background image

A5E0100017867D-04

         

GN: 30400_D200-300-400  

Manual Edition 12/2006

Siemens Aktiengesellschaft
Automation and Drives (A&D)
Sensors and Communication
Process Sensors 
76181 KARLSRUHE
GERMANY

Display recorders

SIREC D200
SIREC D300
SIREC D400

www.siemens.com/processinstrumentation

Displa

y r

ecor

der

s  SIREC  D200, D300, D400

12/2006

Manual Edition 

sirec

A5E01001767-04

@ 1 P A 5 E 0 1 0 0 0 1 7 6 7 @

A5E01001767

Summary of Contents for SIREC D200

Page 1: ...Automation and Drives A D Sensors and Communication Process Sensors 76181 KARLSRUHE GERMANY Display recorders SIREC D200 SIREC D300 SIREC D400 www siemens com processinstrumentation Display recorders SIREC D200 D300 D400 12 2006 Manual Edition sirec A5E01001767 04 1PA5E010001767 A5E01001767 ...

Page 2: ......

Page 3: ... 3 Hazardous Voltage 4 Section 2 Installation 5 Environment and Location 5 Mechanical Installation 6 Installation Instructions 9 Electrical Installation 13 Installation Category 13 Analogue Input Card 16 SIREC D200 Analogue Input Standard card 19 Analogue Output Card 21 Pulse Input Card 22 Transmitter Power Supply Card 24 Alarm Relay Cards Digital Input Output Cards 24 Communications Connections 2...

Page 4: ...atch Control 117 Recording Menu 120 Messages Menu 122 Process Menu 125 Status Menu 127 Finish 140 Section 5 Password Security 141 Log On Off 141 Users and Groups 141 Administrator 141 Password Policy 143 User Interface requirements 144 Audit Trail 144 Level Permissions 145 Default Password Access 147 Section 6 Screen Configuration 155 Process Screen Overview 155 Menu Bar 156 Screen Menu Bar 157 Re...

Page 5: ... Modbus Capabilities 197 OPC Interface Open Process Control 198 Web Browser 199 Internet Security Settings 200 Section 9 PC Software Suite 201 The SIREC D Software Suite 201 System Requirements 202 Section 10 Spares List 203 SIREC D300 Recorder 203 SIREC D400 Recorder 207 SIREC D200 Recorder 212 Section 11 Instrument Care and Maintenance 217 Cleaning Instructions 217 Backlights 217 Operating Tempe...

Page 6: ... with a Specified Temperature 249 External Input Reference 250 Appendix D Alarms 251 Alarms Menu 251 Appendix E Ethernet 253 Ethernet 253 Email 254 General operation of the e mail system 254 Appendix F Fuzzy Logging 255 Appendix G F sub zero Sterilisation 259 The significance of F0 259 Appendix H Calibration 261 AI Calibration and CJC Calibration 261 Sensor Compensation 261 Appendix I Battery Data...

Page 7: ...entation to accompany these recorders are Notes The contents of this manual are correct at the time of issue The contents may change at any time without prior notification This is due to continuous develop ments to the recorder and it s functionality Every effort has been made to ensure the accuracy of this document however should there be any anomalies found please contact SIEMENS All rights are ...

Page 8: ...cations Symbols One or more of the following symbols may appear on the recorder labelling Static Electricity All circuit boards and electronic modules associated with this recorder contain components which are susceptible to damage caused by electrostatic discharge Should it be necessary to handle such components appropriate precautions in accordance with ANSI ESD S20 20 Electrostatic Discharge Co...

Page 9: ...ing device to mate with a socket outlet in the building 2 Whenever it is likely that protection has been impaired the recorder should be made inoperative and secured against operation The manufacturer s service centre should be contacted Table 1 3 Symbol Description WARNING The WARNING symbol indicates a potentially hazardous situation which if not avoided could result in death or serious injury C...

Page 10: ...RNING 7 If the equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be inadequate 8 The protective earth terminal must remain connected even if the recorder is isolated from the mains supply if any of the measuring communications or relay terminals are connected to hazardous voltages Hazardous Voltage Hazardous Voltages are defined by EN61010...

Page 11: ... to recorder spec Including a CJC connector for Thermocouple operation Quick Start Guide to get you started First time Password system instructions for ESS recorders only CD Viewer software documentation Plastic stylus x 2 for use with the touch screen Manual optional Hard copy English French or German Any other items ordered as an option Re packing Environment and Location The recorder is designe...

Page 12: ... right 45 looking down and 55 looking up at the recorder display SIREC D200 45 from the left or right 10 looking down and 30 looking up at the recorder display Panel cut out size for the SIREC D300 and SIREC D200 recorders NOTICE The SIREC D200 recorder is an Emmisions Class A product In a domestic environ ment this product may cause radio interference in which case the user may be required to tak...

Page 13: ...EC D400 recorder The SIREC D300 SIREC D400 and SIREC D200 recorders are DIN Standard sizes and should be panel mounted Panel Cut out Panel Cut out Panel Cut out 281 00 11 06 281 00 11 06 20 00 0 787 20 00 0 787 Please note the recommended spacing for adjacent mounting Figure 2 2 SIREC D400 Panel cut out ...

Page 14: ...D300 Dimension details 4 Mounting clamp positions For standard units fit only two brackets on opposite sides of the unit either top and bottom or left and right slots NEMA 4X rated recorders require all four mounting brackets to be fitted Figure 2 3 SIREC D300 Recorder dimensions ...

Page 15: ...om the front of the panel Two mounting clamps are supplied and can be fixed either on the top and bottom sides or on the left and right sides of the case 4 Mounting clamp positions For standard units fit only two brackets on opposite sides of the unit either top and bottom or left and right slots NEMA 4X rated re corders require all four mounting brackets to be fitted Figure 2 4 SIREC D400 recorde...

Page 16: ... D200 Dimension details Figure 2 5 SIREC D200 recorder dimensions 4 Mounting clamp positions For standard units fit only two brackets on opposite sides of the unit either top and bottom or left and right slots NEMA 4X rated recorders require all four mounting brackets to be fitted ...

Page 17: ...and do the same but in the diagonal position to the opposite side See Figure 2 3 on page 8 6 Tighten the screw using a flat blade screwdriver and the clamp will secure against the panel SIREC D400 1 Insert the panel gasket onto the recorder so it goes between the back of the recorder bezel and the panel From the front panel place unit in the panel and push through the panel 2 To loosen each clamp ...

Page 18: ... clamp positions required on two opposite sides of the recorder Nema 4X requires all 4 clamps to be fitted Mounting clamp slots Figure 2 1 SIREC D300 and SIREC D200 Mounting clamp Figure 2 2 SIREC D400 Mounting clamp 4 mounting clamp positions 2 shown 2 clamps are re quired on opposite sides of the recorder ...

Page 19: ...Before performing any installation please read the section on Safety on page 2 and Warnings and Safety Precautions on page 3 All connections to the unit are made via the rear panel the layout of which is shown in Fig ure 2 3 on page 14 Note The SIREC D200 Analogue Input card Slot A Cable screen must be well connected to the recorder case using a low impedance bond Also avoid use of a length of wir...

Page 20: ...V DC 10 absolute limits are 20V to 30V DC Also accepts 20 to 25V AC CAUTION UNIT DAMAGE CONTROL To protect against component failures the user should fit an external fuse for the DC input power supply The value should be 4A time delay high breaking capacity mini mum 60Vdc rated Failure to comply with these instructions may result in product damage WARNING HAZARDOUS VOLTAGES When using the recorder...

Page 21: ...ue Output or Pulse Input Slot A Slot B Slot C Slot D Slot E Slot F Alarm Relay or Digital I O Slot G Slot H Slot I Ethernet RS485 USB Host Figure 2 4 SIREC D400 Rear panel CJC Sensor position in the middle of the Analogue Input connector Slots A F Table 2 1 Card priority positions Cards SIREC D300 SIREC D400 SIREC D200 Analogue Input card A B A B C D E F A B option Analogue Output card B E F Pulse...

Page 22: ... 6 analogue input cards fitted up to 48 input channels The slot positions A B C D E or F these are identified on the rear panel PC boards are fitted in order slot A starts from the top The SIREC D200 can use this card as an additional Analogue Input card fitted in Slot B pro viding up to 6 more channels This card would be used after using the 3 or 6 channel stand ard SIREC D200 Analogue Input card...

Page 23: ... a channel can be safely connected to a hazardous voltage up to 300V AC common mode with respect to earth However where a channel is connected to a safety low voltage circuit an immediately adjacent channel must be adequately insulated from hazardous voltages between 150V AC and 300V AC max This insulation should comprise of at least 1 5mm air gap or a bar rier rated greater than 1400V AC This is ...

Page 24: ...el numbers 9 to 14 The standard fit Analogue Input card is fitted in slot A with up to 6 channels channels numbers 1 to 6 To fit this option card into the SIREC D200 recorder you will require an expansion card to interface to the recorder See SIREC D200 Analogue Input Standard card on page 19 CAUTION CONTROL UNIT DAMAGE Do not apply a hazardous live voltage between and pins within a channel eg 60V...

Page 25: ... connector resides between channel 4 and channel 5 on the Analogue Input card For information on connecting the CJC sensor see Figure 2 6 on page 18 For the SIREC D200 recorder this is available on the Analogue Input card option SIREC D200 Analogue Input Standard card The SIREC D200 is fitted with a standard Analogue Input card in Slot A with up to 6 chan nels The card is also fitted with an Ether...

Page 26: ...ow voltage circuit is fully maintained The inputs are divided into two banks inputs 1 to 3 are one bank and inputs 4 to 6 if fitted are another bank A voltage of up to 150V AC common mode can be applied on one bank as long as any safety low voltage circuits are on the other bank The recorder is protected against accidental connection of a voltage up to 240V AC common mode which might occur as a te...

Page 27: ...ny external voltage Alternatively if an ohms or R T sensor must be biased to an external voltage ensure that the other two channels within the same input bank are floating or are biased to the same voltage i e inputs of all three channels connected to the same voltage Failure to comply with these instructions may result in product damage WARNING HAZARDOUS VOLTAGES Insulation from channel to channe...

Page 28: ...e rear of the unit The Pulse Input card position for the SIREC D300 is shown in Figure 2 3 on page 14 and Figure 2 4 on page 15 for the SIREC D400 The Pulse Input card is not available on the SIREC D200 recorder however the 8 Digital I O option card has 4 channels that can be set as pulse inputs channels 1 to 4 The operat ing frequency for pulse inputs on the Digital I O card is 1kHz max Input Low...

Page 29: ...ZARDOUS VOLTAGES Insulation from channel to channel Normally a channel can be safely connected to a hazardous voltage up to 300V AC common mode with respect to earth However where a channel is connected to a safety low voltage circuit an immediately adjacent channel must be adequately insulated from hazardous voltages between 150V AC and 300V AC max This insulation should comprise of at least 1 5m...

Page 30: ...5 The SIREC D200 has a 24V DC 130mA Transmitter Power Supply card that can be fitted as an option Connection is made via a 2 way connector at the rear of the unit the mating half is supplied with this option For connector position see Figure 2 3 on page 14 The 24V transmitter power supply is not isolated from the recorder and is not referenced to ground The option card also has an RS485 Modbus por...

Page 31: ...on C and Normally Open NO A Form C dry contact relay is used for this type of card The inputs are designed to accept Dry contact no volt inputs The relays should be used for non inductive loads only where a device requires a voltage to operate it such as a 12 Volt buzzer connect it to the normally open NO contacts unless the fail safe setting is activated The maximum voltage which may be used with...

Page 32: ... the second 8 channels The pin outs for 8 and 16 I O cards are labelled from left to right 1 to 16 on the left side and 17 to 32 on the right Each channel can be set up as an input or an output For output the relay is normally open type A Form A dry contacts relay is used for this type of card The inputs are designed to accept Dry contact no volt inputs Table 2 6 Alarm Relay card 4 channel Alarm R...

Page 33: ...digital input cards can be used as a relay card if required The 16 channel Digital I O card is not available on the SIREC D200 Table 2 7 Digital Input card 8 channel Digital Input card 16 channel Card position Channel number Card position Channel number Slot G 1 to 8 Slot G 1 to 16 Slot H 17 to 24 Slot H 17 to 32 Slot I 33 to 40 Slot I 33 to 48 NOTICE For Digital Inputs short together the 2 pins o...

Page 34: ...ied Diagram shows a view looking from the rear of the unit SIREC D200 Comms card An option card is available with RS485 Modbus port and USB device connections The card can be purchased and fitted at any time The RS485 connection uses a 3 way connector The card also has connection for 24V DC Transmitter Power Supply see Transmitter Power Supply Card on page 24 To fit this option card into the SIREC...

Page 35: ...n cards Analogue Input card in Slot B up to 6 channels Four Relay output card 8 Relay 2 Digital Inputs card 6 fixed Outputs 2 Configurable DI DO 8 Configurable Digital Inputs Discrete 24V Output card Comms card 24Vdc Transmitter Power Supply Rear USB Port RS485 Comms Port USB Devices Print Support Print Support is a firmware option that can be activated using the credit system refer to the Options...

Page 36: ...ted Barcode Reader Most USB barcode readers emulate keyboards and cause no recognition problems Exam ples of tested barcode readers are Dell Model SK 8115 Keyboard IBM ACC42 with USB hubs Dell Model C BG17 Dual Cordless Keyboard and Mouse Combination IBM SK 8815 with USB hubs Logitech Model LX300 Cordless Keyboard and Mouse Combination IBM SK 8806 with USB hubs Peninsula Phoenix 2 Wasp WWR 2905 Pe...

Page 37: ...SB ports for keyboard mouse and storage D300 Up to 32 Totalisers 1 per pen D200 Up to 24 Totalisers 1 per pen D400 Up to 96 Totalisers 1 per pen 24V Transmitter Power Supply 24V Power Supply D300 Up to 16 Digital Inputs 24V Outputs D400 Up to 48 Digital Inputs 24V Outputs D200 Up to 8 Digital Inputs 24V Outputs D300 Up to 8 Relay Alarm Outputs D400 Up to 24 Relay Alarm Outputs D200 Up to 8 Relay A...

Page 38: ...ct Flash cards and USB keys Compact Flash not available for the SIREC D200 No moving parts all solid state flash memory Security Stringent Total Data integrity Password Protection 21CFR Part 11 ESS Extended Security System Plus Health Watch for preventative maintenance Remote Access Advanced Software Data Analysis at your PC Independent Chart and Logging speeds Global Language Support Rapid review...

Page 39: ...uts and the SIREC D400 has up to 48 Ana logue inputs and the SIREC D200 has up to 12 Analogue inputs 70Mb to 400MB of expandable non volatile flash memory available plus additional removable storage media All recorders use digital colour TFT LCD screens to provide easy to read displays with wide viewing angles for the best all around data viewing The touch screen operator interface provides fast e...

Page 40: ...eb fast and convenient Dynamic Host Configuration Protocol DHCP automatically acquires the settings IP address for network communications from a DHCP server RS485 Modbus the RS485 connection allows process data to be transferred to other devices or to record data received in MODBUS RTU protocol slave mode only A Comms option card and expansion card are required for the SIREC D200 recorder Simple N...

Page 41: ...g to remember file names Password Protection Up to 4 levels of password protection with up to 50 different users are available Multiple levels of password protection and an audit trail of actions enhance the security of the data Extended Security System option ESS provides features including entry of unique User ID s and associated passwords time out of password entry password expiration and trace...

Page 42: ...data to be dis played and stored at the rates that best suit the application Language Support standard language prompts for English UK US French German Italian Spanish Brazilian Polish Hungarian Slovakian Czech Turkish Romanian Rus sian Portuguese and Greek Logarithmic Scales all displayed scales can be set as linear or logarithmic max 99 decades Enclosure rating standard NEMA 3 IP54 type front fa...

Page 43: ...ure selected recorder functions only 8 Digital I O available for the SIREC D200 recorder Pulse Frequency four frequency inputs per board are available to measure pulse signals up to 25 kHz max 2 cards Not available for the SIREC D200 recorder but 4 pulse inputs can be used on the Digital I O option card Pulse Inputs The 8 Digital I O option card has 4 channels that can be set as pulse inputs first...

Page 44: ...recorder has up to 20 screens available for displaying combinations of charts bars and DPMs can be configured 4 examples below Horizontal Chart 8 Vertical Bars 8 DPMS 16 Horizontal Bars showing Max Min values and Totals for each pen 16 Digital Panel Meters showing Max Min values and Totals for each pen DPM and Scales ...

Page 45: ...IREC D300 recorder has up to 12 screens available fopr displaying combinations of charts bars and DPMs can be configured 6 examples below 8 Digital Panel Meters 8 Horizontal Bars Horizontal Chart 4 Vertical Bars and 4 DPMs Horizontal Chart and DPMs DPMs and Scales Vertical Chart 8 Horizontal Bars and 8 DPMs ...

Page 46: ...REC D200 recorder has up to 10 screens available for displaying combinations of charts scales and DPMs can be configured 6 examples below 6 Digital Panel Meters 3 Horizontal Bars Horizontal Chart 3 Vertical Bars Horizontal Chart and 6 DPMs Horizontal Bars and DPMs Vertical Chart 3 Horizontal Bars and 3 DPMs ...

Page 47: ...t Slot A Slot B Alarm or Digital I O Slot G RS485 100 250VAC Rear Panel AC power is connected via the standard configuration IEC chassis plug on the rear panel CJC Sensor Wire seal AC supply 100 250VAC 24V TX Power Supply Output RS485 port and USB Host option Up to 6 Analogue Inputs and Ethernet std Earth screw ground 20 to 30VDC 20 to 25VAC Input 24VInstrument power option Analogue Input card Slo...

Page 48: ...er option Analogue Input Pulse Input Slot A Slot B Slot C Slot D Analogue Input Pulse Input Analogue Output Slot E Slot F Alarm or Digital I O Slot G Slot H Slot I RS485 USB Host AC supply 100 250VAC Common Relay Output SPNC 24V TX Power Supply Output 100 250VAC Rear Panel AC power is connected via the standard configuration IEC chassis plug on the rear panel CJC Sensor Slots A to F ...

Page 49: ... is a special slot at the top of the recorder to slide the stylus in from the right If the touch screen does not match correctly to where you are touching it with the stylus the screen may need calibrating See Calibrate on page 116 Other User Interface Control All user actions can be performed using a mouse or keyboard attached to a USB host port Power up 1 Menu Access When the recorder is powered...

Page 50: ...is removed once the password system has been configured Log Off Once the user has logged on the option in the Main Menu will turn to Log Off once selected the user is logged off and returned to the current process screen First Time Log On The first time the system is used a default user name and password is available the user name is Admin and will have no password this is known as the first time ...

Page 51: ...e Options item in the Credits menu and enable the firmware options you require by changing the cross to a tick check symbol When the configuration is complete select the Finish button to Commit Discard or Commit Later Select the Back button to return to the previous menu Menu Path As each button is selected in the menu system a menu path will appear at the top of the screen to enable the user to k...

Page 52: ...117 Recording Start or Stop recording Export Now will transfer data to external media such as Compact Flash or USB key See Recording Menu on page 120 Messages The messages screen will display certain message areas Specific types of messages have been put into categories or all messages can be viewed See Mes sages Menu on page 122 Process Controls for any process in use eg Max Mins Totals and Count...

Page 53: ...General Screen and Recording set up See Edit Setup on page 49 Layout The user can configure how the data is presented on the screen From the Layouts screen choose to Edit Saved or Load layouts in the recorder See Layout on page 104 Passwords Manages the security and access to full password configuration that allows restricted access within the recorder providing password protection at different le...

Page 54: ...for naming the setup file Maximum of 50 characters File format is set The Compact Flash and the front USB device port are found under the front flap on the re corder There is another USB port at the rear of the recorder The first USB device fitted will be USB1 therefore the second USB device fitted is USB2 Compact Flash not available for the SIREC D200 Load Setup Main Menu Configure Setup Layout S...

Page 55: ...ices TCP IP and Network Admin Services takes you to a sub menu containing Modbus Web Email SNTP FTP and Peers menus See Comms Services Menu on page 73 Events Counters Events and counters are firmware options that can be activated using the credit system Events are certain conditions or operations which can be set up and logged according to the time and date of the occurrence See Events Menu on pag...

Page 56: ...utput card or Digital Input Out put card See Alarm Digital IO on page 56 Pulse Inputs Select this to configure each Pulse Input channel See Pulse Input on page 58 Not available for the SIREC D200 recorder Linearisation Tables To be used with Analogue Input type Volts Amps or Ohms These are user defined tables that can be set up to allow a non linear input sig nal to be used See Linearisation Table...

Page 57: ...nput 4 Analogue Out 33 to 40 33 to 36 33 to 36 Slot F 8 Analogue In Pulse Input 4 Analogue Out 41 to 48 41 to 44 41 to 44 Slot G 4 Relay Output 8 Relay 2 Digital In 8 Digital Input Output 16 Digital Input Output 1 to 4 1 to 8 1 to 8 1 to 16 Slot H 4 Relay Output 8 Relay 2 Digital In 8 Digital Input Output 16 Digital Input Output 17 to 20 17 to 24 17 to 24 17 to 32 Slot I 4 Relay Output 8 Relay 2 D...

Page 58: ...ample rate must be the same within each bank only for SIREC D200 recorder Range Ohms Volts and Amps only Toggle between Preset and User Defined The Preset option will make available a list of Range Types or select User Defined to specify High and Lower Limits Range Type Ohms Volts and Amps only Only available when Range is set to Pre set Select for a list of available ranges The factory default ra...

Page 59: ...n page 91 Label Select and enter a identification label for the input Select and enter a label Max 15 characters SQRT Extract Ohms Volts and Amps only Toggle On and Off The Square root extraction in the analogue input is used to linearise certain sensors that have a non lin ear output for example in the calculation of flow So when you check the Square root extraction in the Analogue input section ...

Page 60: ... this for a list of available CJ Compensation See Thermocouple CJC Compensation on page 248 Int Automatic Uses the cold junction sensor in the recorder as a variable ref erence temperature Ext 0 Deg C Assumes the cold junction is held at 0 C to provide a 0mV refer ence external to the recorder Ext with Spec Temp Uses a reference junction held at a constant tempera ture Specify the temperature that...

Page 61: ...nnel profile Enabled Toggle On and Off Allow Overrange Toggle On and Off Disabled as default this will allow the output sig nal to go overrange to 21mA if disabled the maximum is 20mA Transmit Pen Eg Select a pen to output 4 20 mA loop This will take the scale value from the pen it is transmitting and convert to 4 20mA output signal eg if the scale is 0 50 this signal will fit the scale so 4mA 0 a...

Page 62: ... Card There are 8 or 16 Digital channels per card that can be setup as inputs or outputs The Dig ital I O card also has 4 channels that can be set as pulse inputs channels 1 to 4 The op erating frequency for pulse inputs on the Digital I O card is 1kHz max Input Low 1V High 4 5V to 10V DC 9V to 20V p p AC or Volt free input Low short circuit High open circuit To view and log a channel selected as ...

Page 63: ...480 108 minutes in 0 1 sec ond increments Select and enter the pulse length Failsafe Output only Toggles On and Off Each relay channel can be independently selected with the fail safe option This will invert the state of the relay output With Fail safe Off normally open NO relays have open contacts when the power is off and open contacts when there is no active alarm The contacts will close when a...

Page 64: ...g For more information see Appendix B Maths Expressions on page 233 Press the Pulse Input button to display the available pulse inputs Click on individual Pulse Input number to set up each channel profile Enabled Toggle On and Off Hertz Fixed as Frequency Measure in Hertz Update Rate Fixed at 1Hz Label Select and enter an identification label for the pulse input Select and enter a label Up to 16 c...

Page 65: ...e required to do the conversion Click into the text entry boxes under the X and Y boxes and enter the required values or leave it if your table starts at 0 The Signal Input X goes in the first column and the Engineering units Y in the second column To add a line at the bottom click on Add To ad a line above or below click on a line and use the Insert Above and Insert Below buttons To delete a line...

Page 66: ...le They would pro duce the following curve A straight line is drawn between each point as shown by the continuous red line in Figure 4 3 For a more accurate curve as shown by the dotted line blue add more data points into the linearisation table The Linearization tables that you set up here can then be used in the Analogue In Menu on page 52 0 2 4 6 8 10 0 2 4 6 8 10 X Signal Input Y Eng Units Fig...

Page 67: ...then the signal would look like Figure 4 4 50 40 30 20 10 0 10 20 30 40 50 50 10 20 30 40 50 40 30 20 10 0 The last two points are used to follow the slope for the rest of the signal At the bottom of the 0 10V table the last two inputs are X 0 Y 0 and X 2 Y 6 At the top of the 0 10V table the last two points are X 8 Y 9 8 and X 10 Y 10 Figure 4 4 shows these last two inputs at the top and bottom o...

Page 68: ...t Logging to go to a sub menu to set up the logging configuration See Logging Menu on page 64 Alarms Select Alarms to go to a sub menu to set up the alarm profile See Alarms Menu on page 66 Totaliser Select Totaliser to go to a sub menu to set up the totaliser settings See Totaliser Menu on page 68 RAV This will display the Rolling Average for this pen The recorder takes an average of the number o...

Page 69: ...ck button to return to the previous menu Scale Menu Main Menu Configure Setup Edit Setup Pens Scale Individually configure each scale per pen in the scale menu Click on Scale to set up each scale profile per pen Units Scale measurement Units Select this and enter the units Up to 16 characters Span This is the highest value of the scale Select to enter the Span value Zero This is the bottom of the ...

Page 70: ... Notice the value has been rounded up Auto Toggle Between Automatic number for matting and User Defined After Decimal Only available when User Defined is selected Select and enter the number of decimal places up to 15 decimal places When this pen setup is complete go back to the Pen menu and complete the pen setup for all other pens Logging Menu Main Menu Configure Setup Edit Setup Pens Logging Cl...

Page 71: ...ry Method Only available if the logging Type is set to Continuous Select from a list of Methods Sample logs the last sampled reading Average logs the average of all the samples taken since the last log Max Min logs the highest and the lowest of the sampled readings since the last log Align Only available if the logging Type is set to Continuous Select and enter a value from the list to align the l...

Page 72: ...on is the how far this pen can deviate from the Ref Pen before triggering an alarm See Deviation Level and Ref Pen Rate Up and Rate Down Alarms are used to trigger an alarm when the signal changes a defined amount over a specified time See Deviation Level and Time Period Level Select and enter a figure at which the alarm is to be triggered Deviation Level Only available when Alarm Type is set to D...

Page 73: ...ated messages when the alarm becomes active From the position of the Mark on Chart the chart background colour will change to show it is in an alarm state Email Alarm Enable this to send an email when any alarm is triggered on this pen This function is a firmware option that is activated from the Factory menu Credits on page 92 Recipients Only available when email has been enabled Select your reci...

Page 74: ...econd and the total amount that has flowed over a specified time period Multiple totalisations are possible with the use of extra pens firmware Credit option Totalisation values are 10 digits plus exponent Click on Totaliser to set up the totalising profile per pen Select Totaliser from the Pen screen to display the totalising setup menu Enabled Toggles On and Off to activate or de activate totali...

Page 75: ... from the instrument onto the total after the time factor is applied You then need to Divide by the unit factor For example If your flow meter is in litres time and you want to Totalise in litres there 1 litres in 1 litre so your unit factor would be 1 so every 1 second 1 1 unit is added If your flow meter is in litres time and you want to Totalise in Cubic meters there are 1000 litres in 1 cubic ...

Page 76: ...erent processes however F values cannot be com pared unless the z values are the same When temperature is not specified for example F 8 6 it is understood that the temperature is 250F 121 11C the subscript O as in the term Fo 7 4 is used to indicate that the z 18 degrees F and the temperature is 250F 121 11C See Appendix G F sub zero Sterilisation on page 259 Displaying Totals Totals can be displa...

Page 77: ...corder for browsing if you are using DHCP Dynamic Host Configuration Protocol TCP IP Settings Static IP Toggle On and Off With this enabled the IP address will be the same every time the recorder is powered up With this feature Off the recorder s IP address is cre ated dynamically using a DHCP Dynamic Host Configuration Protocol Server With this feature On the IP address can be fixed by entering a...

Page 78: ...WINS MDNS Toggles On and Off With this deactivated the Windows Internet Name Service can be changed from the default if required Pri WINS Address This is a sub menu for DNS WINS MDNS Only available when Auto WINS is deactivated Sec WINS Address This is a sub menu for DNS WINS MDNS Only available when Auto WINS is deactivated Auto MDNS This is a sub menu for DNS WINS MDNS Toggles On and Off This wi...

Page 79: ...hared or work group printers must contain the correct file path see Printer Menu on page 98 Username Enter your network Logon username Password Enter you network password For a local printer connected directly to the recorder via USB no domain is required Ensure the printer name is set to the default LPT1 see Printer Menu on page 98 Domain For network printers enter your network domain No domain i...

Page 80: ...port which sup ports RS485 Modbus protocol and TCP IP Modbus Web Browser See Web on page 75 OPC Server connectivity to third party software OPC Server connection must be ena bled by selecting the OPC option in Credits on page 92 For more details on OPC Servers see OPC Interface Open Process Control on page 198 Rear RS485 Port A Comms option card and expansion card are required for the SIREC D200 r...

Page 81: ...d be set to 12mS min if using the Comms Server Protocol Select this for a list of available protocols Modbus or Modbus X Modbus and Modbus X can both use Ethernet or RS485 Ports Protocols define the format in which the data is transferred from the recorder to a PC or transfer between other devices and peripherals Slave ID This is a unique Modbus ID Address used by the recorder to identify Modbus m...

Page 82: ...ils One method of finding this information is to go to Microsoft Outlook Tools Email Accounts select View or change existing email accounts Select your email server from the box eg Microsoft Exchange Server and click on the Change button The server name you require is displayed in the Exchange Server Settings dialog Enter this name exactly using the on screen or USB keyboard Authentication Indicat...

Page 83: ... per line and up to 100 lines of text can be entered including Embedded Process Values on page 85 This will include specific pen data to your email Contact your IT Administrator for advice on entering Server name requirements SNTP Main Menu Configure Setup Edit Setup Comms Comms Services SNTP Simple Network Time Protocols is a protocol for synchronising the clock on the recorder with a Network Ser...

Page 84: ...o time sync with it This saves many recorders trying to time sync with the network server When the configuration is complete select the Finish button to Commit Discard or Commit Later Select the Back button to return to the previous menu FTP File Transfer Protocol Main Menu Configure Setup Edit Setup Comms Comms Services FTP This is a method of transferring data and setups to and from SIREC D soft...

Page 85: ...pe cifically requested by your IT network administrator If this is changed on the recorder it must also be changed on all other recorders Trend Server and Comms Server If you experience and security issues using peers see Internet Security Settings on page 200 Events Menu Main Menu Configure Setup Edit Setup Events Counters Events Events is a firmware option that can be activated using the credit ...

Page 86: ...e start of the totaliser In summary Cause 1 or Cause 2 will trigger Effect 1 and Effect 2 When selecting Totalisers and Alarms etc ensure they are enabled and configured in the Pens menu Table 4 2 Events Cause and Effect Cause Effect Alarm Into Alarm Mark on Chart Logging Totaliser Digital Outputs Alarm Acknowledge Email Screen Change Print Screen Counters Max Mins Reset Chart Control Clear All Me...

Page 87: ...81 A5E01001767 04 Power up Event 1 example Adding Cause 1 Event 1 example Adding Effect 2 Event 1 example Adding Effect 1 Select which Pen number and which alarm on that pen will have the alarm acknowledged Figure 4 8 Event 1 example ...

Page 88: ...e process menu see Max Min on page 125 Scheduled Events A scheduled event can be set up as a cause so that when a scheduled event occurs it trig gers an effect With scheduled events you can specify the time and date for something to happen Eg A schedule can be setup every weekday at 12 00pm to send an Email Enabled Tick to enable Type Scheduled Sub Type Set Once Interval Specific Days or Month End...

Page 89: ...ents will ensure alignment with a whole hour Count Only available when Interval Specific Days or Month End are selected as a Sub Type This is how often you want this to occur The recorder will carry on with this schedule for the amount entered in the count Eg If 24 is entered into the count the scheduled event will occur at the specified time for 24 hours A count of zero will carry on indefinately...

Page 90: ...al occurs every 30 seconds Counter 1 will increment by 1 A second Event can then be set up using the User Counter Effect in Event 1 as the Cause for Event 2 In this example the Cause will be triggered by User Counter 1 in Event 1 reaching an count of 50 The Effect of this will be a Mark on Chart In summary every 30 seconds a scheduled interval will cause a counter to increment by 1 When the increm...

Page 91: ...pen in formation such as Table 4 3 Embedded Process Variables Variable Description V Value T Tag Z Zero range S Span range U Unit Text time v Time in HH MM SS format date v Date in DD MM YY format td v Time and Date in HH MM SS and DD MM YY format name v recorder name id v recorder ID serial v serial number Table 4 4 Adding Embedded Process Values Text Entry Function Examples P1 V will embed the c...

Page 92: ... C If Pen 1 name is Furnace1 Tag is Temperature the current value is 14 81 and the Unit text is Deg C Embedded variable are not case sensitive and spaces are allowed name v will embed the current recorder name Furnace1 id v will embed the current recorder ID 21 serial v will embed the recorder serial number 200034 Table 4 4 Adding Embedded Process Values Text Entry Function Examples ...

Page 93: ...to Single Line User or Multiline User Auto will enter what the Event was eg Scheduled or Alarm triggered Single Line User can have up to 69 characters of text or use Embedded Process Values on page 85 Multiline User can have up to 80 characters per line with up to 1000 characters including spaces carriage returns and line feed in total They can also include embedded process variable Recipients Ent...

Page 94: ... the corresponding menu item s so you can then specify the number of the Sub Type to be reset User Counters only available when Sub Type is set to User Select the User Counter number to be used from the available list Counters will only be available if they have first been set up in the User Counters Menu Increment By only available when Increment is selected as the Event Action Enter the number a...

Page 95: ... messages in the message list See Mes sages Menu on page 122 Counters Menu Main Menu Configure Setup Edit Setup Events Counters Counters Up to 16 User Counters are available and can be used as a part of the Events system User Counters can be set up as a Cause or an Effect of an Event Setup a User Counter Select the next available Counter number Enabled In the Counter menu tick to Enable Name Name ...

Page 96: ... for setting up a printer See Printer Menu on page 98 Groups Groups of Pens can be specified and named with a Group name or number See Groups on page 99 When the configuration is complete select the Finish button to Commit Discard or Commit Later Select the Back button to return to the previous menu Ident Main Menu Configure Setup Edit Setup General Ident Unique recorder information Name Enter the...

Page 97: ...data or a 1 hour overlap of data Temp Units Select the Temperature Units that the recorder is set to for temperature measurement Pen scale units may need to be changed accordingly See Pen Scale Line Hz Toggle between 50Hz or 60Hz Mains power frequency Used to optimise analogue input filtering Note The default value is set based on the model number but can be changed here When the configuration is ...

Page 98: ...certain functionality including the total credit value Options This displays how many credits are currently in use Select this to produce a list of Firmware options available and their credit values Toggle each option On or Off to enable the feature within the recorder If there are not enough credits available More credits are available from your supplier For a complete lists of all the firmware o...

Page 99: ... recorder is calibrated in the factory These are pre stored calibration val ues that cannot be changed by the user If the recorder is re calibrated to a User Cal the factory values can be restored at any time User Cal User calibration can be applied at any time To meet the accuracy values spec ified see Input Range Performance Accuracy Table on page 227 calibration source should be accurate to 0 0...

Page 100: ...tton When the calibration is complete the icon changes to the User cal icon under the chan nel to show that the channel is using the user cal Calibration Input Ranges This table shows which input range is used for each input type Table 4 5 Analogue In Calibration Calibration Type Factory User Recalibrate Recalibrate All Factory All Table 4 6 Calibration Input range table Input Type Input Range K T...

Page 101: ...he CJC calibration allows the user to compensate for temperature gradi ent Chrome Copel 50mV L Type TC 50mV M Type TC 50mV P Platinel 100mV D Type TC 50mV PT100 RTD 100mV PT200 RTD 250mV PT500 RTD 500mV PT1000 RTD 1000mV Nickel 100 100mV Nickel 120 100mV CU10 50mV Cu53 50mV 200 Ohms 50mV 500 Ohms 100mV 1000 Ohms 250mV 4000 Ohms 1000mV 0 20mA 250mV 4 20mA 250mV Table 4 6 Calibration Input range tab...

Page 102: ...or Commit Later Demo Traces Configure Setup Edit Setup General Factory Demo Traces A set of demo traces available for demonstration or simulation purposes when no Analogue cards are fitted Options for each demo trace are No Simulation Demo traces are deactivated and no simulation traces are available Simulate if board not fitted Simulation is activated when an Analogue In card is not fitted in one...

Page 103: ... page 117 Toggle the batch menu options On or Off User ID Required Tick to make this a requirement when starting a new batch If Pass words are active on the recorder then the User ID page will be skipped for user entry and will be automatically entered Description Required Tick to make this a requirement when starting a new batch Comment Required Tick to make this a requirement when starting a new...

Page 104: ...er option displays a Print button from various screens using a basic USB standard PCL Printer Command Lan guage printer For details on suitable printer types see Print Support on page 29 Allow Printing Tick to enable On and Off Paper Size Toggles between A4 and Letter Orientation Toggles between Landscape and Portrait Printer Name Enter the printer name as found on the network For a local printer ...

Page 105: ...the Finish button to Commit Discard or Commit Later Select the Back button to return to the previous menu Screen Menu Screen Setup Main Menu Configure Setup Edit Setup Screen Set up the recorder s screen configuration Screen Saver In this menu you can configure the Screen Saver functions See Screen Saver on page 100 Charts In this menu you can set the Fast Medium and Slow chart speeds See Charts o...

Page 106: ... brightness is 80 Adjustable between 10 and 100 of full brightness This works on a square law rule that means if you reduce the saver level by 25 you will double the backlight life If you reduce the saver level by 50 you will quadruple the backlight life Normal backlight MTBF at 100 brightness is SIREC D300 55 000 hours 86 500 at 80 brightness SIREC D400 43 000 hours for the 67 000 at 80 brightnes...

Page 107: ...Screen Brightness Set the recorder s screen brightness using the instant brightness slider Default screen brightness is 80 Adjustable between 10 and 100 of full brightness Set the brightness level tick to agree then go to Finish Commit to permanently apply the change For information on increasing the display life by reducing backlight brightness see Back lights on page 217 Edit Recording Main Menu...

Page 108: ...ual Export Now is in progress during the time when a Scheduled export is to occur the scheduled export will hold off until the manual export is finished Storage Bias Main Menu Configure Setup Edit Edit Recording Storage Bias An adjustable slider can be used to determine how much internal flash memory is allocated for storing chart data and how much internal flash memory is allocated to storing log...

Page 109: ...emory the amount of time to fill the chart memory ie chart history will decrease accord ingly Note that as you allocate more chart memory the recorder gives preference to medium and slower chart speeds The log information displays how many pens are currently set for logging recording The shortest pen means the pen that will take the shortest amount of time to fill it s part of the log memory befor...

Page 110: ...he recorder In each screen you can enable check and change the screen properties The Edit button may display a warning message if the Commit Later option has been select ed This means changes to the configuration have been made but the changes have not been committed to the recorder See Commit Later on page 140 Select a standard or a new screen to view the following menu list Name Select to Change...

Page 111: ...Select the screen to delete and it will be removed immediately When the configuration is complete select the Finish button to Commit Discard or Commit Later Select the Back button to return to the previous menu Settings Main Menu Configure Layout Edit Settings Use this menu to set up the layout settings for the screens C Cycle Screens Tick this to cycle though each of the recorder s screens Cycle ...

Page 112: ...f the Replay chart Replay Alarm This will change the colour of the Replay chart when it goes into an alarm state Time Stamp This will change the colour of the time stamp and date at the top of the screen Marker Colour This will change the colour of any Mark on Chart displayed on the screen The Default button will return all colours to their original factory settings The Colour Picker On the right ...

Page 113: ...gure Layout Load Layouts can be loaded from Compact Flash or USB removable storage media Plug in a re movable storage media device and the corresponding button on the screen will become ac tive Select the relevant media button to display the layout files available to load Select the file and click on the Load button All screens loaded on from another recorder via Compact Flash or USB or Screen Des...

Page 114: ...password system has been configured The first time user is reinstated if the password system is reset For recorders with Extended Security System ESS see First Time Password System Setup on page 142 Administrator This is the top level access to all menus Only the Administrator has access to the password setup The Administrator is responsible for adding users and assigning their levels of access th...

Page 115: ...in the web page before logging out Enter the time in seconds 20 to 3600 seconds Old Passwords Select how many previously used passwords are locked from use as a new password Max 12 previous passwords 0 for disabled Cannot be disabled for ESS recorders Username Max Set the maximum amount of characters that can be used for the User name login 1 to 20 characters 4 to 20 for ESS recorders Password Max...

Page 116: ...ions The Administrator can set up a new user but cannot assign a pass word A dummy password is set and the new user is prompted to change the password when they first Log on The same user name cannot be used User names must not contain numeric characters The Administrator can add more than one user at a time They will not be added until the configuration has been Committed When the configuration i...

Page 117: ... factory default setting Select whether to Continue or Stop the reset procedure Change Passwords Main Menu Configure Passwords Change Passwords The Change Password function can be accessed by all users Select Change Password and enter your user name and old password you will then be prompted to enter your new pass word twice to confirm Settings Main Menu Configure Settings Set Time Set up the Time...

Page 118: ...olour iden tification Ack Alarm All Select this button to acknowledge all active latched alarms By Group Select this button to acknowledge latched alarms in a group of pens Pen groups can be set up in the Pens menu By Pen Select this option to acknowledge latched alarms for individual pens Configure Main Menu Alarms Configure This is a short cut to change alarm levels this will display all availab...

Page 119: ...it Layout on page 104 Edit Toolbar For Custom Screens Not available on the SIREC D200 Select the Edit button whilst displaying a Custom Screen Layout from Screen Designer will take you to your current process screen and displays the Edit toolbar at the top of the screen In Edit mode you can select items on the screen and assign channel pen information to them and move and resize certain items on t...

Page 120: ...gets have green grab handles around the edge Pen and or channel information will appear for each object within the widget Each object in the widget can be assigned to the same or different Pen For example a DPM menu will display the pen currently being used and a set of channel information associated to the text digital and alarm marker objects within the DPM widget Select any of the objects in th...

Page 121: ... Current Value Minimum Maximum Average or Total value Showing For Alarm for Pen List of available Alarms Showing For Input Channel Analogue Digital Hi Pulse or Low Pulse Channel Mapping Objects To select an object activate the Expert button on the Screen menu bar Objects have blue grab handles around the edge Select Map from the Screen bar to display the Setup information as described in Channel M...

Page 122: ...dd Screen in Main Menu Configure Layout Edit Lay out on page 104 Clean Screen Main Menu Screen Clean Screen The Clean Screen function disables the touch screen for 30 seconds so that the screen can be cleaned A dialog box will appear informing you You have 30 seconds to clean the screen Press escape if you wish to close this dialog early The escape key option would only be available if a USB keybo...

Page 123: ...at have previously set up in the Batch Menu on page 97 The default field names are Batch Name Name to Identify the batch User ID Identification of user starting the batch If Passwords are active on the recorder then the User ID page will be skipped for user entry and will be automatically entered Lot No Add a batch Lot No if required Desc Enter a description of what the batch is Comment Add any fu...

Page 124: ...omplete when it has been stopped When a batch is stopped E appears as a mark on chart on the screen If the batch is aborted it is not a complete batch and will be marked on the chart with an A to show it has been aborted If the recorder is not logging starting a batch will automatically start the logging However stopping the batch will not stop the logging If a batch is Paused P will appear as a m...

Page 125: ...d I User ID Displays the user entered ID or User ID entered automatically by the Pass word function D Description User entered description of the batch in progress L Lot No User entered Lot number for the batch in progress C Comment Extra comment field of additional information for the batch in progress Barcodes for Batch Batch markers can be created using independent barcode software The barcodes...

Page 126: ...act flash or USB key we recommend you erase it Format ting of Compact Flash cards and USB keys can be done through your PC The formatting types accepted by the recorder are FAT FAT16 2GB limit TFAT and FAT32 Compact Flash not available for the SIREC D200 Start Stop Recording The Recording screen will allow the user to manually Start and Stop recording Select either the start or stop buttons to act...

Page 127: ...start to over write the oldest data Select the Export Now button to go to a sub menu of available external storage devices Buttons become active when a device is fitted Once fitted the size of the device memory and the amount of available space is displayed Select the desired device to export to and this will display two options New and All The All function will export all the data in the recorder...

Page 128: ... types of messages The messages screen will hold the latest 200 messages Alarms This is a list of active alarms that have occurred The screen will display the Type of alarm the Time and Date that the activity occurred and Message details of the activity System This will list a history of system messages The screen will display the Type of messages and warnings and errors that have been generated b...

Page 129: ...runs along the bottom of all messages screens The button are Back Takes you back to the main Messages screen Jump Select an item in any of the message lists and press the Jump button This will take you to the exact time of the occurrence on the replay screen See Replay on page 158 If the message requested is older that the oldest chart time data available a message box will appear and jump you to ...

Page 130: ...d Alarm Red Green bell in Alarm and acknowledged System Diagnostics Information General eg System check System Diagnostics Warning eg media error FTP failure Timeouts System Diagnostics Error eg Password failure power failure no media Security Security audit trail Security Log In open padlock Security Log Out closed padlock Security Access Failure No entry sign User Mark on Chart and Batch User St...

Page 131: ...Select this to reset all values By Groups If Groups of pens have been set up this can be used to reset the max min values for particular groups of pens To set up Groups see Pens Menu on page 62 By Pen Select this to reset max min values for individual pens View Use the View button to just display the max min values for each Pen Totals Main Menu Process Totals Select a button to Start Stop Reset an...

Page 132: ...ser Counters that have been set up Event Counters Reset All will reset all of the Event Counters Reset Single will allow you to select which Event Counters you wish to reset View will display all the Event Counters that have been set up Digital Input Counters Reset All will reset all of the Digital Input Counters Reset Sin gle will allow you to select which Digital Input Counters you wish to reset...

Page 133: ...ew Each pen is displayed with full configuration details including Pen Value Name Maths Scale In Alarm Pen Rate Alarm Total and Group See Pen Overview on page 130 Maintenance The recorder keeps track of important life actions for improved diag nostics and preventative maintenance notification Health Watch Maintenance is availa ble as a firmware option See Maintenance on page 131 Recording Shows th...

Page 134: ... one will display the current status of the recorder for each category General Main Menu Status System General Displays the version status for the different types of firmware hardware and current recorder information Go Back to return to the previous screen or select Print to print the screen Table 4 8 Example System Version Status Options Version ID 0001 Name D300 Serial No Processor MHz Firmware...

Page 135: ... recorder It cannot be enabled by the firmware credit system contact SIEMENS for details Note 2 not available for the SIREC D200 Go Back to return to the previous screen or select Print to print the screen Table 4 9 Options Credits Enabled Full Math 4 or Scripting Full Maths Note 2 6 or Events 6 or Fast Scan Note 2 5 or Totals 4 or Custom Screens Note 2 4 or Maintenance 2 or Printing 2 or Batch 3 ...

Page 136: ...ing for this pen Name Pen name or number Maths Displays any Maths calculation applied to this pen or the Analogue Input chan nel for this pen Summarised to M for any Maths expressions Scale Displays the High and Low limits of the scale range for this pen In Alarm Displays the current status of the alarm tick active and a cross inactive Pen Rate This displays the fastest of all dependencies Alarm D...

Page 137: ...nth and Time the setup was last modi fied Total On time How much time the recorder has had the power turned on Total Off time How much time the recorder has had the power turned off Longest Off time How long was the longest time period the recorder was powered off Lithium cell life Approximately how much battery time is left Backlight Life Approximately how many hours of Back light time left Compa...

Page 138: ...nt the screen Recording Main Menu Status Recording Shows the current logging status of all pens within the system Pen Displays the Pen number and will display a tick when recording and a cross when recording has stopped Value Displays the current pen value Recording Displays either Continuous or Fuzzy logging Log Rate Displays the Log rate set in Hertz A tick denotes if it is enabled and a star wi...

Page 139: ...gnostics The Diagnostics button will become active when Health Watch Maintenance is selected as a firmware option To enable this go to Options on page 129 Hardware Hardware Status on page 133 Events Events Status on page 136 Comms See Comms Status on page 137 Media See Media Status on page 139 Hardware Status Main Menu Status Diagnostics Hardware Complete diagnostics are shown for each of the foll...

Page 140: ...rent Sample rate for this channel SQRT If ticked the square root extract is enabled on this channel to linearise a non lin ear input Sensor Comp This will display if any type of sensor compensation applied to this channel Pen Displays which Pen scale is being used to display this analogue input CJC Only for Thermocouple inputs Displays the final adjusted value of a Cold Junc tion Calibration on th...

Page 141: ... Displays what activity is on this channel Input Output or Pulse Input Alarm Displays the Pen number and the Alarm number that activates the digital output when the alarm is active The Alarm has to be set to Relay out Status Displays the current state of the digital input on this channel or pulsed if Pulse Out is selected The relay is displayed as open or closed Counters Displays the counter numbe...

Page 142: ...iagnostics Events This status screen displays all the currently enabled Events as they occur Each event displays the event number Event 1 followed by the event information C1 Cause 1 C2 Cause 2 E1 Effect 1 E2 Effect 2 If an Event has not been enabled no event will be listed in the status screen If part of an event is not enabled one will appear next to the incomplete cause or effect If a Cause is ...

Page 143: ...n Menu Status Diagnostics Comms General Description and Status of comms on the recorder Displays Ethernet or RS485 in an Active or inactive state and the recorder s IP address Modbus Status Main Menu Status Diagnostics Comms Modbus Description and Status of ModbusTransport Ethernet or RS485 Transport Ethernet or RS485 Address the IP address of your recorder and if it is fixed or Dynamic Device ID ...

Page 144: ...s Supported for the OPCDAServer OPCDA Max Supp Items Maximum Number of Unique Items Supported for the OPCDAServer OPCDA Groups Requested Number of Groups Requested to OPCDAServer OPCDA Items Requested Number of Items Requested to OPCDAServer OPCAE Rec Con Recommended Connections for OPCDAServer OPCAE Clients Number of OPCAE Clients Connected OPCAE Max Alarms Number of Active Alarms Supported in OP...

Page 145: ...nu Status Diagnostics Media Pen Pen number Rate Pen speed Store Size How much memory is allocated to this pen Store Time How much storage time is available Remaining How much memory is left before data is over written Store Size Store Time and Remaining are dependant of the pen logging speed how many pens are logging and will be affected by Storage bias allocation of chart and logged data Go Back ...

Page 146: ...up or the changes that have been made to the existing setup and not implement them into the recorder Commit Later This gives the user the option for a configuration to be partially completed but to be commit ted at a later date This will retain the new set up or the changes to the existing setup until they are required A partially completed setup will not be maintained over a power failure If Comm...

Page 147: ...current process screen User Log in Log Out Method Users can log in and out of the system or web page easily using the touch screen or an at tached keyboard Users and Groups Number of Users The system will support up to 50 users Multiple Log On s Users are allowed to log on to the system more then once allowing the same user to log on from different areas e g via the user interface and via web brow...

Page 148: ...e screen and select the Log In icon in the top right as shown here 3 A box will appear and prompt you to enter a User name enter Admin This is the first time user login Access to the first time login is removed once the password system has been configured The first time user is reinstated if the password system is reset No password is required for first time login No password is required for first...

Page 149: ...annot be the same Minimum Access Level A feature to allow the minimum level access is available For example when a batch starts the recorder will block access to all users of access level Technician and under so techni cians and operators would not be able to log on after a batch start When a batch ends then the minimum access level can be reverted to including operator Calendar Function Day of we...

Page 150: ... defaults it is possible for the user to change the group names to suit their personnel structure This is stored in the policy set up for the Password configura tion Audit Trail A full audit trail is available and is stored as a message log Trail Rules The audit trail cannot be turned off and will always be generated for the password system Audit Trail Entries Audit trail is generated for the foll...

Page 151: ...atus Perm Area 4 View Totals Perm Area 5 View Alarms Perm Area 6 View Max Min Perm Area 7 View Counters Perm Area 8 Acknowl edge Alarms Perm Area 9 Configure Alarms Perm Area 10 Batch Control Perm Area 11 Recording Perm Area 12 Change Password Perm Area 13 Main Con figue Menu Perm Area 14 Configure Counters Perm Area 15 Configure Totals Perm Area 16 Configure Max Min Perm Area 17 Load Save Setups ...

Page 152: ...ork Admin Perm Area 30 Comms Modbus Perm Area 31 Comms Web FTP Perm Area 32 Comms SNTP Perm Area 33 Comms TCP IP Perm Area 34 Comms Email Perm Area 35 Field IO Perm Area 36 Passwords Perm Area 37 View Status via Web Page Perm Area 39 Full Control via Web Page Perm Area 40 Calibrate Screen Table 5 1 Default Level Permissions Default user levels of access to areas within the recorder menu system Per...

Page 153: ...for Supervisors and above incl Engineer and Administrator levels Technician Access is for Technicians and above incl Supervisor Engineer and Adminis trator levels Operator Access is for Operators and above incl Technicians Supervisors Engineers and Administrator levels No Login gives access only to unrestricted areas Access levels can change for each menu for example Operator or above access is re...

Page 154: ...ee Figure 5 6 for Alarms menu access Screen Menu No Login required See Figure 5 7 for Screen menu access Permission Area 2 Messages Menu No Login required All of the Messages buttons require No Login access Permis sion Area 1 Status Menu No Login required All of the Mes sages buttons require No Login access Permission Area 3 Process Menu No Login required See Figure 5 8 for Process menu access Rec...

Page 155: ...Passwords Operator access Settings Supervisor access Settings menu Supervisor access Permission Area 23 Setup menu Technician access See Figure 5 3 for Setup menu access Permission Area 18 Layout menu Supervisor access All of the Layout menu buttons require Supervisor access Permission Area 24 Edit Layout see Figure 5 7 Password menu Operator access See Figure 5 4 for Password menu access Permissi...

Page 156: ... Area 17 Setup menu Technician access Permission Area 18 Edit Supervisor access Save Technician access Load Technician access Figure 5 4 Default password access from the Password Menu Change Password button requires Operator access Permission Area 12 Password Menu Operator access Permission Area 36 User Admin Administrator Change Password Operator access User Admin Administrator access All of the ...

Page 157: ...isor Access All of the Screen menu buttons require Supervisor access Permission Area 25 General menu Supervisor Access See Figure 5 9 for General menu access Permission Area 20 Events Counters menus Supervisor Access All of the Events and Counters menu buttons require Supervisor access Permission Area 27 Edit Setup Menu Supervisor access Permission Area 19 Field I O Engineering access Pens Supervi...

Page 158: ...s No Login Permission Area 5 Figure 5 7 Default password access from the Screen Menu and Edit layout menu Screen Edit Edit layout Supervisor access All of the Edit functions in the status bar re quire Supervisor access Custom Screens are not available for the SIREC D200 Calibrate and Touch Test Engineering access Used to calibrate the touch screen Premission area 40 Screen menu No Login required P...

Page 159: ...ea 16 View requires No Login Permission Area 6 Counters Menu No Login required Reset button for all Counters re quire Technician access Permission Area 14 View requires No Login Permission Area 7 Figure 5 9 Default password access from the General Menu Factory menu requires Engineering access All of the factory menu buttons require Engineering access Permission Area 28 General Menu Supervisor acce...

Page 160: ...ermission Area 33 Network Admin Permission Area 29 Comms Services Engineering access Permission Area 29 Modbus Permission Area 30 Web Permission Area 31 Email Permission Area 34 SNTP Permission Area 32 FTP Permission Area 31 Peers Permission Area 29 Figure 5 11 Default password access from the Web page Web page Engineering access View Status Permission Area 37 Full Control Permission Area 39 ...

Page 161: ... Date Chart Area Realtime Pen Pointers Pen Digital Read out Alarm Marker marks the chart to show when Pen 1 was out of its alarm state Yellow area shows when Pen 1 was in alarm state Figure 6 1 SIREC D300 Process Screen Standard Screen example Chart and DPM Message Count menu allows quick access to Batch User Mark on Chart and Messages Detail View Alarms Touch the screen to activate a short cut to...

Page 162: ...n Select this button to go to the Recording screen to export the data now or set up a timed export using the Scheduled option See Recording Menu on page 120 If the Time Left button shows two green arrows this means that the memory buffer is full and the oldest data has started to be over written List 78 This button produces another button bar for quick access to Batch Controls Mark on Chart or Mes...

Page 163: ...isplay specific screens for an allocated amount of time before switching to the next For Custom Screens this will enable the Edit tool bar go to the Edit Toolbar on page 113 This is for Pen Channel mapping and Expert mode for moving and resizing items on the screen Replay Gives quick access to the Replay Screen See Replay on page 158 List List of all available screens select to change the current ...

Page 164: ...sitioned on the screen Note You can do replay on Bar Charts and Digital Panel Meter process screens and this will jump into a trend replay screen with the DPM s showing the Min Max values When using Custom Screens you can only replay 8 Pens on the SIREC D300 and 12 on the SIREC D400 recorder even though you can have more pens than this on the custom screen Custom Screens are not available on the S...

Page 165: ...est chart time and date available About Replay The replay screen facility enables the user to Show greater coverage of elapsed time display more history Zoom in and out further Display data on a chart and DPM screen Display Max Min readings on DPMs Display pens on a chart replay screen that are currently displayed on a DPM screen Add any enabled pen on to a process screen All enabled pens have his...

Page 166: ...ve you much more elapsed time history but at a lower time resolution here is a representation of what this could look like The lines represent absolute time coverage So if you go right back to the earliest time on the slowest chart shown by in this example you cannot zoom in any more as the medium speed coverage does not go back that far Zooming Capabilities The example in Figure 6 4 on page 161 s...

Page 167: ...r div replay chart 4 hour div replay chart 2 hour div replay chart 1 hour div replay chart Fast chart speed 600mm hr Medium chart speed 20mm hr 10 mins div replay chart 5 mins div replay chart 2 mins div replay chart 1 min div replay chart Zoom In Zoom Out 1 hour div replay chart bigger divisions Slow chart speed 5mm hr ...

Page 168: ... chart This will produce the Settings button in the top right of the screen select this to display the current chart speeds setting for Fast Medium and Slow The cur rent selection will be highlighted To change the actual chart speed setting for Fast Medium and Slow see Charts on page 100 QuickView Changing chart speeds can be used as quick view of the data at different resolutions Screen Activity ...

Page 169: ...arm state Pen pointers will change direction and point up or down when a pen signal goes off scale Mark on Chart There are two different types of Mark on Chart automated or user An automated Mark on Chart can be set up for An Alarm going in and out of an alarm state Start Stop or Reset Totals Batch control such as Start Stop Pause Resume and Abort batch Generated by an effect of an Event A user Ma...

Page 170: ...creen during normal data activity and where they would appear The markers change depending on if the signal goes High or Low outside the Pen Scale or outside the Input Range Note It is recommended to display DPMs on a chart to identify over range and under range activity Pen into alarm User Pen out of alarm Totals started Batch stopped Figure 6 5 Mark on Chart ...

Page 171: ...eated in Screen Designer can also be loaded into the recorder added to a recorder screen or screens and displayed Refer to the Screen Designer manual for further details Table 6 2 Screen Markers DPM Bar Pointer horizontal chart Chart Upscale Burnout Outside Range High Trace at Max Input Range Top Trace at Max Pen Scale Top Displays as normal 1234 567 Bar Trace Pen Scale Bottom Trace at Min Input R...

Page 172: ...ton Go to Main Menu Configure Layout Edit and select Add Screen Go to the Template Type option and your template will be listed here Select your template and it will be added to a screen re name the screen as required To display the new Layout go to the Screen button in the Main menu bar at the top of any process screen and select the next button to scroll through the screens Loading a Layout into...

Page 173: ...n be associated with a totaliser Using extra pens the totalised values can be dis played and recorded multiple totals can be calculated out of the same variable weekly monthly etc The totaliser function can handle Fo and Po sterilisation calculation Custom Screens Note 2 4 Import custom built screens that have been created in Screen Designer Health Watch Maintenance 2 The recorder keeps track of i...

Page 174: ...ix B Maths Expressions on page 233 Applying your Firmware credits To activate the Firmware options follow this file path Main Menu Configue Setup Edit General Factory Credits The Credit menu contains the Serial No of the recorder how may credits are available dis plays the Options Code and lists what firmware Options are currently active Serial No read only and cannot be edited Credits read only a...

Page 175: ...the recorder s web page type in the recorder s IP address in to a web browser such as Internet Explorer If Microsoft WINS system Windows Internet Name Service is available then the recorder name can be used to search for the recorder web page Any problems with connection see IP Address Troubleshooting on page 199 To find your recorder IP address see TCP IP on page 71 Select Remote Viewer to enable...

Page 176: ...170 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 Firmware Credit System ...

Page 177: ...rt here is some information about the comms interfaces that are used in the setup of the SIREC D Server software and Communications Server Rear Ethernet Communication port The rear of the device is fitted with an Ethernet 10 100 port which supports Modbus TCP IP See Modbus on page 172 OPC Server connectivity to third party software OPC Server connection must be enabled by selecting the OPC option ...

Page 178: ... via Ethernet or RS485 ports The device ID and Serial number is held in the setup and this information is required to locate the correct device in SIREC D Server Modbus only requires the correct Slave ID to connect see Modbus on page 75 If the device is detected using the Slave ID the Recorder ID and Serial Number will be transferred if the device is not detected an extra device will appear in the...

Page 179: ...s at one port it is copied to the other ports so that all segments of the LAN can see all packets Switches work in a similar way but send the data directly from one port to another On a busy net work this can be quicker and can have less data collision incidents Connect an Ethernet cable from the Ethernet port on the back of the device to the Ethernet hub Connect another Ethernet cable from the Et...

Page 180: ...m the device Contact your IT systems administrator for setting up this link The TCP IP properties are displayed showing the PC s IP address and the Subnet mask Make a note of the IP Address and the Subnet mask If there is no IP address or Subnet mask displayed contact your IT systems administrator When this information is entered the next stage is to configure the device See TCP IP on page 71 Swit...

Page 181: ...ers remote servers SIREC D Server 1 can access Comms Server 2 and Database Server 2 and all the de vices within the databases on those servers Similarly SIREC D Server 2 can access the devices and databases held on Database 1 and Comms Server 1 Data Logging and Transfer Using the SIREC D Server software the device s details are added on to a database in SIREC D Server Once the device has been conf...

Page 182: ...t from a device straight to the server using Ethernet or RS485 links This actual current data can then be logged to a database and viewed on a graph in real time this is known as Realtime data Different types of data realtime logged and historic data can be displayed next to each other on a split graph screen The comms server is used to configure logging and manage databases and reflect each devic...

Page 183: ...junction with the Communications Server Realtime data can be retrieved from the de vice to a PC via an Ethernet and or RS485 connection This data can be viewed graphed and logged into the system Data from the device can be logged to a database and held on a database server Remote servers can be added to the comms server to allow access to remote devices on remote databases not on a local network S...

Page 184: ... to install This will be dependant on which version has been purchased SIREC Viewer SIREC Manager or SIREC Server Select to install Enter the code and organisation as supplied with each particular version of software The code can be found inside the CD case No code or organisation is required with SIREC Viewer NB This is an alpha numeric code and must be entered exactly in upper case Codes from ot...

Page 185: ...t or from the pro grams menu It is advisable to ensure that each recorder has a unique Recorder ID number this will make identifying individual recorders in SIREC Server much easier This is set in the recorder Ident menu see recorder user manual The first thing to do is to get the recorders setup into SIREC Server This may be achieved by saving the setup at the recorder to Compact Flash or USB mem...

Page 186: ... their Net work ID eg xs nnnnnn where nnnnnn is the recorder s serial number Give a name for the recorder This should be something recognisable all recorders should be given different names Press OK On pressing OK then Done you will return to the External Import dialog box as above Check that Setup only and from Network are still selected Then drop down the list and select the recorder you have ju...

Page 187: ... software If you select the Recorder button on SIREC Server this will show a list of all recorders currently logged with a setup The recorder just added will be the last one on the list This name will be used to set up the Modbus Profile in Comms Server for the recorder ...

Page 188: ...thernet and Serial ports Enable and disable ports Add edit and remove devices Log to database or client connections local or OPC client The comms server will appear as an icon in the system task bar in the bottom right of the PC screen Start up The Communications Server appears as an icon in the Windows system bar at the bottom right of the screen Double click or right click to open loads automati...

Page 189: ...to be enabled The Clear Setup Cache button will remove all setup files Network Settings is for PC s with more than one network card fitted to access devices on other networks The network cards are displayed here for selection If the Use NIC Default IP Address Selection is ticked then the first network card that was added to the list will always be selected Preferences The Timing Setups tab display...

Page 190: ...rview on page 182 shows the comms status screen in the left window from the top is displayed Database Serv er Local and remote database and devices held on the Local database All Logging config uration for comms logging and logging to a database is set up from the Comms Server Connected databases are displayed with a green icon If the database is in red it is not con nected check the IP Address an...

Page 191: ... top left of the comms server window 2 Right click on Database Servers in the top left window Connect to a Database Server 1 Select Database Servers in the left window and then right click on the server to be connected in the servers list in the main window 2 Connect to database server dialog box will appear enter an IP address and a descrip tion to identify the database server Delete a Database S...

Page 192: ...nge to a tick Now the recorder must be added To do this click the add new device button The first in the row of three This will bring up the Device Details box All these methods will produce the Add Device Details box Areas of the box become greyed out as the selections are made Protocol The protocol should be matched to that set on the recorder It will be Modbus X by default so leave it at that u...

Page 193: ...orderswill automatically register a unique Network ID using the serial number The format is xs nnnnnn where nnnnnn is the serial number of the recorder This allows you to browse the recorder if you are using DHCP Dynamic Host Configuration Protocol Slave ID This is a unique Modbus ID Address used by the recorder to identify Modbus messages Applications that talk to the recorder with Modbus will ne...

Page 194: ...tion button to insert the recorder details into the Add Device box When you get back to the Add De vice Detail Box press OK The recorder you have set up will now be added to the device list Add a Device via RS485 Setting up the Comms Server for Modbus on RS 485 follows the same procedure but the PCs comm port that the 485 interface is connected to is selected in the Communications Port drop down l...

Page 195: ...ged Any device can be made active or inactive from here For active Modbus devices the recorder name and protocol variant can be changed modbus vs Modbus X For an inactive Modbus device the device profile can also be changed For information on the Test button see above Click on the OK button to save the changes Delete a Device Select the Comms port containing the device to be deleted and right clic...

Page 196: ... the IP address of the device that will be the database server Click the new database server button Enter the IP address and a new database server will be added Add databases to this server as above Logging Configuration This screen configures channels for logging from a device to a database It can be accessed in several ways 1 Use the Configure Database Logging icon at the top left of the screen ...

Page 197: ...channels are added the next box will ask how often you want these channels to be logged log rate this can be a sample every second to one sample every 24 hours This selection will apply to all channels If channels are added one at a time using the Add Channel Selection button the same log rate box comes up but a different log rate can be set for each channel When all the required channels have bee...

Page 198: ...ll stop for this channel The set up is complete and the logging to the database should start immediately To check the setup go back to the Comms Server screen Send Recorder Events Comms Server has a set of chart controls that can control the chart on the recorder from your PC This can be done in Realtime chart controls on page 192 or can be setup as an Effect of an Event Realtime chart controls Ri...

Page 199: ... logging for that recorder and their log rate Comms Server can be minimised now it will continue to run in the background Client Connections Realtime comms data from the device will only display on the comms server communica tions status screen when realtime data is active on either the server software or by using an OPC client Once data is active on a client connection this window will display de...

Page 200: ...tabase All Logging config uration for comms logging and logging to a database is set up from the Comms Server Connected databases are displayed with a green icon If the database is in red it is not con nected check the IP Address and Device ID are correct and a protocol has been selected on the device Un tick and then tick the active box on the comms server to restart the data base connection This...

Page 201: ... top left of the comms server window 2 Right click on Database Servers in the top left window Connect to a Database Server 1 Select Database Servers in the left window and then right click on the server to be connected in the servers list in the main window 2 Connect to database server dialog box will appear enter an IP address and a descrip tion to identify the database server Delete a Database S...

Page 202: ...he re quired ones onto the graph As soon as the pens are on the graph they should start to update in real time The graph will be split into two as below The white area for historical data will display the data that is stored to the database At this point we have no data being stored to the database it is simply being acquired and graphed if the graph is closed any data downloaded via Modbus will b...

Page 203: ... The Comms Server is a Modbus master It has no slave capability 2 The maximum speed of data transfer over Modbus is 1 one reading per second per channel 3 The maximum speed of data logging of realtime Modbus data is 1 one reading per second per channel 4 The maximum number of devices depends on whether the connection is serial or ether net On the serial port there is a physical limit of 31 devices...

Page 204: ...from different manufacturers in one system OPC gives you the freedom to add new hardware from third party vendors to existing set ups or to replace a device without worrying about compatibility with your chosen software The measurement and control hardware such as a recorder provides front line data acqui sition As soon as the hardware device has collected the data it makes it available to soft wa...

Page 205: ... can be password protected if passwords are enabled See Web on page 75 To access the web page type the device s IP address in to a web browser such as Internet Explorer If Microsoft WINS system Windows Internet Name Service is available then the device name can be used to search for the device web page The recorder will automatically register a unique Network ID using the serial number The format ...

Page 206: ...cal intranet option Firewall settings If this device is sitting on an enterprise network with a firewall in place then the firewall should be configured to allow all requests on port 80 and port 976 for remote control Ac tiveX There is also one port for FTP control and one for OPC which should be opened Access to the firewall settings will differ depending on what firewall is installed Figure 8 10...

Page 207: ...erver but in cludes the added function of an integrated OPC Server to allow easy interfacing to third party HMI soft ware packages that support an OPC Client This provides a real time interface between servers and clients Modbus Profile Configuration Tool this is a tool that comes as part of the TrendServer Pro software that allows the user to set up Modbus Device Profiles for use by the Communica...

Page 208: ... SIREC Manager and SIREC D Screen Designer Minimum System requirements for SIREC Server 1GHz Pentium processor or higher 1GHz Pentium processor or higher CD ROM drive CD ROM drive Monitor screen resolution 1024 x 768 recommended minimum high colour Monitor screen resolution 1024 x 768 recommended minimum high colour Windows 2000 XP Windows 2000 XP 512 Mbyte of RAM 512 Mbyte of RAM 16 bit colour gr...

Page 209: ...43 TV 25 35 GLO Iss 4 Dec 06 UK 203 A5E01001767 04 Section 10 Spares List SIREC D300 Recorder 16 5 3 1 4 2 24 10 49 9 45 19 ...

Page 210: ...A5E01001767 04 52 20 to 55VDC 20 to 30VAC Input Instrument power 24X TX Power Supply Analogue Input or Pulse Input Alarm Digital IO CJC Sensor Analogue Input Analogue Output 7 19 Common Relay Output 27 23 RS485 RS485 USB host Ethernet 54 ...

Page 211: ...453015 502 51453015 503 D300 Power Supply AC Mains D300 Power Supply AC TX D300 Power Supply 20V 55VDC 20 30VAC 50013945 505 50013945 506 D300 Bezel Touch Screen and Std Nema 3 IP54 Door Assy D300 Bezel Touch Screen and Nema 4X IP66 Door Assy Includes Bezel Touch Screen and Door Assy 9 50003508 501 D300 Nema 4X IP66 Door 10 50009118 501 D300 Std Nema 3 IP54 Door 16 50006685 506 50006685 506 D300 B...

Page 212: ...ight Hand Chassis kit 48 30755050 502 D300 Mounting Hardware kit 2 Mount ing Brackets Not shown 49 51453083 501 D300 Panel Gasket 52 51453038 501 Stylus Kit Black pack of 5 53 50013947 501 Connector kit 2 of each connector type Not shown 54 50017179 501 D300 5 5 Backlight kit of 2 Not shown 50017290 501 Touch Screen Protector kit of 5 Not shown 50017181 501 D300 D400 Blanking Plate for I O Slots 2...

Page 213: ...43 TV 25 35 GLO Iss 4 Dec 06 UK 207 A5E01001767 04 SIREC D400 Recorder 14 15 32 46 50 30 31 35 36 28 55 ...

Page 214: ...208 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 52 11 23 33 39 5 6 RS485 USB host Ethernet 1 2 3 4 ...

Page 215: ...Dec 06 UK 209 A5E01001767 04 24V TX Power Supply Output RS 485 Alarm Digital IO Analogue Input or Pulse Input CJC Sensor Analogue Input or Analogue Output 20 to 55V DC 20 to 30VAC Input Instrument supply Common Relay Output ...

Page 216: ...wer Supply AC Mains D400 Power Supply 20 55VDC 20 30VAC 6 51453030 501 D400 Transmitter Power Supply board 11 50013946 505 50013946 506 D400 Bezel Touch Screen Std and Nema 3 IP54 Door D400 Bezel Touch Screen and Nema 4X IP66 Door Assy Includes Bezel Touch Screen and Door 14 50009119 501 D400 Std Nema 3 IP54 Door 15 50003590 501 D400 Nema 4X IP66 Door 23 50001782 501 D300 D400 Speaker Assy 27 5000...

Page 217: ...nel Gasket 51 50004292 501 D400 Panel Clamp Assy Qty 2 Not shown 52 51453038 501 Stylus Kit Black pack of 5 53 50013947 501 Connector kit 2 of each connector type Not shown 55 50017180 501 D400 12 1 Backlight Not shown 50017290 502 D400 Screen Protector Kit of 5 Not shown 51452129 501 10 Ohm Resistors Pack of 8 Not shown 50017181 501 D300 D400 Blanking Plate for I O Slots 2 Not shown 50001249 501 ...

Page 218: ...212 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 SIREC D200 Recorder 16 5 3 1 4 2 24 49 9 45 19 6 49 ...

Page 219: ... host Ethernet RS485 Wire seal AC supply 100 250VAC 24V TX Power Supply Output RS485 port and USB Host option Up to 6 Analogue Inputs and Ethernet std Earth screw ground 20 to 30VDC 20 to 25VAC Input Instrument power Analogue Input card Slot B op tion Alarm or Digital I O Slot G option ...

Page 220: ... 6 50012930 501 D200 Communications card plus 24V DC Transmitter Power Supply RS485 Modbus RTU and USB port 7 50016251 502 D200 Bezel Touch Screen and Nema 4X IP66 Door Assy Includes Bezel Touch Screen and Door Assy 9 50015106 502 D200 Nema 4X IP66 Door 16 50015135 502 D200 Bezel Touch Screen Display As sembly NEMA 4X IP66 Includes Bezel Touch Screen Assy Door Display Speaker In verter Cables and ...

Page 221: ...us Kit Black pack of 5 53 50021404 501 Connector kit 2 of each connector type Not shown 50017290 503 Touch Screen Protector kit of 5 Not shown 50017181 501 D200 D300 D400 Blanking Plates Not shown 51452129 501 10 Ohm Resistors Pack of 8 Not shown 50001251 501 D200 Portable Case Not shown 51453051 501 D200 D300 and D400 Power cord 125V Not shown Table 10 3 SIREC D200 Spares Height 165 1 6 50 Width ...

Page 222: ...216 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...

Page 223: ... their original brightness i e a display has a greater than 50 chance of being half its original brightness when used at 100 after 55 000 hrs for the SIREC D300 Maximum luminosity 400 cd m2 86 000hr if used at 80 43 000 hrs for the SIREC D400 Maximum luminosity 400 cd m2 67 000hr if used at 80 40 000 hrs for the SIREC D200 Maximum luminosity 450 cd m2 62 500hr if used at 80 For this recorder the b...

Page 224: ...r screen selection Clean the screen using a suitable touch screen cleaner Abrasive materials will damage the touch screen Protective Screen covers are available to provide additional protection against abrasive ma terials See Section 10 Spares List on page 203 Calibration It is recommended that Recorder calibration is checked at least every year or in accord ance with your industry regulations to ...

Page 225: ...s Resolution 0 002 or better Accuracy 0 1 0 500ohm load 0 25 500ohm 1Kohm load Maximum load resistance 1Kohm Isolation 300V AC Outputting 0 to 20mA or 4 to 20mA over range capability to 21mA Update rate 250mSec per channel Pulse Input Card The Pulse Card is available as an option and will fit in slots normally allocated to AI cards The frequency output from the card can be used in a Maths block an...

Page 226: ...ons All Digital Inputs are volt free contacts and are sampled at 10Hz max Relay Alarm Output Card Options There are two card options split into two types 4 Channel Relay Alarm Card 120 240 VAC 3 Amps rated resistive load The relay contacts are form C NO NC and includes suppression 8 Channel Relay Alarm Card 120 240V AC 3 Amps rated resistive load Two channels on the 8 Relay Alarm card can be used ...

Page 227: ...n normally open relays have closed contacts when the recorder is powered on and there are no open active alarms and the contacts open with an alarm active or when the power is removed See Failsafe Relay Positions on page 222 Relay Output Specification The SIREC D300 recorder will provide the ability to have at least 1 relay output for each an alogue input i e 16 SIREC D400 recorder will also provi...

Page 228: ...sistive load Digital Input Functions The digital inputs can be used for the following actions A Digital contact on an input can be used to enable or disable one or any combination of alarms Can be used in Maths expressions Can have current status indicated on DPMs Bars and Charts Failsafe Relay Positions Table 12 2 D200 D300 and D400 Relay Positions no alarms active Normal Relay Output States NO N...

Page 229: ...0hr if used at 80 Maximum luminosity 450 cd m2 Touch Screen life 1 000 000 touches Display Update Rate Display values updated every second Status Display A status bar at the top of the recorder s screen displays the real time icons of the recorder status such as Time left and alarm active Communications Ethernet 10 100 base T with RJ45 connector supporting Modbus TCP FTP Internet DHCP or fixed IP ...

Page 230: ...contacts normally open when the recorder is powered no active alarms Rating 24V 1 Amp Not available for the D200 Battery Battery backed up for clock replaceable Lithium battery Type 6032 3 0V 10 years life Recorder powered 4 years life typical Recorder unpowered Password Protection Multiple Administrator control of password setup and management with four levels of password protection for Engineer ...

Page 231: ...st be enclosed within the panel Specification Design Attributes Specification Analogue Inputs Number of Inputs D300 recorder can have 4 6 8 12 or 16 input channels D400 recorder can have 4 6 8 12 16 24 32 40 or 48 input channels D200 recorder can have 3 6 9 or 12 input channels Input Types mV V mA with external shunt provided as standard Thermocouple RTD and ohms Minimum Input Span Range is fully ...

Page 232: ...Bezel Zinc plated steel case with high impact resistant polycarbonate bezel scratch resistant lens Pol yethylene Terephthalate NEMA 3 IP54 protection rating standard with NEMA 4X IP66 Front face only protection rating as an option Mounting Panel Unlimited mounting angle For the best view of the display the viewing angle should not exceed D300 55 from the left or right 40 looking down and 50 lookin...

Page 233: ...28 to 94 94 to 1832 270 to 200 200 to 70 70 to 1000 21 6 3 1 1 3 12 1 7 0 7 0 01 C J 346 to 32 32 to 2192 210 to 0 0 to 1200 3 1 1 2 1 7 0 7 0 01 C K 454 to 94 94 to 2502 270 to 70 70 to 1372 36 1 8 20 1 0 01 C R 58 to 500 500 to 1202 1202 to 3214 50 to 260 260 to 650 650 to 1768 9 3 6 2 7 5 0 2 0 1 5 0 01 C S 58 to 500 500 to 1832 1832 to 3110 50 to 260 260 to 1000 1000 to 1768 5 3 3 2 2 7 3 5 1 ...

Page 234: ... O or 16 I O SPNO 1A 24VDC non inductive internally suppressed 16 I O not available for the D200 Activation Fully programmable internal alarm levels Assignable to any relay or discrete output Digital Input Output optional 8 I O or 16 I O all channels may be selected freely as either digital inputs or outputs The Digital I O card also has 4 channels that can be set as pulse inputs channels 1 to 4 T...

Page 235: ...onal FM not available for the D200 Extended Security System ESS optional Provides full support for 21 CFR Part 11 Includes features for entry of unique User ID s and associated passwords timeout on inactivity 1 to 10 min password expiration 1 to 365 days up to 50 users pass word re entry lock out for incorrect entry of password more than 3 times no re use of passwords pro grammable 4 to 12 times t...

Page 236: ...5 40 65 65 40 65 65 Any Any Any Power Requirements Mains Voltage Vrms Low Voltage AC Vrms DC Voltages Frequency Hz 220 to 240 24 2 24 2 49 8 to 50 2 100 to 250 20 to 30 D300 D400 20 to 25 D200 20 to 55 D300 D400 20 to 30 D200 47 to 63 90 to 264 20 to 30 D300 D400 20 to 25 D200 20 to 55 D300 D400 20 to 30 D200 47 to 63 N A N A N A N A Power Consumption D300 D200 AC 40W max DC 40W max Typical 20W D4...

Page 237: ...tic Capability Directive 89 336 EEC as amended by 92 31 EEC and 93 68 EEC Safety The product range of instruments is compliant with the requirements of BS EN 61010 1 2001 Safety Requirements for Electrical Equipment for Measurement Control and labo ratory Use and UL 61010C 1 and CSA 22 2 1010 1 If the equipment is used in a manner not specified the protection provided by the equipment may be impai...

Page 238: ...232 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...

Page 239: ...f these features Important Note Full Maths and Script functions are Options and must be enable using the Credit System Be sure to enable these options or they will not be available See Firm ware Credit System on page 167 Notes if elseif else are followed by expressions in curly brackets lines within the curly brackets always end in semicolon e g every execution path must have a return statement As...

Page 240: ...rns the percentage of free storage space available on the Compact Flash card CJC CJCn Get the Board CJC value N 1 to 6 Returns value in Degrees F C or K depending on the localisation setting CJC in Degrees C CJCnC Get the Board CJC value N 1 to 6 Always returns value in degrees C Comms Variables CVn Get the Comms variable n 1 to 96 Digitals Dn Get the value of Digital Input n 1 to 48 Digital Input...

Page 241: ...l Input card when in Pulse mode n 1 to 48 1kHz Max RT Compensation RTCOMPn Get RT Compensation value for channel n 1 to 48 Units mV RT Calibration RTCALn Get RT Calibration value for channel n 1 to 48 Units mA Totaliser Tn Get Totaliser value n 1 to 96 UC1 to UC16 UC1 User counters 1 to 16 USB1 free storage space USB1FREE Returns the percentage of free storage space available on the USB storage ke...

Page 242: ...ero Exponent exp x Returns the Exponential of x Floating point Absolute fabs x Returns the Floating Point Absolute value of x Floor floor x Round down x to the nearest whole number Ln ln x Returns the Natural Log of x Log log x Returns the Base 10 Log of x Modulus x y Returns the value of x with a modulus of y Multiply Returns the result of the multiplication Power pow x y Returns the value of x r...

Page 243: ...ature in C to one in F F2c f2c x Converts a temperature in F to one in C Hi hi x y Returns the larger value of x y Hi4 hi4 x y x1 y1 Returns the larger value of x y x1 y1 Inside inside x y z Returns x if between y z otherwise returns 0 Lo lo x y Returns the lower value of x y Lo4 lo4 x y x1 y1 Returns the lower value of x y x1 y1 Outside outside x y z Returns x if outside of y z otherwise returns ...

Page 244: ...value of Pen number x Tot TOT x Get the current value of totaliser x Table 14 6 Boolean Operators Syntax Description AND Returns a true or false result from testing if two tests are both true e g IF A1 GLBV1 A2 GLBV2 Assign Assigns one variable to another e g GLBV1 A1 GLBV1 becomes the value of A1 Equal to Returns a true or false result from testing if two variables are equal to each other e g IF ...

Page 245: ... if two variables are not equal to each other e g IF A1 GLBV1 OR Returns a true or false result from testing if one or other or both tests are true e g IF A1 GLBV1 A2 GLBV2 XOR Returns a true or false result from testing if one or other but not both tests are true e g IF A1 GLBV1 A2 GLBV2 Table 14 6 Boolean Operators Syntax Description ...

Page 246: ...nal test and if true steps into brackets to run Must always finish with a return elseif x 4 return y First run FIRSTRUN Returns true if the script is being run for the first time otherwise returns false If if x Carries out a conditional test and if true steps into brackets to run If false steps to next test without operating the contents of the brackets Next step will be either elseif or else Must...

Page 247: ...ble 14 8 Full Maths examples Full Maths examples P4 lo A1 A2 Pen 4 shows the result of the lowest of either A1 or A2 P3 A1 A2 SQRT A3 Pen 3 shows the result of Analogue input 1 added to Analogue input 2 all multiplied by the square root of Analogue input 3 P4 GLBV1 P4 shows the Global Variable 1 NOTICE Please note Pn is not entered in the Maths Block and is assumed by the Recorder e g To enter the...

Page 248: ...1 equal to channel 2 and display and record input 2 If input 3 is bigger than all the others then make the global variable 1 equal to channel 3 and display and record input 3 If none of the above are correct then Input 4 must be the highest so make the global variable 1 equal to channel 4 and display and record input 4 Display the global variable 1 on another pen to show which channel is biggest a...

Page 249: ...and a change counter that totals the number of times that flow 3 exceeds that of flow 2 The pseudo code is written as If flow meter 3 has a larger reading than flow meter 2 check to ensure that it was already greater than meter 2 if it was return the latest change count value If it was not greater than meter 3 last time set a flag to indicate a change and increment the change counter by 1 then ret...

Page 250: ...splay the timer If input 1 is not the highest input value then stop totalising time and return the current timer value We know that in Example 1 the highest value channel number is contained with GLBV1 and as this is a global variable it is also accessible from this script if A3 A2 Tests if A3 is bigger than A2 if BLKV1 1 If it was then tests if A3 was bigger than A2 last time period return BLKV2 ...

Page 251: ...nt timer value else If not then BLKV1 tpause 1 Pause the timer return tget 1 Return the current paused timer value if D1 1 Tests if the DI 1 is not set If it isn t then if GLBV1 1 Tests if the global variable 1 is equal to channel 1 BLKV1 trun 1 0 If it is then keep the timer running without resetting return tget 1 Return the current timer value else If not then BLKV1 tpause 1 return tget 1 Pause ...

Page 252: ...or single line or if A1 10 if A1 is greater then 10 then return 9 return 9 these are also useful for commenting out code to try different things for example if A1 10 return 9 else return 20 return A1 Here the else statement is commented out so it won t be included but can easily be re in troduced if required Maths Error Messages When the Maths functionality is processing through the scrips you hav...

Page 253: ...age corresponding to 80 C the difference between the hot and cold junctions For the recorder to correctly report the 100 C it needs to know the temperature at the cold junction There are 4 options of cold junction compensation CJC on the recorder that are detailed below The simplest and most common is to use the Internal Automatic compen sation This uses a CJC sensor built onto the AI board to mea...

Page 254: ... The reading from this sensor is read off against a value taken from the thermocouple table which corresponds to the type of thermocouple being used The corresponding reading in volts for the temperature measured by the sensor is then used as a reference for the reading from the thermocouple Diagram shows passive burnout for active burnout replace the for Temperature reading to maths expression Re...

Page 255: ...temperature can be specified in the setup menus This reference temperature is then used in the same way as the reading from the temperature sensor using the Internal Reference method Diagram shows passive burnout for active burnout replace the for Temperature reading to maths expression V Volts Reference junction held at 0 C 0 Volts 0 C Measuring junction Thermocouple cable Copper wire Input termi...

Page 256: ...nput usually RT This input is processed in the normal way and then passed back into the thermocouple signal processing system as a temperature reading Reading in Volts Temperature reading to maths expression A C _ Input terminals on rear panel of recorder Copper wire Normal signal processing Thermocouple Table convert R T temp to Volts Volts D V _ PT100 Copper wire Thermocouple cable Inputs added ...

Page 257: ...or flash colour iden tification Ack Alarm All Select this button to acknowledge all active alarms latched and normal alarms By Group Select this button to acknowledge any alarms in a group of pens Pen groups can be set up in the Pens menu By Pen Select this option to acknowledge any alarms for individual pens Configure This will display all available Pens with alarms set up To change the configura...

Page 258: ...252 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...

Page 259: ...em addresses such as the 32 bit addresses used in the current version of IP The high level IP based networking software in a device is aware of its own 32 bit IP address and can read the 48 bit Ethernet address of its own network in terface but it doesn t know the Ethernet addresses of the other devices on the network To discover the Ethernet addresses of other IP based devices on the network anot...

Page 260: ...dress Any e mail message will consist of a delivery list recipients a subject and an optional message body The message body may be omitted for very short messages or where the message is to be sent to a paging system The e mail subject may be either one of the existing event markers or one of the two e mail subjects The e mail message body may be either one of the existing event markers or one of ...

Page 261: ...e other 8 points are redundant Fuzzy logging works by creating straight lines in the data and discarding redundant points What s it for To help the user in the trade off between Scan Rate Disk capacity and Recording Time after all the Pie is only so big Fuzzy Logging has been developed to help maximise all three sections in effect increas ing the size of the Pie The result is a technique that deli...

Page 262: ...miss them NO you will not miss any Spikes Glitches or Transients these are what you need to see As Fuzzy Logging is an adaptive technique it will log as fast as it needs to in order to capture everything Although not all points are logged the base Scan Rate of the input is the same as if you were using a standard logging technique 7 6 5 4 3 2 1 7 6 5 4 3 2 1 7 6 5 4 3 2 1 Time Input Signal Continu...

Page 263: ...f long periods of little activity relatively constant flow rate and short periods of high activity rapidly changing flow rate it is ideally suited to Fuzzy Logging During the hours of stable flow where the flow rate remained more or less constant the Fuzzy Logging technique would give compression ratios up to 100 times However as soon as a glitch appeared the fast sampling rate was able to capture...

Page 264: ...easured process is new or the ideal scan rate is unknown Fuzzy Logging is ideal as it adapts the log rate to the input signal and can therefore find the opti mum logging rate for you Tolerance band widths Tolerance band width can be set as a percentage of the scale range allowed above and be low the input signal A second band width can be set this is where a tighter tolerance can be specified whic...

Page 265: ...he F0 value would be 15 representing 15 minutes at 121 11 ºC In practice of course to reach this temperature the object would have to be subject to an initial heating period up to that temperature and later a cooling period back down again to ambient temperature more like the profile shown in Figure 2 on page 259 During all this heating up holding at temperature and subsequent cooling micro organi...

Page 266: ...alues are summa rised in this table For setting up the Fo calculation refer to the Totaliser Menu on page 68 Term Definition Default values Allowed Range F0 The equivalent time in minutes at 121 11ºC that would pro duce the same degree of sterilisation This is the totaliser out put value z factor The temperature increase in ºC above the reference tempera ture that will produce a 10 fold increase i...

Page 267: ...er the Offset adjustment required and this is added or subtract ed for all future readings Dual Point Select Dual Point to change two points on the signal input reading The Dual Point adjust ment works in the same way but at two different points on the signal input The two points must be more than 50 of the engineering units away from each other Low Eng and High Eng are the two points where the ad...

Page 268: ...igh Eng value 10V 10V 10V 10V Single Point Sensor Compensation is used to offset the signal input by a user specified amount over the full range Dual Point Sensor Compensation is used to offset the signal input by a user specified amount against the Low and High Eng val ues The offset amount can vary throughout the signal input range Solid line shows without compensation and dotted line shows with...

Page 269: ...e inserted into equipment correctly with regard to polarity and Do not attempt to revive used batteries by heating charging or other means Do not dispose of batteries in fire Do not dismantle batteries Do not short circuit batteries Batteries should be disposed of in accordance with local regulations they must not be dis posed of with normal refuse Type 6032 IEC CR2032 System Li MnO2 org elyt Volt...

Page 270: ...264 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...

Page 271: ...follow ing text message As 2 modbus registers are used to pass an address to function 16 the Number of Addresses has to be back calculated from the required Byte Count to give the lowest integer such that Number of Addresses 2 Byte Count For example if Byte Count 4 then Number of Addresses 2 but if Byte Count 5 Number of Addresses 3 As an example to send the 5 character message Start to a slave ad...

Page 272: ...ock these values can be displayed on the pens i e P1 CV1 will set Pen 1 to the engineering value set address 1880 with the function code 16 Once again these are 4 byte IEEE floats using 2 Modbus registers per reading Pen Values Pen values in engineering units 4 byte IEEE floats using 2 Modbus registers per reading CV1 CV32 CV33 CV64 CV1 1880 CV32 ECV1 2400 ECV 64 Comms variable to be used in Maths...

Page 273: ...23 always equals 05 data blocks are always in order 00 Analogue inputs 02 Digital inputs 03 Digital outputs 06 Pens 09 Totalisers Item Size in bytes Contents Device Description 16d 0x10 Recorder type space software version The length is extended to exactly 16 bytes by trailing 0x00 characters Recorder type is a combination of the OEM series name followed by the OEM device name truncated to 16 char...

Page 274: ...268 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 Modbus Function Codes ...

Page 275: ... 134 Signal Wiring 18 Analogue Out Menu 55 Analogue Output Card 21 Channel Numbers 22 Connection Details 22 Diagnostics 135 Analogue Output Specifications 219 Appearance 106 Appendix A Quality and Safety 231 Appendix B Maths Expressions 233 Appendix C Thermocouple Connections 247 Appendix D Alarms 251 Appendix E Ethernet 253 Appendix F Fuzzy Logging 255 Appendix G F sub zero Sterilisation 259 Appe...

Page 276: ...atus 138 Peers Status 139 SMTP Status 138 Comms Menu DNS WINS MDNS 72 IP Address 71 Ports 72 74 Services 71 TCP IP 71 USB Comms Ports 74 Comms Server 182 Add Pens for Logging 191 Add a Database 185 195 Add a Database Server 185 195 Add a Device 186 Add a new Device 183 Administration 183 Client Connections 193 Comms Server Overview 182 Configure Database Logging 183 Connect to a Database 185 195 C...

Page 277: ...04 Settings 105 Edit Screen Properties Custom Screens 113 Standard Screens 113 Edit Setup 49 Edit Standard Screens 113 Electrical Installation 13 24V DC Input 28 AC Power 14 Alarm Relay Card Connections 24 Analogue Input Card 16 Analogue Output Card 21 Cables 13 Comms Connections 28 DC Power 14 Digital IO Card Connections 24 Fuses 13 Installation Category 13 Pulse Input Card 22 SPCO Relay 29 Signa...

Page 278: ...ime Password Setup ESS 142 Full Maths 168 241 Full Maths Script Processing 233 Function Codes and Memory Maps 265 Functions and Features Overview 31 Fuses 13 Fuzzy Logging Appendix F 255 G General Menu 90 Batch Menu 97 Factory 91 Groups 99 Ident 90 Localisation 91 Printer Menu 98 Getting connected IP Address 174 Groups 99 H Hardware Options Overview 37 Hardware Status Diagnostics 133 Hazardous Vol...

Page 279: ...4 Messages Menu 122 Passwords 108 Process Menu 125 Recording Menu 120 Screen Menu 113 Setup Menu 48 Status Menu 127 Main Menu Access 43 Maintenance Backlights 217 Calibration 218 Cleaning 217 Operating Temperature 217 Touch Screen 218 Maintenance Status 131 Map button 114 Mark Chart Alarms 67 Mark on Chart 85 156 163 Mark on Chart Event 85 Maths Credit Options 233 Maths Error Messages 246 Maths Ex...

Page 280: ...e 37 Recorder Functionality 33 Remote Control Viewer 35 SIREC D200 Rear Connections 41 SIREC D200 Standard Screens 40 SIREC D300 Rear Connections 41 SIREC D300 Standard Screens 39 SIREC D400 Rear Connections 42 SIREC D400 Standard Screens 38 Security 35 USB Devices 35 P PC Ethernet Connections 173 Panel Mounting 11 Panel cut out size 6 Password Policy 143 Password Security 141 Audit Trail 144 ESS ...

Page 281: ...ion 220 Remote Control Viewer Overview 35 Remote Networks Comms 175 Remote Viewer 169 Replay 116 158 Cursor 158 Reset Passwords 111 Reset Setup 96 Resistance Thermometers 18 S SIREC D Software 201 SIREC Manager 201 SIREC Server 201 SIREC Viewer 201 SIREC D200 Rear Connections 41 SIREC D200 Standard Screens 40 SIREC D200 and 300 Portable Case 206 215 SIREC D300 Rear Connections 41 SIREC D300 Standa...

Page 282: ...IO 56 Edit Setup 49 Email 76 Events Menu 79 FTP 78 Factory 91 Field IO 50 Firmware Upgrade 92 General 90 Groups 99 IP Address 71 Ident 90 Language 91 Line Hz 91 Load Menu 48 Localisation 91 Logging 64 Modbus 75 Peers 79 Pens 62 Printer Menu 98 Pulse Input 58 SNTP 77 Save Setup 48 Scale Menu 63 Screen Saver 100 Services 71 TCP IP 71 Temp Units 91 Time Zone 91 Totaliser 68 Web Enable 75 Signal Wirin...

Page 283: ... Internal Reference 248 Thermocouple CJC Compensation 248 Thermocouple Connections Appendix C 247 Time Settings 111 Time Zone 91 Totaliser 68 Displaying Totals 70 Event Causes 82 F sub 0 68 Sterilisation 70 Totaliser Event Effects 87 Totals Start Stop Reset 125 Touch Screen 218 Touch Test 116 Trademarks 1 Transmitter Power Supply Card 24 U USB Comms Ports 74 USB Devices Overview 35 USB Key Format ...

Page 284: ...278 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...

Page 285: ......

Page 286: ...Automation and Drives A D Sensors and Communication Process Sensors 76181 KARLSRUHE GERMANY Display recorders SIREC D200 SIREC D300 SIREC D400 www siemens com processinstrumentation Display recorders SIREC D200 D300 D400 12 2006 Manual Edition sirec A5E01001767 04 1PA5E010001767 A5E01001767 ...

Reviews: