background image

 

1

Intelli-Arc

TM 

Diagnostic Tool  

Instruction Sheet 

Base unit

Handheld device

Summary of Contents for Intelli-Arc

Page 1: ...1 Intelli ArcTM Diagnostic Tool Instruction Sheet Base unit Handheld device ...

Page 2: ...branch circuit protection device rated at 20 Amperes or less 4 To prevent severe shock or electrocution always turn the power off before working on or inside equipment 5 It is the qualified electrician s responsibility to ensure a secured safe working area around the enclosure before turning on power to the equipment 6 Intelli Arc Diagnostic Tool is intended for temporary installation only Never l...

Page 3: ...s are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equ...

Page 4: ...etween 4 and 5 feet c Strip insulation of wires should be limited to a length of 3 8 inch See Intelli Arc Diagnostic Tool base unit label for stripping guide d Ensure that wire connectors are properly torqued Do not over torque See Intelli Arc Diagnostic Tool base unit label and circuit breaker label for the respective torque criteria e Wiring scheme to install base unit of Diagnostic Tool Load Ho...

Page 5: ...and AF LEDs will lock in the top red position when any event causes the device to read maximum levels even if the event ceases to exist Press the CLEAR button to continue evaluation of the branch circuit 8 Turn off and lock out power supplying the device before removing base unit Restore all branch circuit connections Close cover if testing is complete or return to step 1 of Installation Instructi...

Page 6: ... intervals 3 The 5 A point is marked on handheld device for reference Ground Fault GF 1 The full scale current for this LED indication is 50 mA Arc Fault AF 1 This LED indication does not display in reference to current level but rather in severity of events with a full scale reading red LED representing an event that is very likely to cause an AFCI device to trip 2 Partial readings yellow LEDs ma...

Page 7: ... Pollution degree Pollution degree 2 Wire requirements 4 Wires 4 5 feet length 60 75ºC CU 14 8 AL 10 8 Maximum torque for terminal lugs 25 lb in Handheld Batteries The Diagnostic Tool handheld device operates on 2 AA batteries These batteries may be accessed from the back side of the handheld device See Figure 4 below For battery disposal please follow instructions of battery manufacturer Battery ...