background image

MODBUS

®

TCP Communication Unit for Energy Measuring Unit (EMU4-FD1-MB) 

Model EMU4-CM-MT

User's Manual

Before using the product, please read this manual carefully to ensure correct use.

Make sure that the end users read this manual and then keep the manual in a safe place for future reference.

Make sure to deliver this manual to the end-user.

About this manual
You can download User's manual of this Unit from the following site.
http://www.mitsubishielectric.co.jp/haisei/lvs/downloads/handling.htm

1. Features

This Unit is the optional dedicated product for Energy Measuring Unit (EcoMonitorLight Model: EMU4-FD1-MB)

This Unit enables to transfer measured data to programmable controllers for data acquisition via MODBUS

®

TCP communication. 

2. Checking package content

These following items for this device are included in package. Check that no items are missing.
  (1) MODBUS

®

TCP  Communication Unit

  

×1             (2) User’s manual  ×1

 

3. Safety Precautions

3.1 Precautions for Operating Environment and Conditions

This Unit is premised on being used in pollution degree II environment. When used in higher pollution degree, protect this Unit from pollution on another device side to be incorporated. 
For the definition of the pollution degree and the over voltage category, refer to EN61010-1/2010.
Do not use this product in the places listed below. Failure to follow the instruction may cause malfunctions or decrease of product-life. 

Places the Ambient temperature exceeds the range

 

-5-+55°C

Dust, corrosive gas, saline and oil smoke exist

Places the Relative humidity exceeds the range 30-85% or places with dewfall

Places exposed to rain or water drop

Operating altitude exceeds 2000m 

Vibration and impact exceed the specifications

Places metal fragments or conductive substance are flying

Places the average daily temperature e35°C 

Places in strong electromagnetic field or places large amounts of external noise exist

Places exposed to direct sunlight

This unit is the open type device, which are designed to be housed within another device for prevention of electric shock. House this unit within the device such as the control panel 
before use. (Indoor use)

3.2 Matters concerning the precaution before use

Use the Unit in the specified usage environment and conditions.

Before using this Unit, set MODBUS

®

TCP IP address, Subnet mask, Default gateway existence and Default gateway address.

  ※

Please refer to “user’s manual of EMU4-FD1-MB”.

 

3.3 Installation Precautions

For installation and wiring works, make sure that the power source is shut off for all outside phases. 

  If all phases are not turned off, it may cause an electric shock or product damages.

Any person who is involved in installation and wiring of this Unit should be fully competent to do this work.

Work under the electric outage condition when installing and wiring. Failure to do so may cause electric shock or a failure of the Unit, a fire etc.

In 100Mbps communication by the 100BASE-TX connection, a communication error may occur under the influence of high frequency noise from devices other 

  than this device in the installation environment. 

Take the following action to prevent the influence of high frequency noise in the construction of a network system.

(1) Wiring connection

  ・

Do not install a twisted pain cable together with the main circuit and power cables, etc.

  ・

Place the twisted pair cable in a duct.

(2) Communication system

  ・

Increase the number of communication retries if necessary.

  ・

Change the hub used for connection into a 10Mbps hub, and make communication at a transmission speed of 10Mbps. 

3.4 Precautions for Use

Before operating the product, check that active bare wire and so on does not exist around the product. If any exposed conductor is found, stop the operation immediately and take 

  an appropriate action such as isolation protection

In the event of a power outage during the setting, the Unit is not set correctly. Please set again after power recovery. 

When you connect to Energy Measuring Unit of the Unit, Contrast of the LCD display of Energy Measuring Unit is reduced to small.

Do not touch the live part. It may cause electric shock, electric burn injury or burnout of the device.

・Work 

under the electric outage condition when installing and wiring.

Do not disassemble or modify this Unit It may cause failure, malfunction, injury or fire.

Do not touch the MODBUS

®

TCP communication connectors when communicating. It may cause a malfunction or failure of the Unit. 

Push the RESET switch with an appropriate force (1.6N). The addition of force than necessary, it may cause a malfunction or failure of the Unit.

3.5 Maintenance Precautions

Use a soft dry cloth to clean off dirt of the Unit surface. Do not let a chemical cloth remain on the surface for an extended period of time nor wipe the surface with thinner or benzene.

Check for the following items to use this Unit properly for long time.

(1) No damage on this Unit
(2) No abnormality with LED indicators

(3) No abnormal noise, smell or heat
(4) No looseness with installation and wire connection

(Check item No.4 under the power failure condition. Failure to do so may cause electric shock, failure of the Unit or a fire.) 

3.6 Storage Precautions

To store this Unit, put it in a plastic bag. For long-time storage, avoid the following places. Failure to follow the instruction may cause a failure and reduced life of the Unit.

Places the ambient tempe rature exceeds the range -10-+60°C

Places the average daily temperature e35°C 

Places exposed to rain, water drop or direct sunlight

Places the Relative humidity exceeds the range 30-85% or places with dewfall

Vibration and impact exceed the specifications

Places metal fragments or conductive substance are flying

Places where dust, corrosive gas, saline and oil smoke exist 

3.7 Disposal Precautions

When disposing of this Unit, treat it as industrial waste. 

3.8 About packaging materials and this manual

For reduction of environment load, packaging materials are produced with cardboard, and this manual is printed on recycled paper. 

If you are considering using this module for special purpose such as nuclear power plants, 
aerospace, medical care or passenger vehicles please refer to our sales representative.

1)
2)
3)
4)

LED
Connector for MODBUS

®

TCP communication

IEC rail stop
Connection stop

Operation status of MODBUS

®

TCP communication is displayed.

10BASE-T/100BASE-TX connector (RJ45)
This is used to fix to an IEC rail.
This is used to connect the MODBUS®TCP communication Unit to the Energy Measuring Unit.

5. How to wire

6. Mounting the Unit

Connect the MODBUS

®

TCP communication Unit to the Energy Measuring Unit. 

*This unit can be attached to EcoMonitorLight in below.

There are two mounting methods, surface mounting and panel mounting.

(1) Remove the blank label stuck to the side of 
 

the Energy Measuring Unit.

(2) Insert the connector of the MODBUS

®

TCP communication 

 

Unit into the connector of the Energy Measuring Unit and 

 

make these Units closely-attached.

(3) Slide the connection stops (green-colored) of upper 
 

and lower of the MODBUS

®

TCP communication 

 

Unit to lock it.

 

6.1 Mounting the Unit on an IEC rail

4. Name and function of each part

<Name and function of each part>

Front view

Left-side view

Back view

1)

2)

4)

4)

3)

Work under the electric outage condition when connecting the Energy Measuring Unit. Failure to do so may cause electric shock, a failure of the Unit, a fire etc.   

CAUTION

CAUTION

CAUTION

DANGER

CAUTION

DANGER

<Daily maintenance>

Name of part

Functions

No.

*This unit can be attached to EcoMonitorLight in below. This unit can be attached to EcoMonitorPlus as well.

More than 7.3

35

1

27

Applicable IEC rail

Mounting

How to remove

(1) Hold the module and pull the stopper 
 

of IEC rail down. 

(1) Hold the module and pull the 
 

stopper of IEC rail down. 

(4) Push the stopper of 
 

the IEC rail above.

(2) Hook on the rail

(2) Pull tha module

IEC rail

(3) Push the Unit

Blank label

DISP

+/PHASE

−/RESET

SET

Model

EMU4-FD1-MB