background image

Model : Premium (Compact / Energy Efficiency) Type

Standard Type

VRF

Technical 

Data Book

DVM S for Europe 

(R410A, 50Hz, HP)

Summary of Contents for AM080JXVHGH/EU

Page 1: ...Model Premium Compact Energy Efficiency Type Standard Type VRF Technical Data Book DVM S forEurope R410A 50Hz HP ...

Page 2: ...Spec for Modules At cooling mode P 15 to 58 16 01 06 Ver 1 2 Modify Electric Diagram Mapping For AM160KXVGGH Model P 65 to 66 Line up Name Standard Premium Compact High Effi Premium High Efficiency P 4 5 16 01 13 Ver 2 0 Update all contents including installation 16 07 07 Ver 2 01 Modify the Accessory Compatibility table for MCU kit P163 17 09 13 ...

Page 3: ... Outdoor Unit N Indoor Unit 5 Feature 1 V Inverter M DVM S Eco 6 Feature 2 A Standard General Temp Module H High EER Low Temp Module G High EER General Temp Module 7 Rating Voltage E 1Ø 220 240V 50Hz G 3Ø 380 415V 50Hz 8 Mode H Heat Pump R Heat Recovery Nomenclature OutdoorUnit Model Name 1 2 3 4 5 6 7 8 Buyer ...

Page 4: ...tial buildings Samsung DVM S offers innovative features to benefit the indoor comfort as well operational coasts of the system through technological advances such as The world s largest capacity Capacities of the outdoor units offer up to 30 HP rooftop space savings as well as lowering the installations and transportation costs High seasonal energy efficiency Samsung DVM S adopts a dual inverter s...

Page 5: ...ansfer process Extended Piping Length Limits Allows extended piping length of up to 220 m and units will still give a great performance overwide areas With this technology installation is available with a maximum height level of 110 m which is equivalent to 20 stories each story is considered 5 m high Smart management Further improves system s energy efficiency due to precise indoor climate contro...

Page 6: ... 7 2 Specifications 15 3 Electrical Characteristics 95 4 Dimensional drawing 98 5 Center of gravity 101 6 Electrical wiring diagrams 104 7 Sound Data 106 8 Operation range 120 9 Piping diagram 122 10 Installation 129 11 Accessory 156 ...

Page 7: ...U 3 1 1 1 78HP AM780KXVGGH1EU 3 1 1 1 80HP AM800KXVGGH1EU 3 1 1 1 82HP AM820KXVGGH1EU 3 1 2 84HP AM840KXVGGH1EU 3 1 2 86HP AM860KXVGGH1EU 3 1 2 88HP AM880KXVGGH1EU 3 1 2 90HP AM900KXVGGH1EU 3 3 NOTE Make sure to use an indoor unit that is compatible with DVM S Indoor units can be connected within the range indicated in following table If the total capacity of the connected indoor units exceeds the...

Page 8: ...VGGH2EU 4 2 2 78HP AM780KXVGGH2EU 4 1 3 80HP AM800KXVGGH2EU 4 3 1 82HP AM820KXVGGH2EU 4 2 1 1 84HP AM840KXVGGH2EU 4 1 2 1 86HP AM860KXVGGH2EU 4 1 1 1 1 88HP AM880KXVGGH2EU 4 1 1 1 1 90HP AM900KXVGGH2EU 4 1 1 2 NOTE Make sure to use an indoor unit that is compatible with DVM S Indoor units can be connected within the range indicated in following table If the total capacity of the connected indoor u...

Page 9: ... 1 1 78HP AM780KXVAGH EU 3 1 1 1 80HP AM800KXVAGH EU 3 1 1 1 82HP AM820KXVAGH EU 3 1 2 84HP AM840KXVAGH EU 3 1 2 86HP AM860KXVAGH EU 3 1 2 88HP AM880KXVAGH EU 3 1 2 90HP AM900KXVAGH EU 3 3 NOTE Make sure to use an indoor unit that is compatible with DVM S Indoor units can be connected within the range indicated in following table If the total capacity of the connected indoor units exceeds the indi...

Page 10: ... 1 5 1 7 2 2 2 8 3 2 3 6 4 5 5 6 6 0 7 1 8 2 9 0 11 2 12 8 14 0 16 0 1Way CST JSF 0 JSF 1 JSF 2 2Way CST 4Way CST 360 CST Floor Standing Unit 4Way CST S 600X600 Duct S MSP Slim Duct MSP Duct Ceiling Console Boracay Boracay with EEV AR5000 AR5000 with EEV ...

Page 11: ...ng capacity of the indoor unit may decrease Total capacity of the connected indoor units can be allowed from 50 to 130 of the total outdoor unit capacity 0 5 Σ Outdoor unit capacity Total capacity of the connected indoor units 1 3 Σ Outdoor unit capacity You can connect maximum 64 indoor units to the outdoor unit Maximum quantity of connectable indoor unit is set to 64 since outdoor unit only supp...

Page 12: ...M320KXVGGH1EU AM340KXVGGH1EU 36 38 40 42 AM360KXVGGH1EU AM380KXVGGH1EU AM400KXVGGH1EU AM420KXVGGH1EU 44 46 48 50 52 AM440KXVGGH1EU AM460KXVGGH1EU AM480KXVGGH1EU AM500KXVGGH1EU AM520KXVGGH1EU 54 56 58 60 AM540KXVGGH1EU AM560KXVGGH1EU AM580KXVGGH1EU AM600KXVGGH1EU 62 64 AM620KXVGGH1EU AM640KXVGGH1EU 66 68 70 72 74 AM660KXVGGH1EU AM680KXVGGH1EU AM700KXVGGH1EU AM720KXVGGH1EU AM740KXVGGH1EU 76 78 80 82...

Page 13: ... 36 38 AM320KXVGGH2EU AM360KXVGGH2EU AM380KXVGGH2EU 34 AM340KXVGGH2EU 40 42 44 46 48 AM400KXVGGH2EU AM420KXVGGH2EU AM440KXVGGH2EU AM460KXVGGH2EU AM480KXVGGH2EU 50 AM500KXVGGH2EU 52 54 56 AM520KXVGGH2EU AM540KXVGGH2EU AM560KXVGGH2EU 58 AM580KXVGGH2EU 60 AM600KXVGGH2EU 62 64 66 AM620KXVGGH2EU AM640KXVGGH2EU AM660KXVGGH2EU 68 72 74 76 78 AM680KXVGGH2EU AM720KXVGGH2EU AM740KXVGGH2EU AM760KXVGGH2EU AM7...

Page 14: ...0KXVAGH EU AM340KXVAGH EU 36 38 40 42 44 AM360KXVAGH EU AM380KXVAGH EU AM400KXVAGH EU AM420KXVAGH EU AM440KXVAGH EU 46 48 50 52 AM460KXVAGH EU AM480KXVAGH EU AM500KXVAGH EU AM520KXVAGH EU 54 56 58 60 AM540KXVAGH EU AM560KXVAGH EU AM580KXVAGH EU AM600KXVAGH EU 62 64 AM620KXVAGH EU AM640KXVAGH EU 66 68 70 72 74 AM660KXVAGH EU AM680KXVAGH EU AM700KXVAGH EU AM720KXVAGH EU AM740KXVAGH EU 76 78 80 82 AM...

Page 15: ... Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB052FAVBSG x1 DS GB066FAVBSG x1 DS GB066FAVBSG x1 Output kW x n 5 18 x1 6 39 x1 6 39 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 1 100 x1 1 100 x1 Fan Type Propeller Propeller Propeller Discharge direction Top Top Top Qu...

Page 16: ...capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20uPa 4 These products contain R410A which is fluorinated green...

Page 17: ...ate Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x1 DS4GJ5080FVA x1 DS GB066FAVB x 2 Output kW x n 6 39 x1 7 81 x1 6 39 x 2 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 1 400 x1 1 100 x 2 Fan Type Propeller Propeller Propeller Discharge direction Top Top Top Qu...

Page 18: ... unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20uPa 4 These products contain R410A which is fluorinated...

Page 19: ...e Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 2 DS GB066FAVB x 2 DS GB070FAVA x 2 Output kW x n 6 39 x 2 6 39 x 2 6 76 x 2 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x 2 1 100 x 2 1 100 x 2 Fan Type Propeller Propeller Propeller Discharge direction Top Top To...

Page 20: ...r unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20uPa 4 These products contain R410A which is fluorinate...

Page 21: ...ate Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS4GJ5080FVA x 2 DS4GJ5080FVA x 2 DS4GJ5080FVA x 2 Output kW x n 7 81 x 2 7 81 x 2 7 81 x 2 Oil Type PVE PVE PVE Initial charge cc x n 1 400 x 2 1 400 x 2 1 400 x 2 Fan Type Propeller Propeller Propeller Discharge direction Top Top ...

Page 22: ...or unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20uPa 4 These products contain R410A which is fluorinat...

Page 23: ... Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 2 DSGB066FAVBSG x1 DS GB066FAVB x 2 DSGB066FAVBSG x1 DS GB066FAVB x 3 Output kW x n 6 39 x1 x1 6 39 x 2 x1 6 39 x1 x1 6 39 x 2 x1 6 39 x1 x1 6 39 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x1 1 100 x 2 x1 1 100 x1 x1 1 100 x 2 x1 1 100 x1 x1 1 100 x 2 x1 Fan Type ...

Page 24: ... C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pres...

Page 25: ...eat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS4GJ5080FVA x1 DSGB066FAVB x 2 DS GB066FAVB x 4 DS GB066FAVB x 4 Output kW x n 7 81 x1 x1 6 39 x 2 x1 6 39 x 2 x 2 6 39 x 2 x 2 Oil Type PVE PVE PVE Initial charge cc x n 1 400 x1 x1 1 100 x 2 x1 1 100 x 2 x 2 1 100 x 2 x 2 Fan Type Pro...

Page 26: ...nation ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20uPa 4 These produ...

Page 27: ...aterial Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x1 DS4GJ5080FVA x 2 DS4GJ5080FVA x 3 DS GB066FAVB x 2 DS4GJ5080FVA x 2 Output kW x n 6 39 x1 x1 7 81 x 2 x1 7 81 x1 x1 7 81 x 2 x1 6 39 x 2 x1 7 81 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x1 1 400 x 2 x1 1 400 x1 x1 1 400 x 2 x1 1 100 x 2 x1 1 400 x 2 ...

Page 28: ...ating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation conditio...

Page 29: ...erial Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 2 DS4GJ5080FVA x 2 DS GB066FAVB x 2 DS4GJ5080FVA x 2 DS GB070FAVA x 2 DS4GJ5080FVA x 2 Output kW x n 6 39 x 2 x1 7 81 x 2 x1 6 39 x 2 x1 7 81 x 2 x1 6 76 x 2 x1 7 81 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x 2 x1 1 400 x 2 x1 1 100 x 2 x1 1 400 x 2 x1 1 1...

Page 30: ... 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound p...

Page 31: ...Plate EGI Steel Plate Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS4GJ5080FVA x 4 DS4GJ5080FVA x 4 DS4GJ5080FVA x 4 Output kW x n 7 81 x 2 x 2 7 81 x 2 x 2 7 81 x 2 x 2 Oil Type PVE PVE PVE Initial charge cc x n 1 400 x 2 x 2 1 400 x 2 x 2 1 400 x 2 x 2 Fan Type Propeller Propel...

Page 32: ... ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20uPa 4 These products co...

Page 33: ...n Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 2 DS4GJ5080FVAx 2 DSGB066FAVBSG x1 DS GB066FAVB x 2 DS4GJ5080FVAx 2 DSGB066FAVBSG x1 DS GB066FAVB x 3 DS4GJ5080FVAx 2 Output kW x n 6 39x1 x1 6 39x2 x1 7 81x2 x1 6 39x1 x1 6 39x2 x1 7 81x2 x1 6 39x1 x1 6 39x2 x1 7 81x2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x1 1 100 x 2 x1 1 400 x 2 x1 1 100 x1 x1 1 100 x 2 x1 1 4...

Page 34: ...ling Indoor temperature 27 C DB 19 C WB Outdoor temperature 35 C DB 24 C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoust...

Page 35: ... Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS4GJ5080FVA x 3 DSGB066FAVB x 2 DS GB066FAVB x 4 DS4GJ5080FVA x 2 DS GB066FAVB x 4 DS4GJ5080FVA x 2 Output kW x n 7 81 x1 x1 6 39 x 2 x1 7 81 x 2 x1 6 39 x 2 x 2 7 81 x 2 x1 6 39 x 2 x 2 7 81 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 400 x1 x1 1 100 x 2 x1 1 400 x 2 x1 1 100 x 2 ...

Page 36: ...C DB 24 C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on ope...

Page 37: ...l Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 4 DS4GJ5080FVAx 2 DS GB066FAVB x 2 DSGB070FAVAx 2 DS4GJ5080FVAx 2 DS GB066FAVB x 2 DS4GJ5080FVAx 4 Output kW x n 6 39 x 2 x 2 7 81 x 2 x1 6 76 x 2 x1 6 39 x 2 x1 7 81 x 2 x1 7 81 x 2 x1 6 39 x 2 x1 7 81 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100x2 x2 1 400x2 x1 1 100x2 x2 1 ...

Page 38: ...ndoor temperature 27 C DB 19 C WB Outdoor temperature 35 C DB 24 C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic env...

Page 39: ...n Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 2 DS4GJ5080FVAx 4 DS GB066FAVB x 2 DS4GJ5080FVAx 4 DS GB070FAVAx 2 DS4GJ5080FVAx 4 Output kW x n 7 81x2 x1 6 39x2 x1 7 81x2 x1 7 81x2 x1 6 39x2 x1 7 81x2 x1 6 76x2 x1 7 81x2 x2 Oil Type PVE PVE PVE Initial charge cc x n 1 400 x 2 x1 1 100 x 2 x1 1 400 x 2 x1 1 400 x 2 x1 1 100 x...

Page 40: ... 19 C WB Outdoor temperature 35 C DB 24 C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure l...

Page 41: ...e EGI Steel Plate EGI Steel Plate EGI Steel Plate Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS4GJ5080FVAx 6 DS4GJ5080FVAx 6 DS4GJ5080FVAx 6 Output kW x n 7 81 x 2 x 3 7 81 x 2 x 3 7 81 x 2 x 3 Oil Type PVE PVE PVE Initial charge cc x n 1 400 x 2 x 3 1 400 x 2 x 3 1 400 x 2 x 3 ...

Page 42: ... ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20uPa 4 These products co...

Page 43: ... Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVBSG x 2 DS GB066FAVBSG x 2 DS GB066FAVB x 2 DSGB052FAVBSG x1 Output kW x n 6 39 x1 x 2 6 39 x1 x 2 5 18 x1 x1 6 39 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x 2 1 100 x1 x 2 1 100 x1 x1 1 100 x 2 x1 Fan Type Propeller Prop...

Page 44: ...WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 2...

Page 45: ...l Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 2 DSGB052FAVBSG x1 DS GB066FAVB x 2 DSGB066FAVBSG x1 DS GB066FAVB x 3 Output kW x n 5 18 x1 x1 6 39 x 2 x1 6 39 x1 x1 6 39 x 2 x1 6 39 x1 x1 6 39 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x1 1 100 x 2 x1 1 100 x1 x1 1 100 x 2 x1 1 100 x1 x1 1 100 x 2 x1 Fan ...

Page 46: ... C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pres...

Page 47: ... Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 2 DSGB052FAVBSG x 2 DS GB066FAVB x 4 DS GB066FAVB x 4 Output kW x n 5 18 x1 x 2 6 39 x 2 x1 6 39 x 2 x 2 6 39 x 2 x 2 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x 2 1 100 x 2 x1 1 100 x 2 x 2 1 100 x 2 x 2 Fan T...

Page 48: ...DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure...

Page 49: ...e Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 3 DSGB052FAVBSG x1 DS GB066FAVB x 3 DSGB052FAVBSG x1 DS GB066FAVB x 4 DSGB052FAVBSG x1 Output kW x n 5 18 x1 x1 6 39 x1 x1 6 39 x 2 x1 5 18 x1 x1 6 39 x1 x1 6 39 x 2 x1 5 18 x1 x1 6 39 x 2 x 2 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x 2 1 100 x 2 x1 1 100 x1 x 2 1 100 x 2 x1 1 100...

Page 50: ...ure 35 C DB 24 C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending...

Page 51: ...be Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 4 DSGB052FAVBSG x1 DS GB066FAVB x 4 DSGB052FAVBSG x1 DS GB066FAVB x 5 Output kW x n 5 18 x1 x1 6 39 x 2 x 2 5 18 x1 x1 6 39 x 2 x 2 6 39 x1 x1 6 39 x 2 x 2 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x1 1 100 x 2 x 2 1 100 x1 x1 1 100 x 2 x 2 1 100...

Page 52: ...ture 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sou...

Page 53: ...rosion Anti corrosion Compressor Model Name DS GB066FAVB x 2 DS4GJ5080FVA x 2 DSGB052FAVBSG x1 DS GB066FAVB x 2 DS4GJ5080FVA x 2 DSGB052FAVBSG x1 DS GB066FAVB x 2 DS4GJ5080FVA x 2 DSGB066FAVBSG x1 Output kW x n 5 18x1 x1 6 39x2 x1 7 81x2 x1 5 18x1 x1 6 39x2 x1 7 81x2 x1 6 39x1 x1 6 39x2 x1 7 81x2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x1 1 100 x 2 x1 1 400 x 2 x1 1 100 x1 x1 1 100 ...

Page 54: ... differences 0m Cooling Indoor temperature 27 C DB 19 C WB Outdoor temperature 35 C DB 24 C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the ...

Page 55: ... Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB070FAVA x 2 DS4GJ5080FVA x 2 DSGB052FAVBSG x1 DS GB066FAVB x 4 DSGB070FAVA x 2 DS GB066FAVB x 6 DSGB052FAVBSG x1 Output kW x n 5 18x1 x1 6 76x2 x1 7 81x2 x1 6 39x2 x2 6 76x2 x1 5 18x1 x1 6 39x2 x3 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x1 1 100 x 2 x1 1 400 x...

Page 56: ... 24 C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operati...

Page 57: ...anger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 6 DSGB052FAVBSG x1 DS GB066FAVB x 6 DSGB066FAVBSG x1 DS GB066FAVB x 7 Output kW x n 5 18 x1 x1 6 39 x 2 x 3 6 39 x1 x1 6 39 x 2 x 3 6 39 x1 x1 6 39 x 2 x 3 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x1 1 100 x 2 x 3 1 100...

Page 58: ...ture 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sou...

Page 59: ...e EGI Steel Plate Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 4 DS4GJ5080FVA x 2 DSGB052FAVBSG x1 DS GB066FAVB x 8 DS GB066FAVB x 8 Output kW x n 5 18x1 x1 6 39x2 x2 7 81x2 x1 6 39 x 2 x 4 6 39 x 2 x 4 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x1 1 100 x ...

Page 60: ...DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressur...

Page 61: ... EGI Steel Plate EGI Steel Plate EGI Steel Plate Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 8 DS GB066FAVB x 8 DS GB066FAVB x 6 DS4GJ5080FVA x 2 Output kW x n 6 39 x 2 x 4 6 39 x 2 x 4 6 39 x 2 x 3 7 81 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x 2 x...

Page 62: ...C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressu...

Page 63: ...anger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 6 DS4GJ5080FVA x 2 DS GB066FAVB x 6 DS4GJ5080FVA x 2 DS GB066FAVB x 6 DS4GJ5080FVA x 2 Output kW x n 6 39 x 2 x 3 7 81 x 2 x1 6 39 x 2 x 3 7 81 x 2 x1 6 39 x 2 x 3 7 81 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x 2 x...

Page 64: ...C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation c...

Page 65: ...eel Plate Heat Exchanger Type Fin Tube Fin Tube Material Fin Al Al Tube Cu Cu Fin Treatment Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 4 DSGB070FAVA x 2 DS4GJ5080FVA x 2 DS GB066FAVB x 4 DS4GJ5080FVA x 4 Output kW x n 6 39 x 2 x 2 6 76 x 2 x1 7 81 x 2 x1 6 39 x 2 x 2 7 81 x 2 x 2 Oil Type PVE PVE Initial charge cc x n 1 100 x 2 x 3 1 400 x 2 x1 1 100 x 2 x 2 1 400 x 2 x 2 F...

Page 66: ... combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20uPa 4 These...

Page 67: ...ate Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GA046FAVADO x1 DS GB066FAVB x1 DS GB066FAVB x1 Output kW x n 4 39 x1 6 39 x1 6 39 x1 Oil Type PVE PVE PVE Initial charge cc x n 900 x1 1 100 x1 1 100 x1 Fan Type Propeller Propeller Propeller Discharge direction Top Top Top Quant...

Page 68: ...capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20uPa 4 These products contain R410A which is fluorinated green...

Page 69: ...late Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x1 DS4GJ5080FVA x1 DS4GJ5080FVA x1 Output kW x n 6 39 x1 7 81 x1 7 81 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 1 400 x1 1 400 x1 Fan Type Propeller Propeller Propeller Discharge direction Top Top Top Quan...

Page 70: ... unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20uPa 4 These products contain R410A which is fluorinated...

Page 71: ... Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB052FAVB x 2 DS GB066FAVB x 2 DS GB066FAVB x 2 Output kW x n 6 39 x 2 6 39 x 2 6 39 x 2 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x 2 1 100 x 2 1 100 x 2 Fan Type Propeller Propeller Propeller Discharge direction Top Top Top...

Page 72: ...r unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20uPa 4 These products contain R410A which is fluorinate...

Page 73: ...te Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 2 DS GB070FAVA x 2 DS4GJ5080FVA x 2 Output kW x n 6 39 x 2 6 76 x 2 7 81 x 2 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x 2 1 100 x 2 1 400 x 2 Fan Type Propeller Propeller Propeller Discharge direction Top Top T...

Page 74: ...or unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20uPa 4 These products contain R410A which is fluorinat...

Page 75: ...Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 3 DS GB066FAVB x 3 DS GB066FAVB x 3 Output kW x n 6 39 x1 x1 6 39 x 2 x1 6 39 x1 x1 6 39 x 2 x1 6 39 x1 x1 6 39 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x1 1 100 x 2 x1 1 100 x1 x1 1 100 x 2 x1 1 100 x1 x1 1 100 x 2 x1 Fan Type Propeller Propell...

Page 76: ... C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pres...

Page 77: ...be Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS4GJ5080FVA x1 DSGB066FAVB x 2 DS4GJ5080FVA x1 DSGB066FAVB x 2 DS GB052FAVBx2 DSGB066FAVBx2 Output kW x n 7 81 x1 x1 6 39 x 2 x1 7 81 x1 x1 6 39 x 2 x1 6 39 x 2 x 2 Oil Type PVE PVE PVE Initial charge cc x n 1 400 x1 x1 1 100 x 2 x1 1 400 x1 x1 1 100 x 2 x1 1 1...

