background image

CA2N1644en_05 
02.08.2010 

Building Technologies

 

 

1

644

 

 

 

 

 

 

 DESIGO™ 

 

RX 

 

 

Receiver with 
PPS2 interface 

RXZ90.1

 

for use in conjunction with wireless room units QAX90.1/ QAX91.1, with 
 

–  devices of the ranges DESIGO RXC, RXB, RXL, and RXA (PPS2)  

 

–  DESIGO PX Automation stations 

 

–  devices with a PPS2 or PPS interface 

 

 

 

Wireless acquisition of room temperature and setpoint adjustments 

 

For use only in conjunction with the QAX90.1/QAX91.1 wireless room units 
(data sheet CA2N1643) 

 

Determines the average room temperature from several room units 

 

PPS2 interface to controller, may be changed to PPS 

 

Socket for commissioning and service tool, diagnostic plug or service terminal 

Use 

The RXZ90.1 is used for wireless reception of the room temperature (from the 
QAX90.1) and the room temperature setpoint (from the QAX91.1), and for transmission 
of this information to a room controller. Wireless range indoors: approx. 30m. 

Types 

RXZ90.1 

Receiver with PPS2 interface 

 

Summary of Contents for DESIGO RXZ90.1

Page 1: ... use only in conjunction with the QAX90 1 QAX91 1 wireless room units data sheet CA2N1643 Determines the average room temperature from several room units PPS2 interface to controller may be changed to PPS Socket for commissioning and service tool diagnostic plug or service terminal Use The RXZ90 1 is used for wireless reception of the room temperature from the QAX90 1 and the room temperature setp...

Page 2: ...ceiver determines the average of the temperature values received The average room temperature is then transmitted to the room controller In the case of room units with setpoint adjusters QAX91 1 only one may be assigned to each receiver Other room units with setpoint adjusters are treated as QAX90 1 units room temperature only QAX91 1 QAX90 1 QAX90 1 RXZ90 1 QAX90 1 QAX90 1 00481 A 868 MHz Design ...

Page 3: ...municipal waste The relevant national legal rules are to be adhered to Regarding disposal use the systems setup for collecting electronic waste Observe all local and applicable laws Engineering notes The receiver receives its power via the PPS2 interface Receiver range approx 30 m and up to 100 m in the open The range can vary widely Room topologies and building materials metal concrete etc reduce...

Page 4: ...ec Commissioning and establishing wireless communication Please do not make any adjustments without a careful reading of the following commissioning notes The unit s must be mounted at least 1 metre from the receiver Where there is more than one receiver in the same building communication must be established with each receiver separately after a time delay This is because commissioning signals can...

Page 5: ...e Insert batteries in the replacement unit s these will switch to installation mode The receiver recognises all newly connected room units and adds these to its device list Caution Wait 4 minutes before changing any further links Sustained pressure 5s on the button of one of the existing room units The receiver will delete this room unit from its device list and then switch to installation mode In...

Page 6: ...is connected to the controller and its device list is empty With fewer than 5 room units registered connecting the diagnostic plug to the receiver and pressing the button briefly 1s Plugging the RXT20 1 service terminal into the receiver with an empty device list and pressing the service pin on the RXT20 1 4s Sustained pressure 5s on the button of an existing room unit The receiver will delete thi...

Page 7: ...ause 4 room units 4 flashes 5 s pause 5 room units 5 flashes 5 s pause Normal mode Receiver s device list not empty and PPS2 communication not working Flashes more slowly approx once s e g during initialisation of the controller after POWER ON Status Green LED signals PPS2 power supply ON ON continuously PPS2 short circuit OFF Pushbutton Action Brief pressure 1s Sets receiver to installation mode ...

Page 8: ...ingle cable length controller Room unit See Installation guidelines DESIGO RXC CA110334 DESIGO RXB RXL CM110891 DESIGO RXA CA2Z3884 DESIGO PX CA110396 2 core or 4 core twisted pairs unscreened Tool connecting cable Made up in house max 3 m Housing protection standard Protection standard to EN 60529 IP 30 Protection class Insulation protection class III Ambient conditions Ambient conditions to IEC7...

Page 9: ...S2 data negative Bus connection looped to tool socket C 3 with LONWORKS bus DESIGO RXC CLA C 4 with LONWORKS bus DESIGO RXC CLB 5 8 Not used Tool socket Standard RJ45 tool socket Communication Diagnostic plug 1 3206Z01 2 3 45 67 8 1 with LONWORKS bus DESIGO RXC CLA 2 with LONWORKS bus DESIGO RXC CLB 3 4 5 6 7 CP PPS2 data 8 CP PPS2 data Button for installation Button for installation Red LED Red L...

Page 10: ...10 10 Siemens RXZ90 1 Receiver with PPS2 interface CA2N1644en_05 Building Technologies 02 08 2010 Dimensions 9 5 32 36 4 2 60 00496 90 100 56 60 56 2000 2010 Siemens Switzerland Ltd Subject to change ...

Reviews: