Summary of Contents for micromaster 410

Page 1: ......

Page 2: ...m Parameter structure Troubleshooting Specifications and available options of the MM410 Parameter List The Parameter List contains the description of all Parameters structured in functional order and a detailed description Catalogues In the catalogue you will find all the necessary information to select an appropriate inverter as well as filters chokes operator panels and communication options ...

Page 3: ...Converter Type Software version MICROMASTER 410 V1 6 Issue 04 02 Overview 1 Installation 2 Commissioning 3 Using the MICROMASTER 410 4 System Parameters 5 Troubleshooting 6 MICROMASTER 410 Specifications 7 Available options 8 Electro Magnetic Compatibility 9 Appendices A B C Index ...

Page 4: ...scribed in this document may be available However this fact shall not constitute an obligation to supply such functions with a new control or when servicing We have checked that the contents of this document correspond to the hardware and software described There may be discrepancies nevertheless and no guarantee can be given that they are completely identical The information contained in this doc...

Page 5: ......

Page 6: ...tion Qualified personnel For the purpose of this Instruction Manual and product labels a Qualified person is someone who is familiar with the installation mounting start up and operation of the equipment and the hazards involved He or she must have the following qualifications 1 Trained and authorized to energize de energize clear ground and tag circuits and equipment in accordance with establishe...

Page 7: ...ipment and only after becoming familiar with all safety notices installation operation and maintenance procedures contained in this manual The successful and safe operation of this equipment is dependent upon its proper handling installation operation and maintenance Risk of electric shock The DC link capacitors remain charged for five minutes after power has been removed It is not permissible to ...

Page 8: ...fied personnel trained in the setup installation commissioning and operation of the product should carry out work on the device system Only permanently wired input power connections are allowed This equipment must be grounded IEC 536 Class 1 NEC and other applicable standards If a Residual Current operated protective Device RCD is to be used it must be an RCD type B The following terminals can car...

Page 9: ...This equipment is capable of providing internal motor overload protection in accordance with UL508C section 42 Refer to P0610 and P0335 I 2 t is ON by default This equipment is suitable for use in a circuit capable of delivering not more than 10 000 symmetrical amperes rms for a maximum voltage of 115 V 230 V when protected by a H or K type fuse This equipment must not be used as an emergency stop...

Page 10: ...Safety Instructions Issue 04 02 MICROMASTER 410 Operating Instructions 10 6SE6400 5EA00 0BP0 ...

Page 11: ...lation 26 3 Commissioning 31 3 1 Block Diagram 32 3 2 Commission Modes 33 3 3 General operation 42 4 Using the MICROMASTER 410 45 4 1 Frequency Setpoint P1000 45 4 2 Command Sources P0700 46 4 3 OFF and braking Functions 46 4 4 Control Modes P1300 48 4 5 Faults and Alarms 48 5 System Parameters 49 5 1 Introduction to MICROMASTER System Parameters 49 5 2 Parameter Overview 50 5 3 Parameter List sho...

Page 12: ...5EA00 0BP0 8 Options 67 8 1 Variant Independent Options 67 8 2 Variant Dependent Options 67 9 Electro Magnetic Compatibility EMC 69 9 1 Electro Magnetic Compatibility EMC 69 Appendices 75 A Fitting the Operator Panel 75 B Applicable Standards 76 C List of Abbreviations 77 Index 78 ...

Page 13: ...ply Frequency 35 Figure 3 5 Buttons on the Operator Panel 37 Figure 3 6 Changing parameters via the OP 38 Figure 3 7 Typical Motor Rating Plate Example 41 Figure 3 8 Motor Overload PTC Connection 43 Figure 5 1 Parameter Overview 50 List of Tables Table 2 1 Single Phase 115 V Connection 21 Table 2 2 Single Phase 230 V Connection 21 Table 2 3 Derating with Pulse Frequencies 21 Table 2 4 Trip Levels ...

Page 14: ...Table of Contents Issue 04 02 MICROMASTER 410 Operating Instructions 14 6SE6400 5EA00 0BP0 ...

Page 15: ...on The MICROMASTER 410 with its default factory settings is ideal for a large range of simple motor control applications The MICROMASTER 410 can be used in both stand alone applications as well as being integrated into Automation Systems 1 2 Features Main Characteristics Ø Easy installation Ø Easy commissioning Ø Rugged EMC design Ø Can be operated on IT line supplies Ø Fast repeatable response ti...

Page 16: ...o improve braking performance Ø Acceleration deceleration times with programmable smoothing Ø Selectable up and down ramps Ø 4 point ramp smoothing Ø Multi point V f characteristic Ø 150 overload for 60 seconds Ø Automatic restart after a mains failure Ø Start on the fly Protection Characteristics Ø Overvoltage undervoltage protection Ø Overtemperature protection for the inverter Ø Ground fault pr...

Page 17: ...it must be an RCD type B The following terminals can carry dangerous voltages even if the inverter is inoperative the power supply terminals L and N the motor terminals U V W and the terminals DC and DC Always wait 5 minutes to allow the unit to discharge after switching off before carrying out any installation work This equipment must not be used as an emergency stop mechanism see EN 60204 9 2 5 ...

Page 18: ...ltage for one hour Storage period 2 to 3 years Prior to energizing form according to the curve Storage period 3 and more years Prior to energizing form according to the curve 100 50 75 0 5 1 Voltage Time t h 2 4 6 8 Figure 2 1 Forming The serial numbers consist 13 characters and contains the date of manufacture e g XAM214 123456 XAM214 123456 Characters 1 2 are the site where the product is built ...

Page 19: ...tude If the inverter is to be installed at an altitude 1000 m or 2000 m above sea level derating will be required Figure 2 3 below shows the permissible rated input voltages and output current for inverter installations from 500 m to 4000 m above sea level Permissible rated input voltage as a percentage of the nominal voltage 100 90 80 60 70 1000 2000 3000 4000 500 500 Installation altitude in met...

Page 20: ...spheric Pollution Do not install the inverter in an environment which contains atmospheric pollutants such as dust corrosive gases etc Water Take care to site the inverter away from potential water hazards e g do not install the inverter beneath pipes that are subject to condensation Avoid installing the inverter where excessive humidity and condensation may occur Installation and cooling CAUTION ...

Page 21: ...ps 6SE6410 2BB11 2AA0 B 6SE6410 2UB11 2AA0 UNFILTERED 0 12 1 34 1 20 0 83 0 45 0 18 0 12 0 06 6SE6410 2BB12 5AA0 B 6SE6410 2UB12 5AA0 UNFILTERED 0 25 2 90 2 40 1 70 0 95 0 40 0 20 0 20 6SE6410 2BB13 7AA0 B 6SE6410 2UB13 7AA0 UNFILTERED 0 37 4 10 3 50 2 50 1 40 0 60 0 25 0 25 6SE6410 2BB15 5BA0 B 6SE6410 2UB15 5BA0 UNFILTERED 0 55 5 30 4 60 3 30 1 80 0 70 0 40 0 40 6SE6410 2BB17 5BA0 B 6SE6410 2UB1...

Page 22: ... EQUIPMENT MUST BE GROUNDED To ensure the safe operation of the equipment it must be installed and commissioned by qualified personnel in full compliance with the warnings laid down in these operating instructions Take particular note of the general and regional installation and safety regulations regarding work on dangerous voltage installations e g EN 50178 as well as the relevant regulations re...

Page 23: ...mensions and Torques of MM410 Overall Dimensions Frame Size Height Width Depth Fixing Method Tightening Torque of fixings AA 150 mm 5 91 69 mm 2 72 118 mm 4 65 2 x M4 Bolts 2 x M4 Nuts 2 x M4 Washers or Connecting to DIN rail 2 5 Nm with washers fitted AB 150 mm 5 91 69 mm 2 72 138 mm 5 43 2 x M4 Bolts 2 x M4 Nuts 2 x M4 Washers or Connecting to DIN rail 2 5 Nm with washers fitted Not supplied wit...

Page 24: ...ackets The MICROMASTER 410 can be mounted using mounting brackets which are slotted into the heatsink at the rear of the inverter for normal mounting position see Figure 2 6 A For side mounting of the inverter the brackets are slotted into the heatsink as shown in Figure 2 6 B Figure 2 6 Mounting Brackets ...

Page 25: ...ecured to the retaining clip as shown in Drawing B 4 Ensure that the retaining clip can be moved in a downward direction as shown in Drawing C When the retaining clip is released it should return to its normal position in an upward direction If it does not the spring has been fitted incorrectly In order to fit the DIN Rail Mounting Kit to the inverter the following procedure should be performed 1 ...

Page 26: ...work The inverters can be installed in a side by side configuration with a minimum distance of 30 mm 1 18 inches between units and a distance of 100 mm 3 94 inches must be maintained if the inverters are installed on top of each other CAUTION The control power supply and motor leads must be laid separately Do not feed them through the same cable conduit trunking Never use high voltage insulation t...

Page 27: ...olate the mains electrical supply before making or changing connections to the unit Ensure that the inverter is configured for the correct supply voltage single phase 230 V MM410 MICROMASTERS must not be connected to a higher voltage supply The 115 V unit MUST only be connected to a 115 V supply When synchronous motors are connected or when connecting several motors in parallel the inverter must b...

Page 28: ...ease refer to the photographs showing the Power Terminal connections and the Control Terminal connections on the inside of the back cover of this manual Connect the power and motor connections as shown below For access to the DC DC terminals the cut out cover must be removed The terminal connection consists of two spades measuring 6 3 mm by 0 8 mm With the cut out cover removed and not connections...

Page 29: ... Connect the return ground from the motors controlled by the inverters directly to the ground connection PE on the associated inverter Ø Flat grounding conductors are preferred as they have lower impedance at higher frequencies Ø Terminate the ends of the cable neatly ensuring that unscreened wires are as short as possible Ø Separate the control cables from the power cables as much as possible usi...

Page 30: ...screened using the methodology shown in Figure 2 10 Legend 1 Motor cable 2 Use suitable clips to fix motor and control cable screens securely to metal back plate 3 Mains power cable 4 Metal mounting brackets 5 Line commutating Choke 6 Control cable Figure 2 10 Wiring Guidelines to Minimize the Effects of EMI ...

Page 31: ...ies provided to ensure or enforce safe operation even when a fault occurs e g independent limit switches mechanical interlocks etc Certain parameter settings may cause the inverter to restart automatically after an input power failure Motor parameters must be accurately configured for motor overload protection to operate correctly This equipment is capable of providing internal motor overload prot...

Page 32: ...3 Commissioning Issue 04 02 MICROMASTER 410 Operating Instructions 32 6SE6400 5EA00 0BP0 3 1 Block Diagram Figure 3 1 Inverter block diagram RS485 USS protocol ...

Page 33: ... analogue inputs Ø Ramp up time Ramp down time 10 s If more complex application settings are required please refer to the Parameter List Front Panels for the MICROMASTER 410 For instructions on how to exchange replace the Operator Panels please refer to the appropriate Appendix A in this manual To change the parameters of the inverter you will require the optional Operator Panel To assist in the q...

Page 34: ...put 1 1 P0701 1 ON OFF1 Digital Input 2 2 P0702 12 Reverse Digital Input 3 3 P0703 9 Fault Acknowledge Warnings and faults states on the Inverter The LED indicates the operating status of the inverter The LED also indicate various warnings or fault states In section 6 1 on page 57 the inverter states indicated by the LED are explained 3 2 2 Basic operation With the default settings of the inverter...

Page 35: ...erter can be set back to 50 Hz by setting P0100 0 Using the Operator Panel The supply frequency can be set by the following parameters Ø Set P0100 0 50 Hz default Ø Set P0100 1 60 Hz 3 2 4 Commissioning Overview with the optional Operator Panel Prerequisites Mechanical and electrical Installation are completed NOTE We recommend the commissioning according this scheme Nevertheless an expert user is...

Page 36: ...actory default settings for operation via the Operator Panel Notes The OP motor control functions are disabled by default To control the motor via the OP parameter P0700 should be set to 1 and P1000 set to 1 The OP can be fitted to and removed from the inverter whilst power is applied If the OP has been set as the I O control P0700 1 the drive will stop if the OP is removed Table 3 2 Default setti...

Page 37: ... causes the motor to start and run at the preset jog frequency The motor stops when the button is released Pressing this button when the motor is running has no effect Functions This button can be used to view additional information Pressing and holding the button for 2 seconds from any parameter during operation shows the following 1 DC link voltage indicated by d units V 2 Output frequency Hz 3 ...

Page 38: ... parameters 2 Press until P0004 is displayed 3 Press to access the parameter value level 4 Press or to the required value 5 Press to confirm and store the value 6 Only the motor parameters are visible to the user Changing P2011 an indexed parameter Setting USS address Step Result on display 1 Press to access parameters 2 Press until P2011 is displayed 3 Press to access the parameter value level 4 ...

Page 39: ...button again causes the next digit to blink 4 Perform steps 2 to 4 until the required value is displayed 5 Press the to leave the parameter value changing level NOTE The function button may also be used to acknowledge a fault condition 3 2 4 2 Quick commissioning P0010 1 It is important that parameter P0010 is used for commissioning and P0003 is used to select the number of parameters to be access...

Page 40: ...ockwise rotation P1082 Max Motor Frequency Sets maximum motor frequency 0 650Hz at which the motor will run at irrespective of the frequency setpoint The value set here is valid for both clockwise and anti clockwise rotation P1120 Ramp Up Time Acceptable Range 0 s 650 s Time taken for the motor to accelerate from standstill up to maximum motor frequency P1121 Ramp Down Time Acceptable Range 0 s 65...

Page 41: ... if P0003 3 Only one of the parameters is shown depending on the settings of P0100 Ø P0307 indicates kW or hp depending upon the setting of P0100 For detailed information please see the Parameter List Ø Changing motor parameters is not possible unless P0010 1 Ø Ensure that the motor is configured correctly to the inverter star delta connection 3 2 4 3 Reset to Factory default To reset all paramete...

Page 42: ...d applications on Siemens four pole standard motors that have the same power rating as the inverters When using other motors it is necessary to enter the specifications from the motor s rating plate See Figure 3 7 for details on how to read motor data 4 Changing motor parameters is not possible unless P0010 1 5 You must set P0010 back to 0 in order to initiate a run Basic operation with the OP Pre...

Page 43: ...ost motors require de rating for continuous operation at low frequencies To ensure that the motors are protected against overheating under these conditions a PTC temperature sensor must be fitted to the motor and connected to the inverter control terminals as shown in Figure 3 8 NOTE To enable the trip function set parameter P0701 P0702 or P0703 29 1 kΩ Motor PTC 4 5 1 2 or 3 Inverter Control Term...

Page 44: ...3 Commissioning Issue 04 02 MICROMASTER 410 Operating Instructions 44 6SE6400 5EA00 0BP0 ...

Page 45: ...rovided to ensure or enforce safe operation even when a fault occurs e g independent limit switches mechanical interlocks etc MICROMASTERS operate at high voltages Certain parameter settings may cause the inverter to restart automatically after an input power failure Motor parameters must be accurately configured for motor overload protection to operate correctly This equipment is capable of provi...

Page 46: ...ff button on Operator Panel pressing the Off button once long two seconds or twice with default settings OFF3 no standard setting Ø Other settings see P0700 to P0704 Reversing the motor Ø Default Terminal 2 DIN 2 high Ø Other settings see P0700 to P0704 4 3 OFF and braking Functions 4 3 1 OFF1 This command produced by canceling the ON command causes the inverter to come to a standstill at the sele...

Page 47: ...gh the motor can be started resp stopped by re setting OFF1 or OFF2 If OFF3 is low the motor cannot be started Ø Ramp down time see P1135 NOTICE OFF3 can be combined with DC braking or Compound braking 4 3 4 DC braking DC braking is possible together with OFF1 and OFF3 A DC current is applied to stop the motor quickly and hold the shaft stationary after the end of the braking period Ø Enable DC br...

Page 48: ...namic response of the motor Ø Quadratic V f control P1300 2 This mode can be used for variable torque loads such as fans and pumps Ø Multi point V f control P1300 3 For information regarding this mode of operation please consult the MM410 Parameter List 4 5 Faults and Alarms Standard Inverter If an Operator Panel is not fitted the fault states and warnings are indicated by the LED on the panel see...

Page 49: ...ion is automatically performed if P3900 0 Ø P0004 acts as a filter allowing access to parameters according to their functionality Ø If an attempt is made to change a parameter that cannot be changed in this status for example cannot be changed whilst running or can only be changed in quick commissioning then will be displayed Ø Busy Message In some cases when changing parameter values the display ...

Page 50: ...ring P0004 0 no filter function allows direct access to the parameters for the operating panel OP depending on the selected access level P0004 10 Setpoint Channel P 0 0 0 3 3 Access Level E x p e r t P0004 10 P0003 1 Parameters level 1 Parameter accessed P1000 P0004 10 P0003 2 Parameters level 1 and 2 Parameter accessed P1000 P1001 P1002 P1003 P0004 10 P0003 3 Parameters level 1 2 and 3 Parameter ...

Page 51: ...ParNr ParText Default Acc DS QC r0000 Drive display 1 P0003 User access level 1 1 CUT N P0004 Parameter filter 0 3 CUT N P0010 Commissioning parameter filter 0 1 CT N Quick Commissioning ParNr ParText Default Acc DS QC P0100 Europe North America 0 1 C Q P0101 Hidden Switch Setting 0 1 C Q P3900 End of quick commissioning 0 1 C Q Parameter Reset ParNr ParText Default Acc DS QC P0970 Factory reset 0...

Page 52: ...el 100 0 3 CUT N P0640 Motor overload factor 190 0 3 CUT Q P1910 Select motor data identification 0 2 CT Q Commands and Digital I O P0004 7 ParNr ParText Default Acc DS QC r0002 Drive state 3 r0019 CO BO BOP control word 3 r0052 CO BO Act Status word 1 2 r0053 CO BO Act Status word 2 2 r0054 CO BO Act Control word 1 3 r0055 CO BO Add Act Control word 3 P0700 Selection of command source 2 1 CT Q P0...

Page 53: ... 00 2 CUT N P1003 Fixed frequency 3 10 00 2 CUT N r1024 CO Act Fixed frequency 3 P1031 Setpoint memory of the MOP 0 2 CUT N P1032 Inhibit reverse direction of MOP 1 3 CT N P1040 Setpoint of the MOP 5 00 3 CUT N P1070 CI Main setpoint 755 0 3 CT N P1071 CI Main setpoint scaling 1 0 3 CT N P1075 CI Additional setpoint 0 0 3 CT N r1078 CO Total frequency setpoint 3 P1080 Min frequency 0 00 1 CUT Q P1...

Page 54: ...04 13 ParNr ParText Default Acc DS QC r0020 CO Act frequency setpoint 2 r0021 CO Act frequency 2 r0022 Act rotor speed 3 r0024 CO Act output frequency 3 r0025 CO Act output voltage 3 r0056 CO BO Status of motor control 2 r0067 CO Act output current limit 3 P1300 Control mode 0 2 CT Q P1310 Continuous boost 50 0 2 CUT N P1311 Acceleration boost 0 0 3 CUT N P1312 Starting boost 0 0 2 CUT N P1316 Boo...

Page 55: ...P2016 4 CI PZD to BOP link USS 52 0 3 CT N r2018 4 CO PZD from COM link USS 3 P2019 4 CI PZD to COM link USS 52 0 3 CT N r2024 2 USS error free telegrams 3 r2025 2 USS rejected telegrams 3 r2026 2 USS character frame error 3 r2027 2 USS overrun error 3 r2028 2 USS parity error 3 r2029 2 USS start not identified 3 r2030 2 USS BCC error 3 r2032 BO CtrlWrd1 from BOP link USS 3 r2031 2 USS length erro...

Page 56: ...5 System Parameters Issue 04 02 MICROMASTER 410 Operating Instructions 56 6SE6400 5EA00 0BP0 ...

Page 57: ...LED lit Ø Power On Ready 1000 ms On 1000 ms Off Ø Inverter Running OK Steady LED Ø General Warning 500 ms On 200 ms Off Ø Fault Condition 100 ms On 100 ms Off 6 2 Troubleshooting with the Operator Panel OP If the display shows a fault or warning code please refer to Section 6 3 If the motor fails to start when the ON command has been given Ø Check that P0010 0 Ø Check that a valid ON signal is pre...

Page 58: ...mes OFF2 F0003 UnderVoltage Ø Main supply failed Ø Shock load outside specified limits Check the following 1 Supply voltage P0210 must lie within limits indicated on the inverter rating plate 2 Supply must not be susceptible to temporary failures or voltage reductions OFF2 F0004 Inverter Over Temperature Ø Ventilation inadequate Ø Ambient temperature is too high Check the following 1 Pulse frequen...

Page 59: ...legram off time Check USS master OFF2 F0072 USS COMM link setpoint fault No setpoint values from USS during telegram off time Check USS master OFF2 F0085 External Fault External fault triggered via terminal inputs Disable terminal input for fault trigger OFF2 F0101 Stack Overflow Software error or processor failure Ø Cycle through power on off Ø Replace drive if fault is not corrected OFF2 F0450 B...

Page 60: ... temperature must lie within specified limits 2 Load conditions and duty cycle must be appropriate A0505 Inverter I2 t Warning level exceeded current will be reduced if parameterized P0610 1 Check that duty cycle lies within specified limits A0506 Inverter duty cycle Difference between heatsink and IGBT junction temperature exceeds warning limits Check that duty cycle and shock loads lie within sp...

Page 61: ... parameters not set properly ADC parameters should not be set to identical values since this would produce illogical results Check P0757 P0758 P0759 and P0760 A0922 No load applied to inverter No Load is applied to the inverter As a result some functions may not work as under normal load conditions Check that a load has been applied to the inverter ...

Page 62: ...6 Troubleshooting Issue 04 02 MICROMASTER 410 Operating Instructions 62 6SE6400 5EA00 0BP0 ...

Page 63: ...logue motor potentiometer 0 1 Hz Output Frequency Resolution 0 01 Hz digital 0 01 Hz serial Digital Inputs PNP type 3 freely programmable non isolated SIMATIC compatible Analog Input 1 for setpoint 0 to 10 V scalable or for use as 4th digital input Relay Output 1 parameterizable 30 V DC 5 A resistive 250 V AC 2 A inductive Serial Interface RS 485 for operation with USS protocol Electromagnetic Com...

Page 64: ...0 16 0 33 0 5 0 75 1 0 Output Current Max A 0 9 1 7 2 3 3 2 4 2 Input Current A 1 5 3 0 4 4 5 8 7 8 10 10 10 10 16 Recommended Fuse A 3NA3803 3NA3803 3NA3803 3NA3803 3NA3805 mm2 1 0 1 0 1 0 1 0 1 5 Input Cable Min awg 16 16 16 16 14 mm2 2 5 2 5 2 5 2 5 2 5 Input Cable Max awg 12 12 12 12 12 mm2 1 0 1 0 1 0 1 0 1 0 Output Cable Min awg 16 16 16 16 16 mm2 2 5 2 5 2 5 2 5 2 5 Output Cable Max awg 12 ...

Page 65: ...9 0 69 0 69 0 69 0 69 0 h mm 150 0 150 0 150 0 150 0 150 0 d mm 118 0 118 0 118 0 138 0 138 0 w inches 2 72 2 72 2 72 2 72 2 72 h inches 5 90 5 90 5 90 5 90 5 90 Dimensions d inches 4 65 4 65 4 65 5 43 5 43 Input voltage range 1 AC 100 V 120 V 10 Unfiltered Order No 6SE6410 2UA11 2AA0 2UA12 5AA0 2UA13 7AA0 2UA15 5BA0 kW 0 12 0 25 0 37 0 55 Motor Output Rating hp 0 16 0 33 0 5 0 75 Output Current M...

Page 66: ...7 MICROMASTER 410 Specifications Issue 04 02 MICROMASTER 410 Operating Instructions 66 6SE6400 5EA00 0BP0 ...

Page 67: ...0 Inverter For more details please refer to the catalogue or contact your local Siemens sales office if you require assistance 8 1 Variant Independent Options Ø Operator Panel OP Ø DIN Rail Mounting Kit Ø PC to inverter connection kit Ø Software commissioning tools DriveMonitor Starter 8 2 Variant Dependent Options Ø Low leakage Class B filter Ø Line commutating choke ...

Page 68: ...8 Options Issue 04 02 MICROMASTER 410 Operating Instructions 68 6SE6400 5EA00 0BP0 ...

Page 69: ...is intended have been met Only standards that have been officially published in the Official Journal of the European Community can be cited in the manufacturer s declaration 9 1 2 Technical Construction File A technical construction file can be prepared for the apparatus describing its EMC characteristics This file must be approved by a Competent Body appointed by the appropriate European governme...

Page 70: ...urther information Units connected to Industrial Networks1 do not require connection approval see EN 61800 3 section 6 1 2 2 The harmonic current emissions from these products are described in the table below Rating Typical Harmonic Current A Typical Harmonic Current Typical Voltage Distortion Distribution Transformer Rating 10kVA 100kVA 1MVA 3rd 5th 7th 9th 11th 3rd 5th 7th 9th 11th THD THD THD 2...

Page 71: ...3 26 1000 MHz 10 V m Case 2 Filtered Industrial This level of performance will allow the manufacturer assembler to self certify their apparatus for compliance with the EMC directive for the industrial environment as regards the EMC performance characteristics of the power drive system Performance limits are as specified in the Generic Industrial Emissions and Immunity standards EN 50081 2 and EN 6...

Page 72: ...ps Unbalance Frequency Variations EN 61000 2 1 Electrostatic Discharge EN 61000 4 2 8 kV air discharge Burst Interference EN 61000 4 4 2 kV power cables Level 3 2 kV control Level 4 These limits are dependent on the inverter being correctly installed inside a metallic switchgear enclosure The limits will not be met if the inverter is not enclosed NOTICE To achieve these performance levels you must...

Page 73: ... m 32 80 ft Class A In addition a warning label will be required This is a product of category C2 according to IEC 61800 3 In a domestic environment this product may cause radio interference in which case mitigation measures may be required denotes any value is allowed 2 category C1 Power Drive system PDS of rated voltage less than 1000V intended for use in the first environment 3 category C2 Powe...

Page 74: ......

Page 75: ...Issue 04 02 Fitting the Operator Panel MICROMASTER 410 Operating Instructions 6SE6400 5EA00 0BP0 75 Appendices A Fitting the Operator Panel ...

Page 76: ...alled according to the recommendations described in this manual the MICROMASTER fulfils all requirements of the EMC Directive as defined by the EMC Product Standard for Power Drive Systems EN61800 3 Underwriters Laboratories UL and CUL LISTED POWER CONVERSION EQUIPMENT 5B33 for use in a pollution degree 2 ISO 9001 Siemens plc operates a quality management system which complies with the requirement...

Page 77: ...ge Circuit Breaker EMC Electro Magnetic Compatibility EMI Electro Magnetic Interference FAQ Frequently Asked Question FCC Flux Current Control FCL Fast Current Limitation IGBT Insulated Gate Bipolar Transistor I O Input and Output LCD Liquid Crystal Display LED Light Emitting Diode OP Operator Panel PLC Programmable Logic Controller PTC Positive Temperature Coefficient RCCB Residual Current Circui...

Page 78: ...mpatibility general 69 self certification 69 technical construction file 69 Electro Magnetic Interference 29 avoiding EMI 29 Electromagnetic radiation 20 EMC 69 EMC Directive Compliance 70 EMC performance filtered for residential commercial and light industry 72 filtered industrial class 71 general industrial class 71 EMI 29 External motor thermal overload protection 43 F Fault codes with the Oper...

Page 79: ... OP 38 system parameters 49 Performance characteristics 16 Performance Ratings 63 Power and motor connections 27 single phase 29 Power connections 27 Power Losses output graphs 19 Protection characteristics 16 Q Quadratic V f control 48 Qualified personnel 6 Quick commissioning 39 R Reset to Factory default 41 Residual Current Device operation with 27 S Safety instructions 7 Shock 20 Specification...

Page 80: ...Index Issue 04 02 MICROMASTER 410 Operating Instructions 80 6SE6400 5EA00 0BP0 ...

Page 81: ...many For Publication Manual MICROMASTER 410 Email Technical documentation con siemens co uk User Documentation From Name Operating Instructions Order Number 6SE6400 5EA00 0BP0 Date of Issue 04 02 Company Service Department Address Telephone __________ Telefax ________ Should you come across any printing errors when reading this publication please notify us on this sheet Suggestions for improvement...

Page 82: ...MICROMASTER 410 Operating Instructions 82 6SE6400 5EA00 0BP0 ...

Page 83: ...g Instructions 6SE6400 5EA00 0BP0 83 View of Unit Standard Inverter Inverter with Optional Operator Panel Fitted Key 1 Line Terminals 2 Status LED 3 Operator Panel Connector 4 Control Terminals 5 Motor Terminals 6 DC DC Terminals Connections Terminals ...

Page 84: ......