Page 78: ... 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20u...

Page 79: ...er Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVBx4 DS4GJ5080FVA x 3 DS4GJ5080FVA x 3 Output kW x n 6 39 x 2 x 2 7 81 x1 x1 7 81 x 2 x1 7 81 x1 x1 7 81 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x 2 x 2 1 400 x1 x1 1 400 x 2 x1 1 400 x1 x1 1 400 x 2 x1 Fan Type Propeller ...

Page 80: ...15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure l...

Page 81: ...rial Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB052FAVB x 2 DS4GJ5080FVA x 2 DS GB066FAVB x 2 DS4GJ5080FVA x 2 DS GB066FAVB x 2 DS4GJ5080FVA x 2 Output kW x n 6 39 x 2 x1 7 81 x 2 x1 6 39 x 2 x1 7 81 x 2 x1 6 39 x 2 x1 7 81 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x 2 x1 1 400 x 2 x1 1 100 x 2 x1 1 400 x 2 x1 1 10...

Page 82: ...ure 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted soun...

Page 83: ... Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 2 DS4GJ5080FVA x 2 DS GB070FAVA x 2 DS4GJ5080FVA x 2 DS4GJ5080FVA x 4 Output kW x n 6 39 x 2 x1 7 81 x 2 x1 6 76 x 2 x1 7 81 x 2 x1 7 81 x 2 x 2 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x 2 x1 1 400 x 2 x1 1 100 x 2 x1 1 400 x 2 x1 ...

Page 84: ...Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20uPa ...

Page 85: ...corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 3 DS4GJ5080FVA x 2 DS GB066FAVB x 3 DS4GJ5080FVA x 2 DS GB066FAVB x 3 DS4GJ5080FVA x 2 Output kW x n 6 39 x1 x1 6 39 x 2 x1 7 81 x 2 x1 6 39 x1 x1 6 39 x 2 x1 7 81 x 2 x1 6 39 x1 x1 6 39 x 2 x1 7 81 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x1 x1 1 100 x 2 x1 1 400 x 2 x1 1 100 x1 x1 1 100 x 2 x1 1 400 x 2 x...

Page 86: ...ling Indoor temperature 27 C DB 19 C WB Outdoor temperature 35 C DB 24 C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoust...

Page 87: ...Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS4GJ5080FVA x 3 DSGB066FAVB x 2 DS4GJ5080FVA x 3 DSGB066FAVB x 2 DS GB052FAVB x 2 DSGB066FAVB x 2 DS4GJ5080FVA x 2 Output kW x n 7 81x1 x1 6 39x2 x1 7 81x2 x1 7 81x1 x1 6 39x2 x1 7 81x2 x1 6 39 x 2 x 2 7 81 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 400 x1 x1 1 100 x 2 x1 1 400 x 2 x1 1 400 x1 ...

Page 88: ... temperature 35 C DB 24 C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ ...

Page 89: ...in Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 4 DS4GJ5080FVA x 2 DS GB066FAVB x 4 DS4GJ5080FVA x 2 DS GB066FAVB x 4 DS4GJ5080FVA x 2 Output kW x n 6 39 x 2 x 2 7 81 x 2 x1 6 39 x 2 x 2 7 81 x 2 x1 6 39 x 2 x 2 7 81 x 2 x1 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x 2 x 2 1 400 x 2 x1 1 100 x 2 x 2 ...

Page 90: ...temperature 35 C DB 24 C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ d...

Page 91: ...e Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 2 DSGB070FAVA x 2 DS4GJ5080FVA x 2 DS GB066FAVB x 2 DS4GJ5080FVA x 4 DS GB066FAVB x 2 DS4GJ5080FVA x 4 Output kW x n 6 39 x 2 x1 6 76 x 2 x1 7 81 x 2 x1 6 39 x 2 x1 7 81 x 2 x 2 6 39 x 2 x1 7 81 x 2 x 2 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x 2 x 2 1 400 ...

Page 92: ...Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA ...

Page 93: ...late Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu Fin Treatment Anti corrosion Anti corrosion Anti corrosion Compressor Model Name DS GB066FAVB x 2 DS4GJ5080FVA x 4 DS GB070FAVA x 2 DS4GJ5080FVA x 4 DS4GJ5080FVA x 6 Output kW x n 6 39 x 2 x1 7 81 x 2 x 2 6 76 x 2 x1 7 81 x 2 x 2 7 81 x 2 x 3 Oil Type PVE PVE PVE Initial charge cc x n 1 100 x 2 x1 1 400 x 2 x 2...

Page 94: ... 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20u...

Page 95: ...5 3 2 48 7 6 44 123 20 AM440KXVGGH1EU 50 380 415 342 456 50 70 48 40 98 0 125 0 107 8 2 48 7 6 46 128 80 AM460KXVGGH1EU 50 380 415 342 456 53 90 50 20 105 0 125 0 115 5 2 48 7 6 48 134 40 AM480KXVGGH1EU 50 380 415 342 456 53 50 49 90 112 2 125 0 123 4 2 48 7 6 50 140 00 AM500KXVGGH1EU 50 380 415 342 456 56 40 53 50 115 0 150 0 126 5 2 48 7 6 52 145 60 AM520KXVGGH1EU 50 380 415 342 456 61 70 58 40 ...

Page 96: ... 0 99 2 3 31 10 0 44 123 20 AM440KXVGGH2EU 50 380 415 342 456 41 60 41 20 96 4 125 0 99 2 3 31 10 0 46 128 80 AM460KXVGGH2EU 50 380 415 342 456 44 50 44 80 99 2 125 0 124 0 3 31 10 0 48 134 40 AM480KXVGGH2EU 50 380 415 342 456 47 40 48 40 102 0 125 0 124 0 3 31 10 0 50 140 00 AM500KXVGGH2EU 50 380 415 342 456 48 50 49 20 103 4 125 0 124 0 3 72 11 4 52 145 60 AM520KXVGGH2EU 50 380 415 342 456 52 30...

Page 97: ... 2 48 7 6 44 123 20 AM440KXVAGH EU 50 380 415 342 456 55 60 53 60 89 2 100 0 93 7 2 48 7 6 46 128 80 AM460KXVAGH EU 50 380 415 342 456 55 80 51 60 105 0 125 0 110 3 2 48 7 6 48 134 40 AM480KXVAGH EU 50 380 415 342 456 56 60 52 10 112 2 125 0 117 8 2 48 7 6 50 140 00 AM500KXVAGH EU 50 380 415 342 456 59 10 55 30 115 0 150 0 120 8 2 48 7 6 52 145 60 AM520KXVAGH EU 50 380 415 342 456 64 20 59 80 117 ...

Page 98: ...33 4 55 21 4 1695 5 6 3 4 115 4 1 2 74 3 653 2 1 3 4 89 31 2 202 8 803 2 7 1 2 90 3 1 2 95 3 3 4 40 1 1 2 4 20 x 12 SLOT HOLE Foundation bolt holes Pitch of foundation bolt holes Pitch of foundation bolt holes 765 2 6 Units mm inches NO Table of descriptions NO Table of descriptions 1 Gas Ref pipe See note 4 5 Powerwiring conduit Φ22 2 Liquid Ref pipe See note 4 6 Communication wiring conduit Φ44 ...

Page 99: ... 2 1 2 47 1 3 4 107 4 1 4 95 33 4 55 21 4 40 1 1 2 179 7 115 4 1 2 4 20 x 12 SLOT HOLE Foundation bolt holes Pitch of foundation bolt holes Pitch of foundation bolt holes 625 2 1 2 75 3 87 31 2 55 21 4 616 2 1 4 65 2 1 2 107 4 1 4 803 2 7 1 2 765 2 6 Units mm inches NO Table of descriptions NO Table of descriptions 1 Gas Ref pipe See note 4 5 Powerwiring conduit Φ22 2 Liquid Ref pipe See note 4 6 ...

Page 100: ...241 9 1 2 115 4 1 2 179 7 1795 5 10 3 4 88 3 1 2 86 3 1 4 86 31 4 156 6 1 4 243 9 1 2 4 20 x 12 SLOT HOLE Foundation bolt holes Pitch of foundation bolt holes Pitch of foundation bolt holes 765 2 6 Units mm inches NO Table of descriptions NO Table of descriptions 1 Gas Ref pipe See note 4 4 Communication wiring conduit Φ44 2 Liquid Ref pipe See note 4 5 Knock out Hole for Ref Piping bottom 3 Power...

Page 101: ...GH EU AM100JXVHGH EU AM120JXVHGH EU AM080JXVAGH EU AM100JXVAGH EU AM120JXVAGH EU 761 2 6 740 2 5 1695 5 6 3 4 A C B Units mm inches Model A B C AM120 361 1 3 4 455 1 6 560 1 10 AM100 336 1 1 1 4 455 1 6 560 1 10 AM080 336 1 1 1 4 455 1 6 560 1 10 ...

Page 102: ...M160KXVAGH EU AM180KXVAGH EU AM200KXVAGH EU AM220KXVAGH EU 1695 5 6 3 4 761 2 6 1150 3 9 1 4 B A C Units mm inches Model A B C AM220 336 1 1 1 4 654 2 1 3 4 620 2 1 2 AM200 336 1 1 1 4 654 2 1 3 4 620 2 1 2 AM180 336 1 1 1 4 654 2 1 3 4 620 2 1 2 AM160 367 1 2 1 2 656 2 1 3 4 620 2 1 2 AM140 369 1 2 1 2 567 1 11 1 2 620 2 1 2 ...

Page 103: ...AGH EU AM240KXVAGH EU AM260KXVAGH EU AM280KXVAGH EU 761 2 6 1150 3 9 1 4 1795 5 10 3 4 A B C Units mm inches Model A B C AM240 393 1 3 1 2 665 2 2 1 4 640 2 1 1 4 AM260 393 1 3 1 2 665 2 2 1 4 640 2 1 1 4 AM280 335 1 1 1 4 564 1 10 1 4 675 2 2 1 2 AM300 335 1 1 1 4 564 1 10 1 4 675 2 2 1 2 ...

Page 104: ...COMM PBA Printed circuit board communication OIL COMP1 Oil Sensor Compressor1 MAIN COOLING Solenoid valve Main cooling COMP1 Motor compressor1 OIL COMP2 Oil Sensor Compressor2 HOTGAS2V V Solenoid valve Hot Gas Bypass2 COMP2 Motor compressor2 OUT 10K Thermistor Ambient Temp _10Kohm OD EEVV V Solenoid valve OutdoorEEV FAN1 Motor fan1 COND 10K Thermistor Cond Out Temp _10Kohm F101 FUSE InverterPBA FA...

Page 105: ...it board communication OIL COMP1 Oil Sensor Compressor1 MAIN COOLING Solenoid valve Main cooling COMP1 Motor compressor1 OIL COMP2 Oil Sensor Compressor2 HOTGAS2V V Solenoid valve Hot Gas Bypass2 COMP2 Motor compressor2 OUT 10K Thermistor Ambient Temp _10Kohm OD EEVV V Solenoid valve OutdoorEEV FAN1 Motor fan1 COND 10K Thermistor Cond Out Temp _10Kohm F101 FUSE InverterPBA FAN2 Motor fan2 TOP1 200...

Page 106: ...28 00 AM100JXVHGH EU 58 60 79 12 33 60 AM120JXVHGH EU 62 64 81 14 39 20 AM140KXVGGH EU 61 63 81 16 44 80 AM160KXVGGH EU 63 65 83 18 50 40 AM180KXVGGH EU 65 67 89 20 56 00 AM200KXVGGH EU 65 67 89 22 61 60 AM220KXVGGH2EU 63 65 83 24 67 20 AM240KXVGGH2EU 65 67 84 26 72 80 AM260KXVGGH2EU 66 68 89 28 78 40 AM280KXVGGH2EU 66 68 89 30 84 00 AM300KXVGGH2EU 67 69 90 32 89 60 AM320KXVGGH2EU 66 68 90 34 95 2...

Page 107: ...71 73 93 56 156 80 AM560KXVAGH EU 71 73 93 58 162 40 AM580KXVAGH EU 72 74 93 60 168 00 AM600KXVAGH EU 72 74 93 62 173 60 AM620KXVAGH EU 71 73 93 64 179 20 AM640KXVAGH EU 71 73 93 66 184 80 AM660KXVAGH EU 71 73 93 68 190 40 AM680KXVAGH EU 71 73 93 70 196 00 AM700KXVAGH EU 71 73 93 72 201 60 AM720KXVAGH EU 72 74 94 74 207 20 AM740KXVAGH EU 72 74 94 76 212 80 AM760KXVAGH EU 72 74 94 78 218 40 AM780KX...

Page 108: ...nt 2 Silent 3 Hearing threshold Cooling 3 AM120JXVHGH EU 4 AM140KXVGGH EU 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 63 125 250 500 1000 2000 4000 8000 Sound Presure level dB Octave band center frequency Hz 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR20 NR15 Silent 1 Silent 2 Silent 3 Hearing threshold C...

Page 109: ...nt 2 Silent 3 Hearing threshold Cooling 3 AM200KXVGGH EU 4 AM220KXVGGH EU 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 63 125 250 500 1000 2000 4000 8000 Sound Presure level dB Octave band center frequency Hz 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR20 NR15 Silent 1 Silent 2 Silent 3 Hearing threshold C...

Page 110: ...nt 2 Silent 3 Hearing threshold Cooling 3 AM280KXVGGH EU 4 AM300KXVAGH EU 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 63 125 250 500 1000 2000 4000 8000 Sound Presure level dB Octave band center frequency Hz 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR20 NR15 Silent 1 Silent 2 Silent 3 Hearing threshold C...

Page 111: ...threshold Silent 1 Cooling Silent 2 Silent 3 3 AM120JXVAGH EU 4 AM140KXVAGH EU 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 63 125 250 500 1000 2000 4000 8000 Sound Presure level dB Octave band center frequency Hz 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR20 NR15 Hearing threshold Silent 1 Cooling Silent...

Page 112: ...eshold Silent 1 Cooling Silent 2 Silent 3 3 AM200KXVAGH EU 4 AM220KXVAGH EU 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 63 125 250 500 1000 2000 4000 8000 Sound Presure level dB Octave band center frequency Hz 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR20 NR15 Hearing threshold Silent 1 Cooling Silent 2 ...

Page 113: ...hold Silent 1 Cooling Silent 2 Silent 3 3 AM280KXVAGH EU 4 AM300KXVAGH EU 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 63 125 250 500 1000 2000 4000 8000 Sound Presure level dB Octave band center frequency Hz 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR20 NR15 Hearing threshold Silent 1 Cooling Silent 2 Si...

Page 114: ...110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 3 AM120JXVHGH EU 4 AM140KXVGGH EU Sound Power level dB Octave band center frequency Hz 90 95 100 105 110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 125 250 500 1000 2000 4000 8000 A NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR20 NR15 NR10 NR5 NR0 90 95 100 105 110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 ...

Page 115: ... 0 Sound Power level dB Octave band center frequency Hz 3 AM200KXVGGH EU 4 AM220KXVGGH EU Sound Power level dB Octave band center frequency Hz 90 95 100 105 110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 125 250 500 1000 2000 4000 8000 A NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR20 NR15 NR10 NR5 NR0 90 95 100 105 110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 ...

Page 116: ...110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 3 AM280KXVGGH EU 4 AM300KXVAGH EU 90 95 100 105 110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 125 250 500 1000 2000 4000 8000 A NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR20 NR15 NR10 NR5 NR0 90 95 100 105 110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 Sound Power level dB Octave band center fre...

Page 117: ...110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 3 AM120JXVAGH EU 4 AM140KXVAGH EU Sound Power level dB Octave band center frequency Hz 90 95 100 105 110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 125 250 500 1000 2000 4000 8000 A NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR20 NR15 NR10 NR5 NR0 90 95 100 105 110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 ...

Page 118: ... 0 Sound Power level dB Octave band center frequency Hz 3 AM200KXVAGH EU 4 AM220KXVAGH EU Sound Power level dB Octave band center frequency Hz 90 95 100 105 110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 125 250 500 1000 2000 4000 8000 A NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR20 NR15 NR10 NR5 NR0 90 95 100 105 110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 ...

Page 119: ...110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 3 AM280KXVAGH EU 4 AM300KXVAGH EU 90 95 100 105 110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 125 250 500 1000 2000 4000 8000 A NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR20 NR15 NR10 NR5 NR0 90 95 100 105 110 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 Sound Power level dB Octave band center fre...

Page 120: ...nge 1 The operating range is shown in these figures 2 The assumed installation condtions are as follows Outdoor units and indoor units combination The Pipe length including elbow is 5m The Level difference is 0m 3 In the low temperature expansion option application the cooling operating is possible under expand operational range only for HR system 4 In case of heatlng mode operating is possible un...

Page 121: ...4 2 0 2 5 7 Capacity coefficient Outdoor temperature C Capacity coefficient of outdoor unit on defrost operation 0 99 0 98 0 96 0 95 0 91 0 88 0 86 0 91 1 00 On heating operation frost can be formed on heat exchanger according to outdoor temperature Frost on heat exchanger results in decreasing the performance To remove frost on heat exchanger of outdoor unit defrost operation is carried out periodi...

Page 122: ...VI V_EVI SolenoidValve EVIBypass V_EB CheckValve Discharge CV_D CheckValve EEVBypass CV_EB Accumulator AC Electronic Expansion Valve EVI E_EVI Electronic Expansion Valve Main E_M Thermistor Liquidpipe T_L IPMCooler IPMC SolenoidValve 4Way V_4W Thermistor Ambient T_A Thermistor Suctionpipe T_S Thermistor EVIOut T_EO Thermistor EVIIn T_EI Pressure Sensor High PS_H BallValve Liquidpipe BV_L HeatExcha...

Page 123: ...I V_EVI SolenoidValve EVI Bypass V_EB CheckValve Discharge CV_D CheckValve EEVBypass CV_EB Accumulator AC Electronic Expansion Valve EVI E_EVI Electronic Expansion Valve Main E_M Thermistor Liquid pipe T_L IPM Cooler IPMC SolenoidValve 4Way V_4W Thermistor Ambient T_A Thermistor Suction pipe T_S Thermistor EVI Out T_EO Thermistor EVI In T_EI Pressure Sensor High PS_H BallValve Gas pipe BV_L Heat E...

Page 124: ...pass V_EB CheckValve Discharge CV_D PW_H2 Oil Separator2 OS2 CVD_2 CheckValve EEVBypass CV_EB Electronic Expansion Valve EVI E_EVI Electronic Expansion Valve Main E_M Thermistor Liquid pipe T_L SolenoidValve 4Way V_4W Thermistor Ambient T_A Thermistor Suction pipe T_S Thermistor EVI Out T_EO Thermistor EVI In T_EI Pressure Sensor High PS_H BallValve Liquid pipe BV_L Heat Exchanger Main HX_M Outdoo...

Page 125: ...c Expansion Valve EVI E_EVI Electronic Expansion Valve Main1 E_M1 Electronic Expansion Valve Main 2 E_M2 Thermistor Liquid pipe T_L SolenoidValve 4Way V_4W Thermistor Ambient T_A Thermistor Suction pipe T_S Thermistor EVI Out T_EO Thermistor EVI In T_EI Termistor Cond In T_CI High Pressure Sensor HPS BallValve Liquid pipe BV_L OutdoorHeat Exchanger OHX OutdoorFan Motor1 OFM1 OutdoorFan Motor2 OFM2...

Page 126: ... CV_D2 Electronic Expansion Valve EVI E_EVI Electronic Expansion Valve Main1 E_M1 Electronic Expansion Valve Main 2 E_M2 Thermistor Liquid pipe T_L SolenoidValve 4Way V_4W Thermistor Ambient T_A Thermistor Suction pipe T_S Thermistor EVI Out T_EO Thermistor EVI In T_EI Pressure Sensor High PS_H BallValve Liquid pipe BV_L OutdoorHeat Exchanger OHX OutdoorFan Motor1 OFM1 OutdoorFan Motor2 OFM2 Therm...

Page 127: ...k Valve EEV Bypass 2 CV_E2 Check Valve EEV Bypass 1 CV_E1 Electronic Expansion Valve Main 2 E_M2 Electronic Expansion Valve Main 1 E_M1 Ball Valve Gas pipe BV_G Thermistor Liquid pipe T_L Heat Exchanger Main HX_M Solenoid Valve EVI 1 V_EVI1 Solenoid Valve EVI 2 V_EVI2 Ball Valve Liquid pipe BV_L Thermistor Ambient T_A RE 3 0L Thermistor Cond Out T_CO Thermistor Cond In T_CI Pressure Sensor High PS...

Page 128: ...alve EEV Bypass 1 CV_E1 Electronic Expansion Valve Main 2 E_M2 Electronic Expansion Valve Main 1 E_M1 Ball Valve Gas pipe BV_G Thermistor Liquid pipe T_L Heat Exchanger Main HX_M Solenoid Valve EVI 1 V_EVI1 Solenoid Valve EVI 2 V_EVI2 Ball Valve Liquid pipe BV_L Thermistor Ambient T_A RE 3 0L Thermistor Cond Out T_CO Thermistor Cond In T_CI Pressure Sensor High PS_H IPM Cooler2 IPMC2 IPM Cooler1 I...

Page 129: ...er supply system which fulfills the requirement above If necessary the user can ask the public power supply company for the system impedance at the interface point This equipment complies with IEC 61000 3 12 provided that the short circuit power Ssc is greater than or equal to Ssc 2 at the interface point between the user s supply and the public system It is the responsibility of the installer or ...

Page 130: ...la tion ambient temperature 30 C single multi conductor cables If the condition is different from the ones stated please consult an electrical installation expert and re select the power cable If the length of power cable exceed 50m re select the power cable considering the voltage drop Use a power cable made out of incombustible material for the insulator inner cover and the sheath outer cover Do...

Page 131: ...ront part Install the power and communication cable using separate cable protection tube Fix a protection tube to the knock out hole on the outdoor unit by using a CD connector or bushing Make sure to use insulating bushing Main unit Sub unit Sub unit Ground cable Ground cable Ground cable Communication cable Power ground cable Power cable Power cable Power cable Communication cable between outdoo...

Page 132: ...e conditions Flexible PVC conduit PVC When the protection tube is installed indoor and not exposed to outside because it is embedded in concrete structure Class 1 flexible conduit Galvanized steel sheet When the protection tube is installed indoor but ex posed to outside so there are risk of damage to the protection tube Class 1 PVC coated flexible conduit Galvanized steel sheet and Soft PVC compo...

Page 133: ...ication f f Maximum number of units that can be connected to the outdoor main unit is 64 so do not exceed this limit f f Communication cable should be connected in series as in the figure below and malfunction of communication can be occur if many units are connected to the same terminal f f Communication cable between indoor and outdoor units and communication cable between outdoor units has no p...

Page 134: ...pace f f If the installation space is narrow installer or otherworker may get injured during work and may also cause prob lem to the product f f If you install multiple number of outdoor units in one space make sure to secure enough ventilation space if there s any walls around the product that may disturb the air flow If enough ventilation space is not secured product may malfunction f f You may ...

Page 135: ...ht of the wall on the side is not limited If the height of the wall exceeds by certain value h1 h2 additional clearance h1 2 h2 2 Half of the exceeded distance should be added to the service space S1 S2 1500 h1 500 h2 Front side Unit mm S1 h1 2 S2 h2 2 At Machinery Room Make sure to install both discharge duct and suction grille louver Static pressure of the discharge duct should be within the sta...

Page 136: ...und the outdoor unit to prevent the defrost water from the outdoor unit from stagnat ing overflowing or freezing near the installation space f f When the outdoor unit is installed on the roof check the strength and waterproof status of the roof Unit mm 960 760 100 80 80 80 6 0 100 X X Direction of the drainage Slope1 50 Drainage work forsingle installation B A 50 100 150 100 X X SECTION 80 80 80 8...

Page 137: ... f If you install the outdoor unit on the rooftop check the strength and make sure to waterproof the rooftop f f Construct draining pit around the base construction and pay attention to the drainage around the out door unit Condensation or defrost water may form during outdoor unit operation f f If there s any possibility of small animals from entering the pipe outlet block the outlet as shown in ...

Page 138: ... of snowfall install a snow prevention duct as a sufficient countermeasure to prevent snow from accumulating on the outdoor unit When the snow prevention duct is not installed frost may accumu late on the heat exchanger and heating operation may not work normally f f Air outlet of the duct should not be directed to the enclosed space Cautions regarding on installing the frame and selecting the bas...

Page 139: ...ay fall and cause personal injury When installing on a rooftop subject to strong wind countermeasures must be taken to prevent the unit from falling down Use a frame that is resistant to corrosion CAUTION 180 AM140 160 180 200 220 XV 560 22 05 1295 50 98 560 22 05 2400 94 49 1732 68 19 1255 49 41 1080 42 52 1192 46 93 552 21 73 2415 95 08 406 15 98 640 25 20 1252 49 29 1315 51 77 550 21 65 871 34 ...

Page 140: ...e Flaring tool Pipe flaring Refrigerant machine oil Apply refrigerant oil on flared part Exclusive etheroil esteroil alkali benzene oil orsynthetic oil Torque wrench Connect flare nut with pipe Compatible Pipe bender Pipe bending Nitrogen gas Airtightness test Prevent oxida tion within the pipe Welder Pipe welding Manifold gage Airtightness test addi tional refrigerant charging Vacuuming charging ...

Page 141: ... the pipe main pipe by one grade which connects between the outdoor unit to the first branch joint f f For H R model When the pipe length including elbow between an outdoor unit and the farthest indoor unit exceeds 90m you must increase the size of the liquid pipe by one grade among the pipes main pipe which con nects between the outdoor unit to the first branch joint H P 33 6 kW 40 0 kW D E C A B...

Page 142: ...22 Ø 25 40 note1 33 6 kW Ø12 70 Ø 28 58 Ø15 88 Ø 28 58 40 0 kW 45 0 kW Ø 31 75 note2 50 4 kW Ø15 88 Ø19 05 56 0 kW 61 6 kW 67 2 kW Ø 34 92 Ø 38 10 note3 72 8 kW 84 0 kW Ø19 05 Ø 22 22 89 6 kW 95 2 kW 101 6 kW Ø 41 28 Ø 41 28 106 6 kW 135 2 kW 140 2 kW 168 2 kW Ø 53 98 173 6 kW 252 0 kW Ø 22 22 Ø 53 98 Ø 25 40 note1 Maximum pipe length The pipe length between an outdoorunit and the farthest indooru...

Page 143: ...elow Ø12 70 Ø 28 58 Ø15 88 Ø 28 58 Over40 0 kW 45 0 kW and below Ø 31 75 note2 Over45 0 kW 63 3 kW and below Ø15 88 Ø19 05 Over63 3 kW 70 3 kW and below Ø 34 92 Ø 38 10 note3 Over70 3 kW 98 4 kW and below Ø19 05 Ø 22 22 Over98 4 kW 135 2 kW and below Ø 41 28 Ø 41 28 Over135 2 kW 169 0 kW and below Ø 53 98 Over169 0 kW Ø 22 22 Ø 53 98 Ø 25 40 note1 Note1 If Ø 25 40 pipe is not available on site use...

Page 144: ... foroutdoorunit C MXJ TA3419M 135 2 kW and below MXJ TA4122M Over140 2 kW f f First branch joint D Make a selection according to outdoor unit capacity Classification Outdoorunit capacity kW Model name of the branch joint Y joint D 40 0 kW and below MXJ YA2512M 45 0 kW MXJ YA2812M 50 4 kW 67 2 kW MXJ YA2815M 73 6 kW 95 2 kW MXJ YA3419M 101 6 kW 135 2 kW MXJ YA4119M 140 2 kW and over MXJ YA4422M ...

Page 145: ...ssification Model name Specification kW Y joint E MXJ YA1509M 15 0 kW and below MXJ YA2512M Over15 0 kW 40 0 kW and below MXJ YA2812M Over40 0 kW 45 0 kW and below MXJ YA2815M Over45 0 kW 70 3 kW and below MXJ YA3419M Over70 3 kW 98 4 kW and below MXJ YA4119M Over98 4 kW 135 2 kW and below MXJ YA4422M Over135 2 kW 2 Distribution header Classification Model name Specification kW Distribution header...

Page 146: ... Additional refrigerant H P Ø12 70 5 m Ø12 70 5 m Ø12 70 5 m Ø6 35 5 m Ø6 35 10 m Ø6 35 15 m Ø9 52 10 m Ø9 52 10 m Ø9 52 10 m Ø9 52 10 m Ø6 35 5 m Ø9 52 10 m 46 4 kW 4 5 kW 5 6 kW 5 6 kW 7 1 kW 7 1 kW 7 1 kW 7 1 kW 3 6 kW ...

Page 147: ...sification AM080JX VHGH AM100JX VHGH AM120JX VHGH AM140KX VGGH AM160KX VGGH AM180KX VGGH Basic type 6 5 6 5 6 5 9 4 8 4 8 4 Classification AM200KX VGGH AM220KX VGGH AM240KX VGGH AM260KX VGGH AM280KX VGGH AM080KX VSGH Basic type 8 4 8 4 14 14 14 14 f f Amount of additional refrigerant depending on the pipe size ⓐ Amount of additional refrigerant has to be calculated based on the sum of all liquid p...

Page 148: ...K 0 380 380 38 Slim duct AM FNLDE 0 17 0 17 0 17 0 26 0 35 0 35 0 45 0 42 0 42 0 62 0 62 MSP duct AM NMDE 0 24 0 24 0 24 0 280 28 0 28 0 32 0 54 0 68 0 68 0 91 Ceiling AM FNCDE AM JNCDK 0 39 0 39 0 56 0 95 Console AM NJDE 0 16 0 27 0 27 0 27 0 27 Neo forte AM FNTDE 0 24 0 24 0 24 0 24 0 36 0 36 Neo forte with EEV AM FNQDE 0 34 0 34 0 34 0 34 0 51 0 51 0 51 AR5000 AM JNADK 0 16 0 16 0 19 0 25 0 25 ...

Page 149: ...a tion Size of liquid pipe Length m Unit amount of refriger ant kg m Amount of additional refrigerant kg Total amount of addition al refrigerant kg Liquid pipe ⓐ Ø 6 35 35 0 02 0 7 ⓐ 5 575 Ø 9 52 50 0 06 3 0 Ø 12 70 15 0 125 1 875 Classification Model name of indoorunit Number of units Unit amount of refrigerant kg EA Amount of additional refrigerant kg Total amount of additional refrigerant kg In...

Page 150: ...efrigerant ⓐ ⓑ 11 965 4 66 16 625 kg Temper grade and minimum thickness of the refrigerant pipe Outerdiameter mm Minimum thickness mm Tempergrade Ø 6 35 0 70 Annealed Ø 9 52 0 70 Ø12 70 0 80 Ø15 88 1 00 Ø19 05 0 90 Drawn Ø 22 22 0 90 Ø 25 40 1 00 Ø 28 58 1 10 Ø 31 75 1 10 Ø 34 92 1 21 Ø 38 10 1 35 Ø 41 28 1 43 Ø 44 45 1 60 Ø 50 80 2 00 Ø 53 98 2 10 For pipes larger than Ø 19 05 drawn type C1220T 1...

Page 151: ...ng outdoor units f f Height of the connection pipe should be same or lower than the ones connected to the outdoor units f f Check the changes in comparison with the DVM II III and IV Caution Correct installation Incorrect installation Refrigerant pipes should be connected at the same orlowerlevel than the ones connected to the outdoorunit Refrigerant pipes must be connected by the side of the prod...

Page 152: ...10 Installation 152 Refrigerant pipe installation Examples of refrigerant pipe installation H P 1 Using Y joint 2 Using distribution header ...

Page 153: ...stalling onlywith Y joint Branch joint Outdoorunit Indoorunit Branch joint Outdoorunit Indoorunit Installing with Y joint and distribu tion header Branch joint Distribution header Outdoorunit Indoorunit Outdoorunit Indoorunit Distribution header Branch joint Installing onlywith distribution header Outdoorunit Indoorunit Distribution header Outdoorunit Indoorunit Distribution header ...

Page 154: ...nt a b c d e f g h i j k l m n p 1000m Installing with Y joint and distribution header a b c d e f g h i j k 1000m Installing only with distribu tion header a b c d e f g h i 1000m Outdoorunit Outdoor unit Module installation Pipe length 10 m or less r 10 m s 10 m t 10 m Equivalent length 13 m or less r 13m s 13m t 13m Maximum allowable height dif ference of pipe Outdoorunit Indoorunit 110 110m No...

Page 155: ...t and the outdoorunit is not increased by1 grade a b c d e f g 2 h i j k l m n p 1000 m If the size of pipe main pipe between the first branch joint and the outdoorunit is increased by 1 grade a b c d e f g 2 h i j k l m n p 1000 m Each Y joint Each indoorunit h i j p 45 m Difference between the distance of the outdoorunit to the farthest in doorunit and nearest indoorunit 45m a b c d e g p a h 45...

Page 156: ...R WE11N DVM CAC Wired Remote Controller Simple Type MWR SH00N DVM CAC Wired Remote Controller Touch Simple Type MWR SH10N DVM CAC ERVWired Remote Controller MWR VH12N ERV Olny DVM CAC Wired Remote Controller MWR WW00N EHS Only EHS ReceiverKIT MRK A10N DVM CAC Zone Controller MWR ZS00N Mastercontroller Dampercontroller DVM CAC Zone Controller MWR ZS10N Slave controller DVM CAC Zone Controller MRW T...

Page 157: ...ace Module MIM N01 DVM CAC ERV Interface Module MIM N10 DVM CAC Integrated management System DMS2 5 MIM D01AN DVM CAC S NET3 MST P3P DVM CAC Gate Way BACnet Gateway MIM B17BN DVM CAC Lonworks Gateway MIM B18BN DVM CAC External Contact Interface Module MIM B14 DVM CAC MTFC Multi Tenant Function Controller MCM C210N DVM SIM Signal Interface Module MIM B12N DVM CAC PIM Pulse Interface Module MIM B16N...

Page 158: ...MIM C02N DVM CAC Others External Room Sensor MRW TA DVM CAC Operation Mode Selection Switch MCM C200 DVM Module Controller MCM A00N CHILLER Only CHILLER FCU Interface Module MIM F10N CHILLER Only CHILLER NOTE In case you want more information about the accessories please refer to the control and accessories TDB on pvi Samsung com site ...

Page 159: ...0N DVM CAC WIFI KIT MIM H03N MIM H03 DVM CAC Interface Module MIM N01 MIM N01 DVM CAC ERV Interface Module MIM N10 MIM N10 DVM CAC Integrated management System DMS2 5 MIM D01AN MIM D00A DVM CAC S NET3 MST P3P MST P3P DVM CAC GateWay BACnet Gateway MIM B17BN MIM B17 DVM CAC Lonworks Gateway MIM B18BN MIM B18 DVM CAC External Contact Interface Module MIM B14 MIM B14 DVM CAC MTFC Multi Tenant Functio...

Page 160: ... below MXJ TA4122M 140 2 kW and Over Y Joint Only H R OutdoorUnit MXJ TA3100M 135 2 kW and below MXJ TA3800M 140 2 kW and Over Distribution Header MXJ HA2512M 45 0 kW and below for4 rooms MXJ HA3115M 70 3 kW and below for8 rooms MXJ HA3819M Over70 3 kW 135 2 kW and below for8 rooms MCU MCU S6NEE1N 56 kW 6 indoorunits MCU S4NEE1N 56 kW 4 indoorunits MCU S4NEE2N 56 kW 6 indoorunits EEV KIT MEV E24SA...

Page 161: ... PC4SUSMEN 4Way Cassette S 600x600 Classic PC4NUSKAN 4way Cassette S Waffle PC4NUSKEN 4way Cassette S Classic PC4NBSKAN 4way Cassette S Waffle Black PC4NUDMAN 360 CST Square White PC4NUNMAN 360 CST Circular White PC4NBDMAN 360 CST Square Black PC4NBNMAN 360 CST Circular Black S Plasma lon KIT MSD CAN1 Option 1Way 4Way 4Way 600x600 360 Big Ceiling Include Console MSD EAN1 Option Duct S Big Duct ERV...

Page 162: ...075S GU3D MSP S Duct 5 6 7 1 kW MDP E075SEE3D Slim Duct 2 0 14 0 kW MDP G075SP Duct S External All Capacities BIG Duct MDP G075SQ Duct S Internal 3 5 kW 14 kW BIG Duct AHU KIT MXD K025AN 7 0 kW 8 75 kW MXD K050AN 14 0 kW 17 5 kW MXD K075AN 21 0 kW 26 25 kW MXD K100AN 28 0 kW 35 0 kW MXD A64K100E MCM D201N 28kW 35kW 56kW 70kW 84kW 105kW 112kW 140kW MDX A64K100E X 1 EA MDX A64K100E X 2 EA MDX A64K10...

Page 163: ...U3D O MDP E075SEE3D O MDP G075SP External All Capacities O O MDP G075SQ Internal O O S Plasma Ion KIT MSD CAN1 O O MSD EAN1 O Motion detect Sensor MCR SMA O ERVCO2 Sensor MOS C1 O EEVKITS MEV E SA 1 Indoor O MXD E K A 2 3 Indoor O MCU KIT MCU S6NEE1N Below6 IDU below56 Kw O O O O O O O O O O O O O O O O O O O O O O MCU S4NEE1N Below4 IDU below56 kW O O O O O O O O O O O O O O O O O O O O O O MCU S...

Page 164: ... PM SE Head Office Suwon Korea 129 Samsung Ro Yeongtong Gu Suwon City Gyeonggi Do Korea 16677 Website www samsung com http btsp samsunggsbn com Email airconditioner samsung com Images and data in this book may subject to change without prior notice ...

Reviews: