Installation Instructions 

Document No. 588-097  

Rev. 1, July, 2002 

 

TTL/RS-485 Interface 

 

 

 

Page 1 of 2 

Product Description 

The TTL/RS-485 Interface is a TTL to RS-485 trunk 
interface. It converts two-wire TTL level signals into 
RS-485 signals for the network controller. No 
internal settings are required for communication 
speed (bps). The TTL/RS-485 Interface operates at 
any required trunk speed. The TTL/RS-485 Interface 
is supplied with a 120 Vac Hz wall plug-in power 
pack with a 6-foot (1.8 meter) CD power cord. 

 

CAUTION: 

Use only the plug-in transformer shipped 
with this device. 

 

Product Numbers 

538-907 

TTL/RS-485 Interface 115V 

 

Required Tools 

• 

Flat-blade screwdriver (1/8 inch blade width) 

• 

Wire strippers 
 

 

CAUTION: 

Always wear an electro-static discharge 
wrist strap and discharge accumulated 
static before touching field panel 
components. 

 

Expected Installation Time 

20 minutes 

Prerequisites 

 

To comply with installations requiring 
Class 1 conduit connections, you may 
mount the TTL/RS-485 Interface in a field 
panel enclosure. 

For Console Top Installation 

• 

TTL source device in place; TTL cable 
assembled and connected to source device 

• 

Source of transient protected 120 Vac 60 
Hz available 

• 

Network controller installed and tested 

For Wall-mounted Enclosure 

• 

Enclosure mounted 

• 

Transient protected outlet installed 

• 

Network controller installed and tested 

 

Installation 

1. 

Connect the TTL cable between the RS-485 
Interface and the TTL source device. See the 
TTL Interface side of the TTL/RS-485 Interface 
for circuit polarity.  

2. 

Maintain proper fit. If the TTL trunk contains a 
shield, cut it flush with the cable jacket or tape it 
back. 

3. 

Connect the RS-485 Interface terminals to the 
network controller.  

4. 

Maintain polarity between the network controller 
and the RS-485 connections. The shield should 
be landed on the network controller, but taped 
back at the RS-485 Interface connections. 

The network controller installation is now complete. 