Installation and Wiring Instructions

MODEL FS-MSM

Addressable Manual Station

The 

SIEMENS

 FS-MSM Addressable Manual Station

is an addressable device containing advanced control

panel communication technology. This technology

which provides bidirectional communication with the

control panel, produces an Intelligent Initiating

Device. The FS-MSM is a single action station; when

used with the MS-FD Adapter, it is a double action

station. The FS-MSM Addressable Manual Station is

compatible with the FS-100 Fire Alarm Control Unit.
When an alarm condition occurs, pull down on the

PULL DOWN lever of the manual station. The pull-

down cover remains down and locked until the station

is reset. The FS-MSM with the MS-FD Adapter has

an additional lever labeled LIFT - PULL HANDLE

which must be lifted up before access is provided to

the station PULL DOWN lever.

PARTS SUPPLIED

1

FS-MSM Addressable Manual Station

2

Screws, #6-32 x 3/4”

1

Glass Rod

1

Allen Wrench

1

Instruction Sheet

Step 1.) Installation is to be done by qualified personnel who

have thoroughly read and understood this instruction
sheet.

Step 2.) Disconnect all power into system, including batteries.
Step 3.) Mount box, attach conduit and run wires as required.

CAUTION:

1. To prevent damage to the FS-FPI, do not connect

modules to the FS-FPI until the Addressable Device

Circuit wiring is disconnected.

2. Only one device must be connected to the FS-FPI at a

time.

Step 4.) Plug the programming cable of the FS-FPI  Programmer/

Tester into the two-pin receptacle on the module.

Step 5.) Set the address for the module by following the

instructions in the FS-FPI Programmer/Tester Manual

(P/N 315-699480).

Step 6.) Record the device address on the nameplate located

on the inside of the manual station mounting plate.

Step 7.) Connect  wires  to  the  fire  alarm  system  control  unit  as

directed in Figure 1.

Step 8.) Mount the FS-MSM (Refer to Figures 2 and 3).

CAUTION:

Do not overtighten the screws. Overtightening may

distort the backplate.

Step 9.) Apply power to system.

Step 10.) Check for proper operation of functions.

TO RESET STATION

1. Turn lock barrel 1/4 turn counter-clockwise with the allen key

provided. This will allow the front to hinge down, releasing

PULL-DOWN plate to disengage from the switch.

2. Return the front to its closed position, then turn the lock

barrel back clockwise.

+

+

_

_

TO NEXT ADDRESSABLE DEVICE

GROUND

1

2

3

FROM

OR PREVIOUS

ADDRESSABLE DEVICE

ADDRESSABLE

DEVICE CIRCUIT OF A

COMPATIBLE CONTROL

UNIT

ADDRESSABLE DEVICE CIRCUIT

24VDC NOMINAL, SUPERVISED

NOTES:

1. Units to be installed in accordance with all local electrical

codes.

2. Terminal  block  will  accept  a  maximum  of  #14  AWG

wiring.

3. Place manual stations according to the regulations of the

authorities having jurisdiction.

4. Requires unshielded, twisted pair, low capacitance cable.

Refer to the wire selection guide in the FS-100 Manual,

P/N 315-699461, for full details.

Figure 1

FS-MSM Wiring