background image

Occupancy Sensor AutoON/Override Power Pack

Cat. No. LCA2292

Load Ratings: 20A, 2400W @ 120V, 60Hz - Incandescent / 20A, 2400VA @ 120V, 60Hz - Fluorescent

20A, 5540VA @ 277V, 60Hz - Fluorescent / 1/2 HP @ 120V - Motor Load / 2 HP @ 240/277V, 60Hz - Motor Load / 0.5A 120V, 1A 30VDC - HVAC Relay

For use with LRM2250, LRM2255, LRM2260, LRM2265, LRM2270,LRM2275, LRM2280 Low Voltage Sensors

INSTALLATION INSTRUCTIONS

WARNINGS AND CAUTIONS:
• 

TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at circuit breaker or fuse and test that power is off before wiring!

•  To be installed and/or used in accordance with appropriate electrical codes and regulations.

•  If you are unsure about any part of these instructions, consult an electrician.

•  Use this device with 

copper or copper clad wire only.

• 

Disconnect power when servicing fixture or changing lamps.

•  Lights Flickering
  -  Lamp has a bad connection.

  -  Wires not secured firmly with wire connectors.
•  Lights did not turn ON
  -  Circuit breaker or fuse has tripped.

  -  Lamp is burned out.

  -  Lamp Neutral connection is not wired.

  -  Hold OFF or Manual ON input is active.

  -  Low Voltage miss wired. Verify wiring pre appropriate diagram.

  -  Line Voltage miss wired. Verify wiring pre appropriate diagram.
•  Lights stay ON
  -   Constant motion. 

To Test: adjust sensor; remove motion source (HVAC, Mask, or 

move sensor). 

•  Lights turn ON too long
  -  Adjust sensor settings.
•  Lights came ON during presentation
  -  AutoON mode is connected and the time delay expired.

  -  Increase the sensor time delay or generate more motion during the presentation.
•  Lights do not turn OFF with time delay
  -  Hold ON input is active.

 FEATURES

•  Title 24 Compliant

•  Hold On/ Hold Off capabilities

•  Regulated 24VDC, 150mA output current 

•  Mounts inside Fluorescent Ballast cavity

•  Mounts inside or outside Junction Box

•  Rated for Plenum spaces

 RATINGS

Part Number 

HVAC Relay 

Power Input

1

   

Power Output

2

LCA2292  

Yes  

120-277VAC, 50/60Hz 

24VDC, 150mA 3.6W

1

 Input voltage tolerance 10%, Frequency tolerance 5%.

2

 Output voltage tolerance 15%, Output voltage listed at nominal.

 DESCRIPTION 

The power pack contains a power supply, a load switching relay and an HVAC relay. 

The power supply provides Class 2 low-voltage power for LRM2250, LRM2255, 

LRM2260, LRM 2265, LRM2270, LRM2275, and LRM2280 Series Occupancy 

Sensors. The relay in the power pack is controlled by the occupancy sensors 

connected via the 22 Gauge Blue "occupancy" wire. Multiple occupancy sensors 

can be connected to a single power pack in order to fully cover an area. The power 

packs include zero cross switching circuitry to minimize inrush current associated with 

incandescent and electronic ballasts. This reduces wear and tear on the relay contacts 

making the power pack last longer.
Application Notes:
1.
  When a lighting load exceeds a single power pack’s rating, the load can be split 

between multiple power packs. The low voltage occupancy input (Blue wire) and DC 

return (Black wires) of the power packs must be connected together for all power 

packs to operate together as one. Connect the Blue (occupancy) wires of all power 

packs and sensors together. Connect the Black (return) wires of all power packs and 

sensors together. Connect the Red (+24VDC) wires of the sensors to the Red wires 

of only one power pack. Never connect the Red (+24VDC) wires of two different 

power packs together.

2.  When more sensors are required than one power pack can supply, multiple power 

packs can be used to supply power to the occupancy sensor, but not switch any 

load. The primary power pack is the power pack switching the load. The secondary 

power packs only provide low voltage power to the occupancy sensor(s). Connect as 

many sensors to the primary power pack as possible (see current capacity section 

below), by connecting the Red wires of the sensors to the Red wire (+24VDC) of 

the primary power pack. Connect the Red wires (+24VDC) of the remaining sensors 

to the Red wires of the secondary power pack. Connect the Black (return) wires of 

all power packs and all sensors together. Connect the Blue (occupancy) wire of all 

sensors together to the Blue wire (occupancy) of the primary power pack. Never 

connect the Red (+24VDC) wires of two different power packs together.

FCC COMPLIANCE STATEMENT (LCA2292)

This equipment has been tested and found to comply with the limits for a Class A digital 

device, pursuant to part 15 of the FCC Rules. These limits are designed to provide 

reasonable protection against harmful interference when the equipment is operated 

in a commercial environment. This equipment generates, uses, and can radiate radio 

frequency energy and, if not installed and used in accordance with the instruction

manual, may cause harmful interference to radio communications. Operation of this 

equipment in a residential area is likely to cause harmful interference in which case the 

user will be required to correct the interference at his own expense.

 LOW-VOLTAGE CURRENT CAPACITY

 INSTALLATION

LCA2292

Total Number of Sensors

150mA

1. 

WARNING:

 TO AVOID FIRE, SHOCK, OR DEATH; 

TURN OFF POWER AT 

CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!

2.  Mount power pack per desired application:
 

A.   To mount outside 4"x4" junction box using 2" EMT nipple, refer to Figure 1. Wire 

per instructions 

Step 3A and 3B.

 

B.   To mount inside 4"x4" junction box, refer to Figure 2. Wire per instructions Step 

3A and 3B.

 

 

• Ensure that conduit/cable entry clamp is located in corner of junction box.

 

 

• Dress wires to provide enough clearance when device is installed.

    

CAUTION:

 Low-voltage wires must also be dressed so they are separate 

from the high voltage (Class I) conductors. Refer to local building codes for the 

appropriate installation requirements for the low voltage wiring. Jacketing over the 

low-voltage wires may be required to provide appropriate insulation from the high-

voltage wiring.

 

C.   To mount inside ballast cavity of light fixture, refer to Figure 3A. Wire per 

instructions 

Step 3A and 3B.

    

CAUTION:

 Low-voltage wires must also be dressed so they are separate 

from the high voltage (Class I) conductors. Refer to local building codes for the 

appropriate installation requirements for the low voltage wiring. Jacketing over the 

low-voltage wires may be required to provide appropriate insulation from the high-

voltage wiring.

 

D.   To mount outside ballast cavity of light fixture, refer to Figure 3B. Wire per 

instructions 

Step 3A and 3B.

3A. Line Voltage Wiring: Remove 5/8" (1.6 cm) of insulation from each circuit conductor. 

Make sure that ends of conductors are straight. Connect lead wires from Power Pack 

to LINE circuit per appropriate WIRING DIAGRAM as follows: Twist strands of each 

lead tightly and, with circuit conductors push firmly into appropriate wire connector. 

Screw connectors on clockwise making sure that no bare conductor shows below the 

wire connectors. Secure each connector with electrical tape.

3B. Class 2 and HVAC Wiring: Connect Low-Voltage wires from Power Pack to Sensor 

per appropriate WIRING DIAGRAM as follows: Twist strands of each lead tightly and, 

with circuit conductors, push firmly into appropriate wire connector. Screw connectors 

on clockwise making sure that no bare conductor shows below the wire connectors. 

Secure each connector with electrical tape.

4. Refer to sensor Installation Instructions for further details.
5. Restore power at circuit breaker or fuse. INSTALLATION IS COMPLETE.

Mounts outside

junction box

Figure 1

Line Voltage Wires

Class 2 Wires

Figure 2

Mounts inside

junction box

Line Voltage Wires

Class 2 Wires

 OPERATION

The AutoOn/Override Power Pack can be turned ON and OFF automatically using an 

occupancy sensor input, a timer, panel or BAS input, and manually from an optional low 

voltage momentary switch.
AUTO ON (See Wiring Diagram):

The occupancy sensor input, Hold ON input and the optional momentary switch input can 

all be used to turn the load ON.

When the load is turned OFF using the momentary switch, the power pack does not turn 

it ON automatically until after the sensor time delay expires (e.g., presentation mode). 

Pressing the momentary switch before the sensor time delay expires turns the load ON.

When the occupancy sensor’s time delay expires, the power pack reverts to AutoON mode 

and it turns the load ON with the next input from the occupancy sensor.
MANUAL ON (See Wiring Diagram):

Occupants must press the low voltage momentary switch to turn the load ON.

When the occupancy sensor is the only input keeping the load ON, the load turns OFF 

when the sensor time delay expires. If the sensor input re-triggers within 30 seconds after 

the load turns OFF, the load turns ON again. After the 30 seconds expire with no sensor 

input press the momentary switch to turn the load ON.
LOW VOLTAGE INPUTS

24VDC input wires are provided to control the load relay. The inputs may be used in 

combination or individually, depending on the application(s). See wiring diagrams for 

connections.
MAINTAINED INPUTS

Occupancy Sensor (Blue) - This input is for occupancy sensor AutoON/AutoOFF.

Applying 24v closes the relay (Occupied). Remove the voltage and the relay opens (Vacant). 
Occupancy Sensor (Blue/White) - This input is for occupancy sensor ManualON/AutoOFF.

When the attached occupancy sensor detects motion, no action occurs. A local 

momentary switch is required to manually turn the load ON. Then the sensor will turn the 

load OFF when the time delay expires.  
Hold ON (Yellow) - This input is intended for timer or panel input.

Applying 24VDC closes the relay

 and disables other inputs

.  

 

 

 

 

 

 

     

 

   

   

 It 

can be 

overrid

den by the Hold

 O

FF

 input. 

Hold OFF (Orange) – This input is used for timer, panel, BAS or load shed input.

Applying 24VDC opens the relay.  Remove the voltage and the relay can accept any other 

input. It overrides the Control ON and Hold ON inputs.
Local Switch (Yellow/Orange) – This input is for a low voltage momentary switch.

Applying 24VDC momentary input changes the relay to the opposite state. It overrides the 

Control ON, Hold ON and Hold OFF inputs.

•  All wires rated at 105

o

 C, 600V insulation.

•  Class 2 wires are Teflon coated, for plenum applications.
•  HVAC wiring is Class 1 and Class 2 rated.

Line Voltage Wires

Class 2 Wires

Line 120-277V
Neutral
Load
Load

Power (24 VDC)
DC Return
Occupancy Auto ON

HVAC Wires
HVAC Common
HVAC NO (Normally Open)
HVAC NC (Normally Closed)

Occupancy Manual ON
Hold ON
Hold OFF
Local Switch Input

Signal Name

Black
White
Blue
Blue

Red
Black
Blue

Green
Brown/White
Brown

Blue/White
Yellow
Orange
Yellow/Orange

Color

18 AWG
18 AWG
14 AWG
14 AWG

22 AWG
22 AWG
22 AWG

22 AWG
22 AWG
22 AWG

22 AWG
22 AWG
22 AWG
22 AWG

Gauge

Wire Designations

 TROUBLESHOTING

Reviews: