NORMAL OPERATION/MANUAL TEST

 

OP-PANEL INDICATORS/OPERATION:

 

 

 

GREEN - Status:   Solid indicates system normal and AC power is on. 

NOTE:  To start the Manual test, simply press the Green Indicator (button) as indicated below. To Reset/Cancel a test press the Green Indicator 
(button) once during any test. When Unit is in test mode the Green Indicator LED is flashing.

 

 

 

1 Press:   perform a 5-sec brief lamp test, LED strip operating from battery only.  

 

2 Presses:   perform a 1-min diagnostic test, LED strip operating from battery 
only. 

 

3 Presses:   perform a 90-min diagnostic test, LED strip operating from battery 
only.  

 

6-sec Continuous Press:  perform a RESET operation.

 

 

CONTINUOUS MONITORING:  The system monitors the following continuously: 
Battery, 2) LED strip, 3) Charger, 4) Transfer function.

 

 

 

The battery requires at least 24 hours of charge time to perform any extended diagnostic test. If the battery has not charged for 72 hours after 
installation and a diagnostic test is requested, the charger light will come on and stay on for one minute indicating that the battery is not fully charged 
for attempted test.

 

 

OPTIONAL FACTORY EQUIPPED ITEMS:

 

 

FIRE-ALARM INTERFACE (FI): Unit will be supplied with a connector at the FAFI location and an interface cable to connect to the building system 
(per wiring diagram).

 

 

 

FLASHING EM (F): Unit will flash the EXIT sign when operating from the battery only. (Flash rate is 1 flash/sec. with a 70%-on duty cycle.)

 

 

 

BUZZER EM (B): Unit will buzz for approx. ½ -sec during power-up sequence or after a reset operation. Buzzer does not activate during either manual 
or automatic testing. Buzzer will only activate when operating from the battery and only due to AC power loss.

 

 

 

 

 

 
 
 
 
 
 
 

 

 

 

No Rigid 

Conduit

 

 

 

 

 

Flexible 

Conduit Only

 

 

Emergency Lighting

 

COMPAC 

Thermoplastic Exit

 

 
 

 

 

 

 

o

 

Simple snap-out Chevrons

 

 

 

CHEVRON 

CHEVRON

 

CXX Series 

INSTRUCTION SHEET 

 

 

 

 

LASER TEST (LX): To operate using a laser pen: use laser pen and point the laser beam over the remote sensor (see below), thereby duplicating 
the manual button (1,2,3) pushes. The laser must impact the remote sensor for at least 0.2 seconds to be recognized.

 

 

 

TROUBLE  INDICATORS/TROUBLESHOOTING

 

IMPORTANT SAFEGUARDS

 

READ AND FOLLOW ALL  SAFETY INSTRUCTIONS

 

 

WARNING: Electrical Shock Potential!! Do not attempt to install, maintain or relamp without disconnecting

 

 

TEST 

Button

 

 

 
 
 
 
 
 
 
 
 
 

REMOTE SENSOR

 

(IF EQUIPPED)

 

Xtest  DISPLAY  PANEL  INDICATOR:

 

 

GREEN - Status:  solid indicates system normal and AC power is on and flashes during any manual/auto test 

cycle.

 

 

RED – CHARGER FLASHING:  a charger failure requires the diagnostic charger board to be replaced.

 

 

RED – BATTERY FLASHING:  battery is disconnected or if it is connected and charged for more than

 

24 hours, a replacement is needed.

 

 

RED - LAMP FLASHING:  LED strip is disconnected or if it is connected a replacement is needed.

 

 

ALL 3 RED FLASHING:  bad transfer; battery and LED strip are disconnected or if they are connected a 

replacement diagnostic charger board is needed.

 

all power. Failure to disconnect power can result in electrocution, shock, or severe burns.

 

 

CAUTION: This fixture is designed for permanent installation in ordinary (NON-HAZARDOUS) locations in 
accordance with the National Electrical Code and all applicable local codes. Do not use in areas of limited 
ventilation or in high ambient enclosures. When using electrical equipment, basic safety precautions should 
always be followed; including the following:

 

 

 

Do not use outdoors.

 

 

Do not let power supply cords touch hot surfaces.

 

 

Do not mount near gas or electric heaters.

 

 

Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If

 

WIRING INFORMATION

 

 
 

 

Transformer Inputs

 

 

BLACK - 120V

 

WHITE - Common or Neutral

 

RED - 277V

 

 
 

Diagnostic  Charger  Board

 

 

 

 
 
 
 

 

Buzzer

 

(If Equipped)

 

acid is spilled on skin or in eyes, flush acid with fresh water and contact a 
physician immediately.

 

 

Equipment should be mounted in locations and at heights where it will not readily 
be subjected to tampering by unauthorized personnel.

 

 

The use of accessory equipment not recommended by the manufacturer may cause 
an unsafe condition.

 

 

Do not use this equipment for other than intended use.

 

 

Servicing of this equipment should be performed by qualified personnel only.

 

Transformer

 

Connector

 

EXIT 

Connector

 

Battery

 

Connector

 

Fire-Alarm Interface 
Connector (If Equipped)

 

 

SAVE THESE  INSTRUCTIONS

 

9

 

Philips Lighting Canada Ltd. 
281 Markham Road, 
Markham, ON, Canada  L6C 2S3 
Phone: 800-668-9008 

www.philips.com/luminaires

 

727543101 
CMANU0505A 

February 2016 

 

 

Reviews: