad s serial number TS1 WirelessTouch Screen Keypads For 2GIG TS1 Wireless Touch Screen Keypads press LEARN The Control Panel will display Pair with TS 1 Initia...

Page 32: ...HIFT button accesses the pound and star symbols The P button adds a 3 second pause to the dialing NOTE If a second Central Station telephone number is programmed with question Q 41 the Control Panel w...

Page 33: ...e supervised If the wiring to the sounder is cut for 15 30 or 45 seconds a bell trouble report can be sent to the Central Station The default 0 disables external sounder supervision To supervise the e...

Page 34: ...information on setting the cancel report trigger time NOTE This default can be changed without affecting SIA CP 01 compliance Q 33 Select cross sensor 47 48 0 1 DEFAULT Disabled 0 The Control Panel c...

Page 35: ...sses B C D E and F characters Q 42 Select remote control phone 0 3 DEFAULT Data and voice 3 This setting controls remote telephone access to the system The data option is for the installer It allows a...

Page 36: ...trouble beeps from sounding from 10 pm to 9 am The trouble s will still be displayed and immediately reported to the Central Station and can be acknowledged but they won t sound beeps until after 9 a...

Page 37: ...shutdown until the time of disarm and the sensor is closed The default 0 prevents alarm restore reports To allow alarm restore reports select enabled 1 Q 58 Select trouble restore reports to CS 0 1 DE...

Page 38: ...light saving end week Q 71 Select system tamper causes trouble 0 1 DEFAULT Enabled 1 The Control Panel s case has a tamper switch that detects if the case has been opened The system can be programmed...

Page 39: ...isible 1 The Z Wave home services feature can be enabled or disabled with various remote control access options The default 1 displays the SERVICES button but will show a message that the feature is c...

Page 40: ...1 DEFAULT Disabled 0 This setting enhances system operation in personal emergency applications and also provides the dealer with the option of the siren sounding until the bell cut off or to the end...

Page 41: ...permitted 4 Setup each User Code with the User Access Option Screen Each User Code can be set to be currently valid or not or to have conditional validity depending on a time and date schedule Refer...

Page 42: ...ome active again To re enable the sounder manually follow these steps 1 From the Installer Toolbox Screen press ENABLE SOUNDER 2 A confirmation screen will be displayed Press OK Zone ReportingTest To...

Page 43: ...est report to the Central Station Exiting the Walk Test Mode will send a stop test report to the Central Station To perform a walk test follow these steps 1 From the Installer Toolbox screen press WAL...

Page 44: ...Installer Toolbox TelephoneTest The telephone test checks the land line connection to the Central Station through the Control Panel s built in digital communicator The test is accessed through the Us...

Page 45: ...s Industry Canada Notices NOTICE The ringer equivalence number REN assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone int...

Page 46: ...exit delay restart 0 1 1 enabled Q QUESTION DEFAULT Q 28 Select quick exit 0 1 1 enabled Q 29 Enter periodic test in days 0 255 30 days Q 31 Enter cancel time in minutes 5 255 5 minutes Q 32 Select c...

Page 47: ...126 LAUNDRY 127 LEFT 128 LEVEL 129 LIBRARY 130 LIGHT 131 LIGHTS 132 LIQUOR 133 LIVING 134 LOADING 135 LOCK 136 LOFT 137 LOW WORD 138 MAIN 139 MAINTENANCE 140 MASTER 141 MEDICAL 142 MEDICINE 143 MENU...

Page 48: ...46 Notes...

Page 49: ...47 Notes...

Page 50: ...panel internal features 4 Control panel location 5 Control panel location height 5 Control panel mounting 11 Control panel mounting plate 8 Control panel wiring 11 Control panel wiring diagram 2 Cross...

Page 51: ...31X telephone jack 9 S Saving programming 39 Security screen 12 Select keyfob remote arming mode on system not ready 38 Select siren mode 38 Sensor signal loss through materials 5 Sensor types 18 Sens...

Page 52: ...v1 9 233497 E Copyright 2012...

Reviews: