Fire alarm systems 

Analog 

multi detector 

4300 

 

Constant sensitivity / Service signal at a fixed level of contamination 

 

New advanced algorithms and functions and yet compatible with older EBL systems 

General 

The multi detector contains one photo-
electric (optical) smoke detector and one 
heat detector within the low profile housing.  
The latest IC technology will secure the 
highest reliability possible. It has 

unleaded 

soldering

.  In the 

smoke

 detection chamber 

is a high-efficient optical system consisting 
of an LED and a photodiode with two 
lenses.  Scattered light (i.e. reflection of 
infrared light) is used to detect smoke.  The 
smoke enters the detection chamber through 
an insect filter and an optical labyrinth.  This 
construction not only improves the smoke 
inflow, it also causes steam, fog, etc. to 
condense into moisture on its surfaces, to 
prevent false (nuisance) alarms.   
The 

heat

 sensing element is a thermistor.  

The detector is supplied with two LEDs that 
will light when the detector goes into alarm.  
The detector is plugged in the analog base 
3312x / 4313.  The COM loop is connected 
to the base, which also has terminals for an 
external LED, e.g. 2218. The detector is 
intended for indoor use in dry premises and 
in the systems 

EBL512

 / 

128

 / 1000 / 2000 

depending on the detector mode. 

Constant sensitivity 

The detector maintains a constant sensitivity 
regardless of its contamination.  A service 
signal will be given when the detector has 
reached a service level.   

Address / Detector mode 

The address setting tool 3314 is used to set 
the detector's COM loop address and the 
detector mode NORMAL, 2330 or 2312. 
See Planning Instructions for the system 
respectively for more information about the 
modes and functions. 

 

NORMAL

 mode (analog):  Detector 

4300 is used in the systems EBL512 
(SW version > 2.0) and EBL128, also as 
a spare part for the detector 3316 in 
NORMAL mode. 

 

2330

 mode (conventional):  Detector 

4300 is used in the systems EBL512 / 
1000 / 2000 as the best substitute for the 
detectors 2316 & 2317 + base 2330. 

 

2312

 mode (analog):  Not used for 4300.  

The different modes have different functions 
and features, e.g. in the 2330 mode, the 
detector does the fire judgement but in the 
NORMAL mode this is done in the c.i.e.  
The detector is prepared for an "Advanced 
mode" to be used in conjunction with future 
EBLxxx SW versions. 

AI function 

In the 2330 mode is the AI function used, 
i.e.: 

 

Combined heat and smoke sensing

 will 

guarantee reliable and accurate fire alarm 
detection. 

 

Variable delay function

, i.e. the delay 

time before an alarm is influenced by 
temporary temperature and/or smoke 
obscuration changes. 