W3-002-SLSUPS-002A

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

REMOTE STATUS ALARM PANEL

 

INSTALLATION/INSTRUCTION MANUAL

 

RSAP

Mitsubishi Electric Automation, Inc.

UPS Group

 

Summary of Contents for REMOTE STATUS ALARM PANEL

Page 1: ...W3 002 SLSUPS 002A REMOTE STATUS ALARM PANEL INSTALLATION INSTRUCTION MANUAL RSAP Mitsubishi Electric Automation Inc UPS Group ...

Page 2: ...osed Hardwired Figure 1 1 5 Terminal Block Description Figure 2 0 6 Terminal Block Description Hardwired Figure 2 1 7 Remote Monitor Open Figure 3 0 8 Remote Monitor Open Hardwired Figure 3 1 9 Remote Monitor Conduit Access Figure 4 10 Figure 2033A Analog UPS 11 Figure 2033A DDC UPS 12 Figure 2033C UPS 13 Figure 2033D 9800AD UPS 14 Figure 9700 Series 15 Figure 9800A UPS 16 ...

Page 3: ... 0 3 0 and the corresponding UPS wiring diagram connect the seven 7 pairs of twisted wire from the RSAP to the customer accessible alarm contact terminal bar in the UPS module Refer to the UPS owner s manual for location 6 Refering to Figure 3 0 install 6 AA batteries included Batteries will provide about 8 hours of run time in the event of an AC power failure Replace these batteries yearly for op...

Page 4: ...ackup mode The audible alarm will beep intermittently 3 Inverter On LED The green LED is illuminated as long as the UPS inverter is operating 4 Output LED This green LED is illuminated as long as there is power to the critical load either by the Inverter or Bypass 5 Load On Bypass LED This yellow LED is illuminated as long as the critical load is powered by the Bypass 6 AC Input LED This green LED...

Page 5: ...GE RED LED 11 ALARM SILENCE RED LED 12 INTERNAL MONITOR BATTERY OK YELLOW LED 5 LOAD ON BYPASS YELLOW LED 4 OUTPUT TO CRITICAL LOAD GREEN LED 3 INVERTER ON GREEN LED 2 BATTERIES ON YELLOW LED AUDIBLE ALARM MONITOR RESET PUSHBUTTON MONITOR TEST PUSHBUTTON ALARM SILENCE PUSHBUTTON INTERNAL MONITOR BATTERY TEST PUSHBUTTON INPUT TRANSFORMER FEMALE MIC PLUG 6 CORD FIGURE 1 0 INPUT CONFIGURATION SEE OPT...

Page 6: ...LED 7 UPS FAULT RED LED 8 OVERLOAD RED LED 9 INPUT FAILURE RED LED 10 BATTERY LOW VOLTAGE RED LED 11 ALARM SILENCE RED LED 12 INTERNAL MONITOR BATTERY OK YELLOW LED 5 LOAD ON BYPASS YELLOW LED 4 OUTPUT TO CRITICAL LOAD GREEN LED 3 INVERTER ON GREEN LED 2 BATTERIES ON YELLOW LED AUDIBLE ALARM MONITOR RESET PUSHBUTTON MONITOR TEST PUSHBUTTON ALARM SILENCE PUSHBUTTON INTERNAL MONITOR BATTERY TEST PUS...

Page 7: ...HEN ON BATTERIES BATTERY COMMON RECTIFIER CLOSES WHEN RECTIFIER IS RUNNING RECTIFIER COMMON UPS FAILURE CLOSES ON UPS FAILURE UPS COMMON LOW BATTERY CLOSES WHEN BATTERIES ARE LOW LOW BATTERY COMMON OVERLOAD CLOSES WHEN IN OVERLOAD OVERLOAD COMMON AC INPUT L1 OPTION 1 2 3 4 5 7 8 6 9 16 15 14 11 13 12 10 TB1 TERMINAL BLOCK DESCRIPTION LOCATED INSIDE BOX FIGURE 2 0 ...

Page 8: ...CTIFIER IS RUNNING RECTIFIER COMMON UPS FAILURE CLOSES ON UPS FAILURE UPS COMMON LOW BATTERY CLOSES WHEN BATTERIES ARE LOW LOW BATTERY COMMON OVERLOAD CLOSES WHEN IN OVERLOAD OVERLOAD COMMON NOT USED 4 5 7 8 6 9 16 15 14 11 13 12 10 TERMINAL BLOCK DESCRIPTION LOCATED INSIDE BOX FIGURE 2 1 INTERNAL POWER SUPPLY HARDWIRE OPTION AC LINE INPUT L1 AC NEUTRAL INPUT GROUND 3 2 1 17 18 ...

Page 9: ... BATTERY COMMON 9 RECTIFIER 10 RECTIFIER COMMON 11 UPS FAILURE 12 UPS COMMON 13 LOW BATTERY 14 LOW BATTERY COMMON 15 OVERLOAD 16 OVERLOAD COMMON 1 AC INPUT L1 OPTION BATTERY ARRANGEMENT TERMINAL BLOCK LABELS 6 6 312 Ø MOUNT HOLES CIRCUIT BOARD BATTERY HOLDER INPUT PLUG INPUT TRANSFORMER 12 VOLT DC OUTPUT FIGURE 3 0 ...

Page 10: ...WER SUPPLY HARDWIRE OPTION BATTERY ARRANGEMENT 11 RECTIFIER 15 LOW BATTERY 14 UPS COMMON 13 UPS FAILURE 17 OVERLOAD 18 OVERLOAD COMMON 16 LOW BATTERY COMMON 12 RECTIFIER COMMON 3 GROUND 7 INVERTER 6 BYPASS COMMON 4 NOT USED 9 ON BATTERIES 10 BATTERY COMMON 8 INVERTER COMMON 5 BYPASS 2 AC NEUTRAL INPUT 1 AC LINE INPUT L1 ...

Page 11: ...ULT OVERLOAD INPUT FAILURE ALARM SILENCE INTERNAL MONITOR BATTERY TEST MONITOR RESET MONITOR TEST OUTPUT BYPASS INPUT 1 50 1 50 1 50 4 00 6 00 6 00 1 00 1 00 Ø 0 312 MOUNT HOLES KNOCKOUT FOR 1 2 EMT CONDUIT TYP TOP AND BOTTOM KNOCKOUT FOR 1 2 EMT CONDUIT REAR VIEW FRONT VIEW TOP VIEW FIGURE 4 ...

Page 12: ...ble Item 3 Rectifier On Battery Operation Selectable Item 4 On Batteries Load on Inverter Selectable Item 2 Load on Inverter Common Common Load on Bypass Selectable Item 1 Load on Bypass 02 15 00 Tom Kobayashi U 23026 1 1 Remote Status Alarm Panel RSAP Interconnect Diagram 2033 A Analog External Terminal Strip in UPS Terminal Strip TB1 in Remote Status Alarm Panel 16 awg twisted pair recommended N...

Page 13: ...ailure UPS Failure Common Common Converter Operation Rectifier On Battery Operation On Batteries Load on Inverter Load on Inverter Common Common Common Common Load on Bypass Load on Bypass 03 10 98 Mario Recine U 23028 1 1 Remote Status Alarm Panel RSAP Interconnect Diagram 2033 A DDC External Terminal Strip in UPS Terminal Strip TB1 in Remote Status Alarm Panel 14 awg shielded wire recommended No...

Page 14: ...ter Operation Common Rectifier On Common Converter Operation Rectifier On Battery Operation On Batteries Load on Inverter Common Load on Inverter Battery Operation Common On Batteries Common Load on Bypass Common Load on Bypass Common Load on Bypass Load on Bypass 02 15 00 Tom Kobayashi U 23C012 1 1 Remote Status Alarm Panel RSAP Interconnect Diagram 2033 C External Terminal Strip in UPS Terminal ...

Page 15: ...mon Battery Operation Converter Rectifier Operation Load on Inverter Common Load on Inverter 8 29 03 Carl E Luecht U 23D019 1 1 Remote Status Alarm Panel RSAP Interconnect Diagram 2033D 9800AD External Terminal Strip TN1 Output in UPS Terminal Strip TB1 in Remote Status Alarm Panel 6 Load on Bypass Load on Bypass Common Bypass Common 16 15 14 13 12 11 10 9 8 7 6 5 Overload Common Overload Low Batt...

Page 16: ...S Failure UPS Failure Common Common Converter Operation Rectifier On Battery Operation On Batteries Load on Inverter Load on Inverter Common Common Common Common Load on Bypass Load on Bypass 10 21 97 Mario Recine U 97017 1 1 Remote Status Alarm Panel RSAP Interconnect Diagram 9700 External Terminal Strip in UPS Terminal Strip TB1 in Remote Status Alarm Panel 14 awg shielded wire recommended Note ...

Page 17: ...ation Rectifier Operation Load on Inverter Common Load on Inverter Common Load on Inverter 07 09 99 Mario Recine U 98015 1 1 Remote Status Alarm Panel RSAP Interconnect Diagram 9800A External Terminal Strip in UPS Terminal Strip TB1 in Remote Status Alarm Panel 18 17 Load on Bypass Load on Bypass Common Load on Bypass Common Load on Bypass 16 15 14 13 12 11 10 9 8 7 6 5 Output Overload Common Outp...