INTRODUCTION

Use the Model XLS-MLE6(R)-ADPT Adapter Kit from Siemens Industry, Inc., to
upgrade existing MXL Systems installed in Model MLE-6(R) backboxes to FireFinder-
XLS/Desigo Fire Safety Modular/Cerberus PRO Modular Systems. The XLS-MLE6(R)-
ADPT Adapter Kit consists of an adapter plate, inner door and outer door. The XLS-
MLE6-ADPT (S54430-C9-A1) inner and outer doors are black; the XLS-MLE6R-ADPT
(S54430-C9-A2) inner door is black and outer door is red. The XLS-MLE6-ADPT and
the XLS-MLE6R-ADPT are identical in all other ways and will be referred to in the
remainder of this document as XLS-MLE6-ADPT.

The adapter plate installs over the existing studs in an MLE-6(R) backbox with the
#1/4 x 20 hex flange nuts supplied and provides studs on which to mount three
CAB-MP mounting plates (P/N 500-633012) and two PTB power termination boards
(P/N 500-033390).

The outer door consists of the door frame and three removable panels. Each remov-
able panel is secured to the door with #10-32 nuts. The removable panels may be
clear (OD-LP), blank (OD-BP/-R), or vented (OD-GP/-R) depending on the application.
The OD-BP-R and OD-GP-R panels are red. The outer door is attached to the backbox
by hinge pins and secured to the backbox by a keyed latch.

The inner door has three openings in it for the installation of an operator interface and
other modules. There are eight threaded studs around each opening on the inner
door. These threaded studs allow equipment installation on the door. The equipment
is secured by #10-32 nuts. The inner door is permanently hinged right, is attached to
the backbox by screws, and is secured to the backbox by a swell-action latch.

The XLS-MLE6(R)-ADPT is for indoor use only in dry environments.

With this conversion, the maximum battery set that can be used in the backbox is 33

AH (model BTX-1). If larger batteries are required, use either a BB-55 or CAB-BATT

battery box.

When converting an MXL to an XLS/Desigo Fire Safety Modular/Cerberus PRO
Modular system, it may be necessary to use the XLS-EXT-CABLE-PKG (S54430-K1-
A1). This kit includes a 58 inch 60-pin Data Bus cable, a 58 inch 6-pin CAN Bus cable
and a 20 inch 12AWG ground wire.

To convert an MLE-6(R) backbox from an MXL System to an XLS/Desigo Fire Safety
Modular/Cerberus PRO Modular component system, you must first disassemble the
MXL and then assemble the XLS/Desigo Fire Safety Modular/Cerberus PRO Modular.
This two-part procedure is described in detail on page 2.

Summary of Contents for XLS-MLE6(R)-ADPT

Page 1: ...panel is secured to the door with 10 32 nuts The removable panels may be clear OD LP blank OD BP R or vented OD GP R depending on the application The OD BP R and OD GP R panels are red The outer door is attached to the backbox by hinge pins and secured to the backbox by a keyed latch The inner door has three openings in it for the installation of an operator interface and other modules There are e...

Page 2: ...S MLE6 ADPT are installed separately The adapter plate is installed first followed by the inner door and then the outer door Adapter Plate The XLS MLE6 ADPT adapter plate has 18 holes in it that fit over the studs in the MLE 6 backbox in only one way 1 Place the XLS MLE6 ADPT over the studs in the backbox and secure it in place with the six 1 4 x 20 hex flange locknuts supplied in the locations ma...

Page 3: ... The stud marked D is a lug for grounding the AC input Remove the ground lug before mounting the PTB After installing the PTB be sure to reinstall the ground lug 5 There is room in the bottom of the enclosure for a battery set of up to 33 AH 6 System cards can be installed in the CC 5 CC 2 cardcage s as required Install the Inner Door Install the inner door by following the steps listed below 1 Pl...

Page 4: ... as needed for system operation 8 Insert blank plates as needed in unused spaces on door and secure with 10 32 nuts Refer toTable 1 and Figure 3 1 E L B A T S E T A L P R O O D R E N N I L E D O M N O I T P I R C S E D G N I T N U O M P M D I 6 M C F r o f t e k c a r b e t a l p g n i t n u o M M C B d n a 8 M C S 8 M C L d e r u c e S r o o d n i s d u t s n o s t n u o M s t u n 2 3 0 1 o w t h...

Page 5: ... P N A5Q00075194 on the inside of the outer door 2 E L B A T S E T A L P R O O D R E T U O L E D O M N O I T P I R C S E D G N I T N U O M P L D O e s u r o f e t a l P s n e L r a e l C f o n o i t a c i d n i l a u s i v n e h w d e r i u q e r s i n o i t a r e p o m e t s y s r o o d n i s d u t s n o s t n u o M s t u n 2 3 0 1 t h g i e h t i w d e r u c e S R P B D O n e h w e s u r o f e t...

Page 6: ... R Figure 4 Outer Door and Plates 4 A ground wire comes installed on the inside of the outer door Refer to Figure 5 Bring the free end of the ground wire through the opening at the top left hand side of the inner door and secure it in place on an unused stud in the backbox with a 10 32 hex nut user supplied ...

Page 7: ...or and secure with the key latch WIRING In compliance with NEC Article 760 all power limited fire protective signaling conductors must be separated a minimum of inch from all of the following wiring located within a control panel electric light power Class 1 or non power limited fire protective signaling conductors To meet these requirements the following guidelines must be observed when installin...

Page 8: ...er limited wiring Wiring must be in the shortest route and must not overlap any other wiring Power Limited Wiring Wiring entering the enclosure from the top and the left side of the backbox is considered power limited Wiring must be in the shortest route and must not overlap any other wiring Use the existing lances in the backbox to dress the wires as needed to maintain separation of power limited...

Page 9: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Page 10: ...Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada Document ID A6V10328630_en _b ...

Reviews: