background image

A6V10324661_en--_m

SIEMENS Industry, Inc.

2020-08-28

Smart Infrastructure

Installation Instructions
Model OOHC941

Multi-Criteria Fire/CO Detector

UL268 7th edition listed

Figure 1

These  instructions  are  written  in  accordance  with  the
installation guidelines of NFPA 72, National Fire Alarm
Code and CAN/ULC-S524, The Installation of Fire
Alarm  Systems.  The  model  OOHC941  detector  (as
shown  in  Figure  1)  meets  the  VEWFD  (Very  Early
Warning  Fire  Detector)  classification  and  sensitivity
requirements  of  NFPA  76  (Standard  for  the  Fire
Protection 

of

Telecommunications 

Facilities)

incorporating  a  programmable  “Alert”  (Pre-Alarm)
sensitivity  threshold  of  0.2%/ft  obscuration  and  an
“Alarm” sensitivity threshold of 1.0%/ft obscuration.

CAUTION

DO NOT install this detection device until all construction
is completed.
DO  NOT  store  this  detection  device  where  it  can  be
contaminated by dirt, dust, or humidity.

DETECTOR PLACEMENT

Although no specific spacings are set for the detectors
used  for  a  clean  air  application,  for  multi-criteria  fire
detection  use  30-foot center  spacing  (900  sq  ft)  from
NFPA  72  initiating  devices  chapter,  if  practical,  as  a
guide or starting point for a detector installation layout.
This  spacing,  however,  is  based  on  ideal  conditions–
smooth  ceiling,  no  air  movement,  and  no physical
obstructions. 

In 

some 

applications, 

therefore,

considerably less area is protected adequately by each
smoke  detector.  This  is  why  it  is  mandatory  to  closely
follow the installation drawings. In all installations place
the detector on the ceiling, a minimum of 6 inches from
a side wall, or on a wall, 12 inches from the ceiling. For
CO  gas  detection  applications,  follow  detector
installation  requirements  in  NFPA  72 for  Installation  of
Carbon Monoxide Detection and Warning Equipment.

  For thermal detection, use the matrix below:

Spacing, Feet Temperature Rating, °F With/without Guard Model

50

135, 145, 155, 165, 175

With and without STI Guard

60

135, 145, 155, 165, 175

70

135, 145

Drawings  provided  or  approved  by  Siemens Industry,
Inc.,  or  by  its  authorized  distributors  are extremely
important. The  detector  placements  shown  on  these
drawings were chosen after a careful evaluation of the
area  that  is  protected.  Such  factors  as  air  currents,
temperature,  humidity,  pressure, and  the  nature  of  the
fire  load  were  carefully  considered.  Especially  noted
were  the  room  or  area  configuration  and  the  type  of
ceiling  (sloped  or  flat,  smooth  or  beamed).  Siemens
Industry, Inc.’s extensive experience in the design of the
system assures the best detector placement by following
these  drawings. Sound  engineering  judgment  by
qualified personnel must be followed.

TO AVOID NUISANCE ALARMS

Do  not  locate  the  detectors  where  excessive  smoke
concentrations exist under normal conditions, or in areas
of prolonged high relative humidity where condensation
occurs.
Do  not  locate  the  detectors  next  to  an  oil  burner, or
garage where exhaust fumes can trigger an alarm. Other
causes  of  false  alarm  are  dust  accumulation,  heavy
concentrations of steam, heavy pipe or cigar smoke, and
certain aerosol sprays.

Summary of Contents for OOHC941

Page 1: ...datory to closely follow the installation drawings In all installations place the detector on the ceiling a minimum of 6 inches from a side wall or on a wall 12 inches from the ceiling For CO gas detection applications follow detector installation requirements in NFPA 72 for Installation of Carbon Monoxide Detection and Warning Equipment For thermal detection use the matrix below Spacing Feet Temp...

Page 2: ... can also be installed in duct applications between 0 and 4000 ft min For duct installations follow detector installation requirements in NFPA 90A Chapter for Special Ceiling Construction Factors When the detectors employ a fixed temperature rating of 165 F 74 C or less they are intended for a maximum installation temperature of 100 F 38 C LED INDICATOR OPERATION The Model OOHC941 contains an LED ...

Page 3: ...op When the OOHC941 is wired for Isolator mode the positive line needs to be connected to 1b and the negative line to 6 The next device needs to be connected to 1b and 5 The Line Isolator is located between connector 6 and 5 NOTICE Ensure that the panel supports Isolator mode for the OOHC941 product version 30 Isolator mode must not be used with a OOHC941 product version 30 You will find the produ...

Page 4: ...mitory Airborne dust and temperature changes living quarters Cooking fumes smoking and steam Utility Room Transformer room normal to somewhat dirty environment heat from running equipment Lobby Relatively clean area temperature changes cellular phones some outside particulate Office Reasonably clean climate controlled atmosphere Hotel Life safety some temperature swings steam smoking and cooking p...

Page 5: ...TIBLE CONTROL UNIT OR PREVIOUS ADDRESSABLE DEVICE OPTIONAL REMOTE ALARM INDICATOR MODELS 8727W 8727C RL HW RL HC TO NEXT BASE TO NEXT BASE DO NOT USE AN END OF LINE DEVICE DETECTOR BASE MODEL DB 11 DB 11E LINE 1 LINE 2 5 6 1a TB1 TB3 TB2 1b 5 6 1a 1b The relay contacts are shown after System reset which represents the non alarm condition OOHC941 is a polarity insensitive detector Line 1 and Line 2...

Page 6: ...ensitivity and cause CO sensor troubles This test is simply used to ensure that smoke can enter the sensing chamber and alarm the control panel when the detector reaches the programmed obscuration concentration level CAUTION DO NOT use any test gas other than the one mentioned above as compatibility to the CO sensor cannot be assured CO DETECTOR FUNCTIONAL TEST CO TEST GAS The fire control panel m...

Page 7: ...pecial applications setting incorporates a pre alarm and sensitive alarm levels to provide a Very Early Waring Fire Detection VEWFD alarm level for applications to avoid business disruption Typical suitable applications for the special applications Telecommunications application profile include Telecommunications Data Centers IT rooms Clean Rooms Laboratories and any clean environment Applications...

Page 8: ...equipment in accordance with installation instructions manual Read the following information This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual may cause interference to radio communications It has been tested and found to comply with the limits for a Class A computing device pursuant to Part 15 of FCC Rules...

Reviews: