MODEL: R3-NMW1F

R3-NMW1F SPECIFICATIONS

ES-8286 Rev.0   Page 1/12

http://www.m-system.co.jp/

Remote I/O R3 Series

MODBUS INTERFACE MODULE

(Modbus Wired Communication, Modbus-RTU Transparent
900 MHz Band Devices Use)

154

(6.06)

280

(11.02)

mm (inch)

27.5 (1.08)

MODEL: R3–NMW1F-[1][2]

ORDERING INFORMATION

• Code number: R3-NMW1F-[1][2]
Specify a code from below for each [1] and [2].
  (e.g. R3-NMW1F-N/E/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] POWER INPUT

N: No power supply

AC Power

M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
 47 – 66 Hz)*

DC Power

R: 24 V DC

(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *

* Not selectable for use with independent power modules or
network modules with the internal power input options.

[2] OPTIONS (multiple selections)

Antenna

/S: Sleeve antenna
/E: Rooftop antenna

Other Options

blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to M-System's web site.)

/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

FUNCTIONS & FEATURES

• Equipped with 900 MHz band wireless device
• Uses Modbus-RTU protocol wired com. as main network,
and monitors I/O signal with wireless
• Available to use wireless device as main network
• Wireless deive incorporates a module conforming to FCC
part 15, and can be used within the United States only.
• Modbus-RTU gateway function available, outputs data
received with wireless to wired network

RELATED PRODUCTS

For the details of the wireless device related products,
please refer to M-system website.
• PC configurator software (model: R3CON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC.  Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
Maintenance software
 Maintenance console: MH920 Console for International
(model: MH920CI) (OKI)
(Maintenance software is downloadable at M-System’s web
site.)
Coaxial cable
• 7.5 m extension cable for rooftop antenna (model: CX-
SAC0SAD0Q0750) (OKI)

PACKAGE INCLUDES...

• Terminating resistor (110 Ω, 0.25 W)

GENERAL SPECIFICATIONS

Connection
 Wireless network: SMA coaxial connector
 Wired network: Tension clamp terminal (Front Twin
connection)
  Applicable wire size: 0.2 - 1.5 mm

2

, stripped length: 10 mm

 Internal bus: Via the Installation Base (model: R3-BSx)
 Internal power: Via the Installation Base (model: R3-BSx)
  Power input, RUN contact output: M3 separable screw
terminal (torque 0.5 N·m)
Maintenance: Mini USB type B female connector
Screw terminal: Nickel-plated steel
Isolation: Modbus to internal bus or internal power or

Summary of Contents for R3 Series

Page 1: ...less device as main network Wireless deive incorporates a module conforming to FCC part 15 and can be used within the United States only Modbus RTU gateway function available outputs data received wit...

Page 2: ...in use Transmission configuration Multidrop Gateway funcion in use WIRELESS SPECIFICATIONS Communication Standard IEEE802 15 4g Frequency 900 MHz band 902 928 MHz Max Tx power 20 mW Bandwidth 400 kHz...

Page 3: ...Short address 0000 invalid 0001 to FFFD hexadecimal 4 digits 0000 Network name English one byte characters within 16 characters one byte space _ are usable Blank Encryption key 0000 0 to FFFF F hexad...

Page 4: ...ONNECTIONS SLAVE MODE Tx Rx Tx Rx SG Rx Rx HOST PC DA DB DG SLD FE R3 NMW1F DA DB DG SLD FE R3 NMW1F FG FG TERMINATOR GATEWAY MODE DA DB DG SLD FG SLAVE DEVICE DA DB DG SLD FG SLAVE DEVICE DA DB DG SL...

Page 5: ...s 08 Diagnostics 09 Program 484 10 Poll 484 11 Fetch Comm Event Counter 12 Fetch Comm Event Log 13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave read wr...

Page 6: ...ted slot to 0 Error Status indicates error status for each module as described below The bit corresponding to such module turns to 1 R3 TSx R3 RSx R3 US4 Input burnout R3 DA16A Power input in error or...

Page 7: ...28 Slot 2 129 192 Slot 3 193 208 Slot 4 209 224 Slot 5 225 240 Slot 6 241 256 Slot 7 For Coil 0X and Inputs 1X addresses 16 times assigned data areas Data Allocation Type are allotted with the Data Al...

Page 8: ...n case of CLSE R5 integer obtained by multiplying unit value A by 1000 ACCUMULATED COUNT DATA 32 bit data models R3 PA2 PA4A WT1 WT4 etc 32 bit binary data is used for accumulated counts and encoder p...

Page 9: ...ASSIGNMENTS unit mm inch 109 4 29 45 1 77 200 7 87 TERMINAL COVER 109 4 29 2500 98 43 Dia 3 12 Dia 1 2 05 Dia 27 1 06 36 1 42 80 3 15 WITH SLEEVE ANTENNA WITH ROOFTOP ANTENNA 19 75 1 2 3 4 5 6 150 5...

Page 10: ...protective conductor terminal FE SLD DG DB DA To Other Modbus Devices 5 Configuration Jack JACK USB CONNECTOR Maintenance Connector ANTENNA CONNECTOR 1 4 RUN RUN RUN CONTACT OUTPUT 2 3 6 FE1 U V POWE...

Page 11: ...TCP and RTU protocol Also Gateway function allows to communicate with slave devices connected in multi drop configuration with wired network using Modbus and RTU protocol Wireless Gateway model WL40E...

Page 12: ...MODEL R3 NMW1F R3 NMW1F SPECIFICATIONS ES 8286 Rev 0 Page 12 12 http www m system co jp Specifications are subject to change without notice...