P/N 315-050263-3

Audio Level Conversion Card

Installation Instructions
Model ALCC

INTRODUCTION

The Model ALCC from Siemens Industry, Inc., is an
Audio Level Conversion Card that contains two audio
channels. Each channel is capable of accepting speaker-
level audio at 70VRMS from Siemens amplifier models
ZAC-30 (MXL) and ZAC-40 (XLS/Desigo Fire Safety
Modular/Cerberus PRO Modular). There is a single
output channel of line-level audio for connection to the
AIC (Audio Input Card).

The ALCC adds system-wide live emergency paging
capability to networked XLS/Desigo Fire Safety
Modular/Cerberus PRO Modular Voice systems as well
as an all-call function for XLS/Desigo Fire Safety
Modular/Cerberus PRO Modular-based MXL/XLS/
Desigo Fire Safety Modular/Cerberus PRO Modular
hybrid systems. Located on the receiving end in up to
63 remote XLS/Desigo Fire Safety Modular/Cerberus
PRO Modular nodes, the ALCC converts the audio
signal generated by the amplifiers located in the
primary and secondary paging stations into a form that
is compatible with AICs located in the remote stations.

The ALCC is transparent to the host system. As such, it
supports all styles of wiring supported by ZAC-40 (XLS/
Desigo Fire Safety Modular/Cerberus PRO Modular) as
well as ZAC-30 (MXL) amplifiers. It provides supervision
by constantly monitoring its two audio channels,
reporting faults both visually and through the down-
stream AIC. Furthermore, the ALCC contains audio
detection and channel selection circuitry that prioritizes
incoming audio, enables the appropriate channel,
closes the AIC audio active contact, or cuts the output
of the ALCC to generate an AIC trouble, depending on
the presence of incoming audio or circuit faults. Finally,
all XLS/Desigo Fire Safety Modular/Cerberus PRO
Modular functions are configured in the Zeus program-
ming tool via standard logic functions with no need for
special software or hardware upgrades.

Two isolated audio channels, 70VRMS input from ZAC-30 (MXL) or ZAC-40
(XLS/Desigo Fire Safety Modular/Cerberus PRO Modular) amplifiers.

Single channel output to the AIC, 0.775VRMS.

±6dBu output adjustment capability, independent for each channel.

Up to 63 ALCCs on a single audio riser.

PRIMARY SELECTED

SECNDRY SELECTED

POWER

ALCC

FAULT TEST

GAIN

_

+

ACTIVE

FAULT

SECONDARY

CHANNEL

FAULT TEST

GAIN

ACTIVE

FAULT

PRIMARY

CHANNEL

_

+

Figure 1

ALCC Speaker Line

Output Card

Features

Summary of Contents for ALCC

Page 1: ... located in the primary and secondary paging stations into a form that is compatible with AICs located in the remote stations The ALCC is transparent to the host system As such it supports all styles of wiring supported by ZAC 40 XLS Desigo Fire Safety Modular Cerberus PRO Modular as well as ZAC 30 MXL amplifiers It provides supervision by constantly monitoring its two audio channels reporting fau...

Page 2: ... Safety Modular Cerberus PRO Modular system The ALCC contains no digital circuitry and integrates seamlessly into the existing XLS Desigo Fire Safety Modular Cerberus PRO Modular framework as it is com pletely transparent to the overlying system structure Refer to the ALCC Usage Restrictions on page 8 Controls and Indicators The following table contains a description of LED indicators visible thro...

Page 3: ...stalled To connect external wiring 1 Loosen the screw of the terminal by turning it counterclockwise 2 Insert the wire into the side of the terminal block 3 Tighten the screw of the terminal block by turning it clockwise For all versions of Zeus earlier than 7 0 the ALCC is not an option under CC 5 or CC 2 As a result such proper ties as card cage slot availability and battery power supply current...

Page 4: ... or ZAM 180 LED switch LED VSM 1 LED switch LED ACM 1 not required for global paging from an MXLV head end XNET ZAC 40 DAC NET NIC C SCM 8 ALCC LVM ALCC NIC C DAC NET AIC AUDIO AUDIO PRESENT AIC CONTACT XLSV Desigo Fire Safety Modular Cerberus PRO Modular MXLV XLSVR Desigo Fire Safety Modular Cerberus PRO Modular NIC C ZAC 40 or ZAM 180 LED switch LED LVM MMM 1 NIM 1W NIC C DAC NET HNET HNET LED L...

Page 5: ...igo Fire Safety Modular Cerberus PRO Modular PRIMARY AUDIO RISER 1 ZAC 40 ZAC 40 ZAC 40 ZAC 40 PRIMARY AUDIO RISER 2 SECONDARY AUDIO RISER 1 SECONDARY AUDIO RISER 2 ALCC ALCC AIC SECONDARY RISER AUDIO SECONDARY PRESENT CONTACT PRIMARY RISER AUDIO PRIMARY PRESENT CONTACT REMOTE PAGING STATION XLSV Desigo Fire Safety Modular Cerberus PRO Modular XLSV Desigo Fire Safety Modular Cerberus PRO Modular F...

Page 6: ... capacitance is 0 33 μF Line to Line 0 66 μF Line to Ground max for each audio riser 6 Parallel wiring T tapping is not allowed 7 All ALCC audio riser wiring is rated power limited and should be wired in accordance with applicable codes 8 The ALCC supports both Class A and Class B audio riser wiring Refer to Figure 6 for details Figure 5 outlines the input and output connections of the ALCC and th...

Page 7: ...50263 3 7 Figure 6 ALCC Class A and Class B Wiring Diagram GLOBAL PAGING STATION CLASS A EOLR 68k OHMS ZAC 40 XLS Desigo Fire Safety Modular Cerberus PRO Modular or ZAC 30 MXL CLASS B EOLR 68k OHMS CLASS A ONLY AUDIO RISER CLASS A and CLASS B LAST ALCC FIRST ALCC ...

Page 8: ...is limited at 160W For ULC approved product the following usage restrictions apply a The maximum power of the ZAM 180 amplifier using the ZAC 40 XLS Desigo Fire Safety Modular Cerberus PRO Modular as the ALCC paging source is limited at 165W b The ZAC 30 MXL is not allowed as the ALCC paging source Document ID A6V10248630 Cyber security disclaimer Siemens products and solutions provide security fu...

Reviews: