4400 Series UPS Seismic Kit Installation Instructions – 94016-002

4400 Series UPS Seismic Adapter Kit  

Installation Instructions

Date: March 2020

Doc. No.: 94016-002

The  4400  Series  cabinets  can  be  installed  to  meet  California  OSHPD  seismic  specifications  using  the 

optional Seismic Kit and the floor anchorages specified below. 
These instructions describe how to install the seismic adapter kits on the 4400 Series UPS, Battery , and 

Auxiliary Cabinets.  There is a SEISMIC KIT for each cabinet style:  15-30 kVA, 50 kVA, and 80 kVA.  

 

1.  4400 15-30kVA 

Seismic Installation

 2

.  4400 50kVA 

Seismic Installation

 3

.  4400 80kVA 

Seismic Installation

1     4400 15-30kVA Seismic Installation

Table 1 lists the contents of the 4400 15-30kVA Seismic Kit.  

Figure 1.1

 shows the order of assembly for 

the [bolt + lock washer] fastener group. 

TABLE 1  15-30KVA SEISMIC CONTENTS

440300SEISMICKIT Contents

No.

P/N*

Description

Quan

1

93437 TOP SEISMIC  BRACKET 30kVA)

1

3

67813 BASE MOUNTING BRACKET, 

1

4-a

Hex Bolt, 1/4—20,1-1/2”

1

4-b

Flat Washer, 1/4

1

4-c

E—Ring, F/0.25 Shaft

1

11-a

Hex Bolt, 5/16—18 x 1”

10

11-b

Lock Washer, 5/16

10

11-c

Flat Washer, 5/16

10

94016 4400 Seismic Kit Installation 

Manual

1

a
b

c

FIgUrE 1.1: FASTENEr 

grOUP (BOLT +LOCK WASH-

Er + WASHEr)

Cabinet Footprint

1.75 in

(44.4 mm)

2.75 in

(70 mm)

2.0 in

(51 mm)

Conduit Knock-out

(3 Places)

34.05 in. (865 mm)

12 in (305 mm)

12 in (305 mm)

9.22 in (234 mm)

4.28 in  (109 mm)

5.55 in 

(141 mm)

Base Plate Footprint

1/2 in. Bolt (6)

FIgUrE 1.2: 15-30KVA SEISMIC 

ANCHOrAgE - FLOOr PATTErN

Summary of Contents for 4400 15-30kVA Seismic

Page 1: ...VA Seismic Installation Table 1 lists the contents of the 4400 15 30kVA Seismic Kit Figure 1 1 shows the order of assembly for the bolt lockwasher washer fastener group TABLE 1 15 30KVA SEISMIC CONTENTS 440300SEISMICKIT Contents No P N Description Quan 1 93437 TOP SEISMIC BRACKET 30kVA 1 3 67813 BASE MOUNTING BRACKET 1 4 a Hex Bolt 1 4 20 1 1 2 1 4 b Flat Washer 1 4 1 4 c E Ring F 0 25 Shaft 1 11 ...

Page 2: ...o the floor anchors installed in Step 1 7 Roll the 15 30 kVA UPS cabinet between the two vertical sides of the Base Mounting Bracket 4 Figure 1 6 8 Line up the UPS so the bolt holes on the Bottom Seismic Brack ets line up with the holes on the Seismic Base Plate vertical sides 9 Secure the UPS to the Seismic Base Plate using the remaining eight 8 fastener group 11 Insert the bolts through the Seis...

Page 3: ...PS Seismic Kit Installation Instructions 94016 002 15 30 kVA Seismic Adapter Kit Cont 11 11 11 11 11 11 Slide UPS into Base Plate Figure 1 6 INSTALLING ON SEISMIC BASE PLATE Figure 1 7 SEISMIC DOOR ANCHOR 15 30 KVA 4 ...

Page 4: ...4 4400 Series UPS Seismic Kit Installation Instructions 94016 002 Figure 1 8 SEISMIC 15 30 KVA DIMENSAIONAL DRAWING ...

Page 5: ... placement in Step 1 Figure 2 4 3 Table 2 lists the components of the 50kVA Seismic Kit Figure 2 2 shows the Seismic anchorage components in the Seismic Kit for the 50kVA cabinets 4 Assemble the fastener groups in Table 2 7a 7c 10a 10c and 11a 11c as shown in Figure 2 1 5 Secure the Top Seismic Bracket 5 to the top rear of the UPS using three 3 fastener group 11 Figure 2 5 6 Position the UPS over ...

Page 6: ...olt Anchor 6 Figure 2 6 BOTTOMSEISMICBRACKETINSTALLATION FLOOR AND ANCHORS NOT SHOWN 11 11 11 11 11 11 11 11 Bottom Bracket P N 67193 6 6 Figure 2 4 50KVA SEISMIC ANCHORAGE WALL PATTERN 5 16 in Bolt Anchor 4 7 0 in 178 mm 75 01 in 1905 mm 7 0 in 178 mm 10 0 in 254 mm 5 0 in 127 mm 14 03 in 356 mm Seismic Mounting Channel 32 1 in 816 mm 4 06 in 103 mm Figure 2 5 TOP SEISMIC BRACKET INSTALLATION 11 ...

Page 7: ...it Installation Instructions 94016 002 7 7 Anchor Bolt 5 16 in x 18 Press Nut 5 16 in x 18 Bolt 5 16 in Lock Washer 5 16 Washer 11 Fastener Group Figure 2 7 50 KVA SEISMIC FLOOR ANCHOR DETAIL Figure 2 8 SEISMIC DOOR ANCHOR 50KVA ...

Page 8: ...8 4400 Series UPS Seismic Kit Installation Instructions 94016 002 Figure 2 9 SEISMIC 50 KVA DIMENSAIONAL DRAWING ...

Page 9: ...cement for ancillary battery and or Auxiliary cabinets Figure 3 3 2 Prepare the wall anchorages Key measurements off the an chorage placement in Step 1 Figure 3 4 3 Table 3 lists the components of the 80kVA Seismic Kit Figure 3 2 show the Seismic anchorage component in the Seismic Kit for the 80kVA cabinets 4 Assemble the fastener groups in Table 3 7a 7c and 11a 11c as shown in Figure 3 1 5 Secure...

Page 10: ...7 1 in 689 mm 2 5 in 64 mm 2 5 in 64 mm 37 2 in 944 mm 32 1 in 816 mm 5 8 in Bolt Anchor 4 Figure 3 4 80KVA SEISMIC ANCHORAGE WALL PATTERN 5 16 in Bolt Anchor 4 7 0 in 178 mm 74 98 in 1904 mm 7 0 in 178 mm 10 0 in 254 mm 5 0 in 127 mm 13 55 in 344 mm Base C Channel 32 1 in 816 mm 11 11 11 Figure 3 5 TOP SEISMIC BRACKET INSTALLATION 5 ...

Page 11: ...11 4400 Series UPS Seismic Kit Installation Instructions 94016 002 Figure 3 6 SEISMIC 80 KVA DIMENSAIONAL DRAWING ...

Page 12: ...This Page Left Intentionally Blank ...

Page 13: ......

Page 14: ...EMS GROUP POWER ELECTRONICS DIVISION 13131 West Little York Road Houston Texas 77041 9990 Tel 855 803 7087 Fax 713 896 5212 US 800 231 1412 Canada 800 872 2192 Mexico 01 800 527 1204 https www toshibaups com Printed in the U S A ...

Reviews: