1

COMMUNICATION INSTRUCTION MANUAL

TEMPERATURE CONTROLLER

KT2

No. KTC3E5 2013.05

To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.
For this product to which communication function has been added, “1” is entered at the end of the model number.
(For the model number and basic operation, refer to the instruction manual for KT2.)

Warning

Turn the power supply to the instrument off before wiring or checking.
Working or touching the terminal with the power switched on may result in severe injury or

death due to Electric Shock.

1. Setup of the KT2

Set the items “Communication protocol selection”, “Instrument number setting”, “Communication speed
selection” after the “Sensor correction setting” in Auxiliary function setting mode 1.
To enter Auxiliary function setting mode 1, press the

key for 3 seconds while holding down the

key.

Display

Name, Functions, Setting range

Default value

Communication protocol selection

Modbus ASCII mode

• Selects the communication protocol.

: Unavailable

: Modbus ASCII mode
: Modbus RTU mode

Instrument number setting

0

• Sets the instrument number individually to each instrument

when communicating by connecting plural instruments in
serial communication.

• Setting range: 0 to 95 (However, number of connectable units:

Max. 31 units)

Communication speed selection

9600bps

• Selects a communication speed to be equal to the speed

of the host computer.

:

2400bps

:

4800bps

:

9600bps

: 19200bps

2. Terminal arrangement

TC

: Thermocouple input terminals

RTD

: RTD input terminals

DC

: DC current, DC voltage input terminals

For DC current input type, connect 50
shunt resistor (sold separately) between
input terminals.

OUT1 : Control output or Heating output

(Heating/Cooling control option) terminals

POWER SUPPLY: Power terminals

EV1/OUT2: Event output 1 or Cooling output

(Heating/Cooling control option) terminals

EV2

: Event output 2 terminals

DI

: DI (Digital input) terminals

Three DI functions: SV1/SV2 external

(Fig. 2-1)

selection function, OUT/OFF (RUN/STOP)
external selection and Timer function

RS-485: Serial communication terminals

Summary of Contents for KT2

Page 1: ...unication protocol selection Modbus ASCII mode Selects the communication protocol Unavailable Modbus ASCII mode Modbus RTU mode Instrument number setting 0 Sets the instrument number individually to e...

Page 2: ...in Connection RS 232C RS 485 Communication speed 2400 4800 9600 19200bps Fig 4 1 RS 485 PLC KT2 No 0 KT2 No 1 KT2 No 2 KT2 No 30 RS 485 Host computer KT2 No 0 KT2 No 1 KT2 No 2 KT2 No 30 RS 485 RS 232...

Page 3: ...speed of KT2 in accordance with that of the host computer For instrument number setting and communication speed selection refer to Chapter 1 Setup of the KT2 or the instruction manual for KT2 Memory c...

Page 4: ...communication line within a 1 character transmission period after sending the response Master side Notice on programming Set the program so that the master can disconnect the transmitter from the com...

Page 5: ...a value Value out of the setting range 17 11H Illegal setting Unsettable status 18 12H Illegal setting During setting mode by keypad etc 4 Data Data differs depending on the function code A request me...

Page 6: ...range is set The function code MSB is set to 1 for the response message in exception error status 86H 38H 36H If an exception code 03H 30H 33H Value out of the setting range is returned the error can...

Page 7: ...by setting the MSB to 1 because the former is an illegal function For negative acknowledgement exception code Table 6 4 2 below is set to the data of response message and returned to the master in or...

Page 8: ...tatus 83H If an exception code 02H Non existent data address is returned the error can be determined by reading this code Fig 6 4 7 3 Setting Address 1 SV1 A request message from the master When setti...

Page 9: ...1191H Step 9 time Set value Decimal point ignored 03H 06H 0001H SV1 Set value Decimal point ignored 0002H Not used 03H 06H 0003H AT 0000H Cancel 0001H Perform 03H 06H 0004H OUT1 Heating proportional...

Page 10: ...ecimal point ignored 03H 06H 0026H A2 hysteresis Set value Decimal point ignored 0027H Not used 0028H Not used 03H 06H 0029H A1 action delayed timer Set value 03H 06H 002AH A2 action delayed timer Set...

Page 11: ...g MV manipulated variable Decimal point ignored 03H 0082H OUT2 Cooling MV reading OUT2 Cooling MV Decimal point ignored 03H 0083H Current SV reading Current SV Decimal point ignored 03H 0084H Running...

Page 12: ...failure Check the following The connection or wiring of the communication cable is not secure Burnout or imperfect contact on the communication cable and the connector Communication speed of the slav...